GENERAL NOTES:
1. STRUCTURE PROXIMITY LOADING DISCLAIMER:
STORMTRAP MODULES AND FOUNDATION ARE NOT DESIGNED TO ACCEPT ANY ADDITIONAL LOADING FROM ANY NEARBY STRUCTURES NEXT TO OR OVER THE TOP OF STORMTRAP. EXAMPLES OF NEARBY STRUCTURES MAY INCLUDE BUT ARE NOT LIMITED
TO BUILDINGS, FOUNDATION ELEMENTS, RETAINING WALLS, LIGHT POLES, BOLLARDS, SIGNPOSTS, FENCES. ADDITIONALLY, STORMTRAP IS NOT RESPONSIBLE FOR INSTALLATION CONFLICTS ARISING FROM ANY OF THESE NEARBY STRUCTURES. IF ADDITIONAL
LOADING CONSIDERATIONS ARE REQUIRED FOR STRUCTURAL DESIGN OF STORMTRAP, PLEASE CONTACT STORMTRAP IMMEDIATELY. FOR LIGHT POLES SHOWN OVER THE TOP OF THE SYSTEM, STORMTRAP WILL PROVIDE A 5'-0" LATERAL DISTANCE CAVITY
AROUND THE LIGHT POLE TO ACCOMMODATE IT. THE FOR TO TAKE RESPONSIBILITY FOR ENSURING THE LIGHT POLE IS NOT INFLICTING ANY LOADING ON THE STORMTRAP MODULES AND FOUNDATION.
2. TREE LOADING DISCLAIMER:
THE NUMBER OF TREES OR WEIGHT OF TOTAL PLANT MATERIAL PRESENT ON TOP OF A SINGLE STORMTRAP MODULE SHALL NOT EXCEED 16,000 LBS. THE REQUIREMENTS LISTED HERE APPLY AT BOTH THE TIME OF INSTALLATION AND FOR THE LIFE
OF THE TREES AND PLANTS IN QUESTION. THE FOR AND LANDSCAPE ARCHITECT ARE RESPONSIBLE FOR ENSURING THAT TREE AND OTHER PLANT ROOTS DO NOT INTERFERE WITH OR COMPROMISE THE FUNCTIONAL AND STRUCTURAL INTEGRITY OF
STORMTRAP'S UNDERGROUND MODULES. APPROPRIATE MEASURES SHOULD BE TAKEN TO PREVENT ROOT GROWTH INTO THE STORMTRAP SYSTEM FROM ADJACENT OR OVERHEAD TREES. FURTHERMORE, THE ROOTS OF THE TREES MUST BE CONTAINED TO
PREVENT FUTURE DAMAGE TO THE STORMTRAP SYSTEM. STORMTRAP ACCEPTS NO LIABILITY FOR DAMAGES CAUSED BY TREES OR OTHER VEGETATION PLACED AROUND OR ON TOP OF THE SYSTEM.
3. PRE-TREATMENT/SEDIMENT/FILTER CHAMBER DISCLAIMER:
FOR SYSTEMS CONTAINING PRE-TREATMENT, SEDIMENTATION AND/OR FILTER CHAMBERS; IF REQUIRED TO BE SEALED TO PREVENT SAND AND/OR PRE-TREATED WATER FROM MIGRATING INTO ADJOINING MODULES, IT IS THE SOLE RESPONSIBILITY OF
THE INSTALLING CONTRACTOR TO ENSURE THAT THOSE MODULES ARE SEALED.
4. OUTLET CONTROL STRUCTURE DISCLAIMER (IF SHOWN ON THESE PLANS):
IF A WATERTIGHT SOLUTION IS REQUIRED FOR AN OUTLET CONTROL STRUCTURE, ALL EXTERIOR COLD JOINTS, INCLUDING JOINT BETWEEN TOP AND BASE MODULES, BETWEEN TOP AND BASE OF ADJOINING SYMONS WALLS, AND JOINTS BETWEEN MODULE
AND ADJACENT END PANELS WILL BE THE SOLE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO PROVIDE AND INSTALL THE WATERTIGHT APPLICATION PER THE EOR'S SPECIFICATION.
BILL OF MATERIALS
OTY.
UNIT TYPE
DESCRIPTION
TOP WEIGHT
BASE WEIGHT
27
I
10'-0" DOUBLETRAP
15493
15291
1
II
10'-0" DOUBLETRAP
17906
17704
15
III
10'-0" DOUBLETRAP
15412
15311
2
IV
10'-0" DOUBLETRAP
16618
16517
5
SPIV
10'-0" DOUBLETRAP
<16618
<16517
4
T2 PANEL
8" THICK PANEL
9258
7
T4 PANEL
8" THICK PANEL
7288
12
POINT WRA
150' PER ROLL
48
POINT TAPE14.5'
PER ROLL
TOTAL PIECES = 100
TOTAL PANELS = 11
HEAVIEST PICK WEIGHT = 17906
A
B
C
D
E
F
G 18"0 OPENING
12" HDPE f
INVERT-"
H
18"0 OPENING
12" HDPE I
J INVERT=45:
DESIGN CRITERIA
ALLOWABLE MAX GRADE = 457.64'
ALLOWABLE MIN GRADE = 455.39'
INSIDE HEIGHT ELEVATION = 453.50'
SYSTEM INVERT=443.50'
NOTES:
1. DIMENSIONING OF STORMTRAP SYSTEM SHOWN BELOW ALLOW FOR A 3/4" GAP BETWEEN EACH MODULE.
2. ALL DIMENSIONS TO BE VERIFIED IN THE FIELD BY OTHERS.
3. SEE SHEET 3.0 FOR INSTALLATION SPECIFICATIONS.
4. SP - INDICATES A MODULE WITH MODIFICATIONS.
5. P - INDICATES A MODULE WITH A PANEL ATTACHMENT.
6. CONTRACTORS RESPONSIBILITY TO ENSURE CONSISTENCY/ACCURACY TO FINAL ENGINEER OF RECORD PLAN SET.
7. IN ORDER FOR STORMTRAP TO GENERATE APPROVAL DRAWINGS, CIVIL ENGINEERING DRAWINGS MUST BE PROVIDED TO STORMTRAP
AND SHALL INCLUDE ALL PIPE SIZES, PIPE MATERIAL, PIPE INVERT ELEVATIONS, ACCESS OPENING SIZE AND SHAPE. IN ADDITION,
FINAL GRADING PLANS SHALL ALSO INCLUDE MINIMUM AND MAXIMUM GRADES OVER THE TOP OF THE STORMTRAP SYSTEM.
1 2 3 4 5 6 7 8
NOTE: VAULT PENETRATIONS FOR INLET AND OUTLET PIPES,
AND ALL NECESSARY VENTS AND LIDS TO BE COORDINATED
WITH STORMTRAP PRIOR TO ORDER PLACEMENT
43667 9
,isTE4�' 6
IVA1,
1TO
REVISION
StormTrap.
PAM uslm m pn0yVs1a01wmyt m01
1287 WIDHAM PARKWAY
ROIEOVILLE, IL 60446
P.815-941-4549 / F.331 3183347
ENGINEER INFORMATION:
Jacobson Consulting Engineers
255 S. King St.
Suite 800
Seattle, WA 98104
206-426-2600
PROJECT INFORMATION:
Hazen High School
1101 Hoquiam Ave NE
Renton, WA 98059
CURRENT ISSUE DATE:
6/12/2025
ISSUED FOR:
CONSTRUCTION
REV.
DATE:
ISSUED FOR:
BY:
)0(/XX/XX
CONSTRUCTION
DG
5
5/19/2025
APPROVAL
SB
4
5/13/2025
APPROVAL
SB
3
3/19/2025
PRELIMINARY
ZM
2
2/11/2025
PRELIMINARY
ZM
1
10/25/2D24
PRELIMINARY
DG
SCALE:
NTS
SHEET TITLE:
GENERAL NOTES
SHEET NUMBER:
Lo
StormTrap•
1287 WINGHAM PARKWAY
ROMEOVILLE, IL 60446
P.815-941-4549 / F.331-318-5347
ENGINEER INFORMATION:
Jacobson Consulting Engineers
255 S. King St.
Suite 800
Seattle, WA 98104
206-426-2600
PROJECT INFORMATION:
Hazen High School
1101 Hoquiam Ave NE
Renton, WA 98059
CURRENT ISSUE DATE:
6/12/2025
ISSUED FOR:
CONSTRUCTION
REV.
DATE:
ISSUED FOR.
OWN
XX/XX/XX
CONSTRUCTION
DG
5
5/19/2025
APPROVAL
SB
4
5/13/2025
APPROVAL
SB
3
3/19/2025
PREUMIKARY
ZM
2
2/11/2025
PRELIMINARY
ZM
1
10/25/2024
PRELIMINARY
DG
SCALE:
NTS
SHEET TITLE:
DOUBLETRAP
SYSTEM LAYOUT
SHEET NUMBER:
2.0
STRUCTURAL DESIGN LOADING CRITERIA
LIVE LOADING: AASHTO HS-20 HIGHWAY LOADING
GROUND WATER TABLE: BELOW INVERT OF SYSTEM
SOIL BEARING PRESSURE:3000PSF
SOIL DENSITY: 120 PCF
EQUIVALENT UNSATURATED
LATERAL ACTIVE EARTH PRESSURE:35 PSF / FT.
EQUIVALENT SATURATED
LATERAL ACTIVE EARTH PRESSURE:80 PSF/FT. (IF WATER TABLE PRESENT)
APPLICABLE CODES:ASTM C857
ACI-318
BACKFILL TYPE: SEE SHEET 4.0 FOR BACKFILL OPTIONS
SEE SHEET 4.0 FOR
BACKFILL SPECIFICATIONS
STORMTRAP SYSTEM INFORMATION
UNIT HEADROOM: 10'-0" DOUBLETRAP
TOTAL STORAGE PROV: 52,632.52 CUBIC FEET
STORMTRAP SYSTEM
LIVE STORAGE PROV: 47,369.27 CUBIC FEET
MIN. 3000 PSF BEARING CAPACITY
TO BE VERIFIED IN FIELD BY OTHERS
SITE SPECIFIC DESIGN CRITERIA
1. STORMTRAP UNITS SHALL BE MANUFACTURED AND INSTALLED ACCORDING TO SHOP DRAWINGS APPROVED BY
THE INSTALLING CONTRACTOR AND ENGINEER OF RECORD. THE SHOP DRAWINGS SHALL INDICATE SIZE AND
LOCATION OF ROOF OPENINGS AND INLET/OUTLET PIPE TYPES, SIZES, INVERT ELEVATIONS AND SIZE OF
OPENINGS.
2. COVER RANGE: MIN. 1.39' MAX. 3.64' CONSULT STORMTRAP FOR ADDITIONAL COVER OPTIONS.
3. ALL DIMENSIONS AND SOIL CONDITIONS, INCLUDING BUT NOT LIMITED TO GROUNDWATER AND SOIL BEARING
CAPACITY ARE REQUIRED TO BE VERIFIED IN THE FIELD BY OTHERS PRIOR TO STORMTRAP INSTALLATION.
4. FOR STRUCTURAL CALCULATIONS THE GROUND WATER TABLE IS ASSUMED TO BE BELOW INVERT OF SYSTEM
IF WATER TABLE IS DIFFERENT THAN ASSUMED, CONTACT STORMTRAP.
5. SYSTEM DESIGN INTENT IS TO CONTAIN WATER WITH AN ALLOWABLE LEAKAGE RATE OF 15% OVER A 24-HOUR
PERIOD. A THIRD PARTY WATER -PROOFING SOLUTION IS REQUIRED FOR SEALING OF SYSTEM / MODULE JOINT
AND SEAMS. SOLUTION TO BE PROVIDED AND INSTALLED BY CONTRACTOR IN ACCORDANCE WITH THIRD PARTY
WATER -PROOFING SUPPLIER'S PRODUCT SPECIFICATIONS.
6. WATER TIGHT TEST TO BE A WATER FILL TEST. ALL INLET AND OUTLET PIPES TO BE PLUGGED. AFTER ALL
SIDES OF THE SYSTEM HAVE BEEN BACKFILLED UP TO THE TOP OF THE ROOF SLAB, THE SYSTEM IS TO BE
FILLED WITH WATER TO THE HIGHEST CONNECTION INVERT. 24 HOURS FOLLOWING THE INITIAL FILL,
CONTRACTOR HAS THE OPTION TO REFILL, UP TO THE HIGHEST CONNECTION INVERT. WATER LEVEL DEPTH TO
BE MEASURED 24 HOURS AFTER COMPLETION OF FILL.
IMPERMEABLE LINER AS SPECIFIED
BY ENGINEER. PROVIDED AND
INSTALLED BY OTHERS
---------------- FREEBOARD__--
9,-0.
LIVE
STORAGE
--------- ----6.------
10'-0" DOUBLETRAP
STORMTRAP INSTALLATION SPECIFICATION
1. STORMTRAP SHALL BE INSTALLED IN ACCORDANCE WITH ASTM C891 (STANDARD PRACTICE FOR INSTALLATION OF
UNDERGROUND PRECAST CONCRETE UTILITY STRUCTURES). THE FOLLOWING ADDITIONS AND/OR EXCEPTIONS ARE
PROVIDED FOR EMPHASIS. THE MENTION OF THESE ITEMS DOES NOT PRECLUDE THE INSTALLING CONTRACTOR FROM
FOLLOWING ASTM C891 IN ITS ENTIRETY AND IMPLEMENTING ALL APPROPRIATE MEASURES. THE INSTALLING CONTRACTOR
OWNS AND IS RESPONSIBLE FOR THE STORMTRAP SYSTEM UPON REMOVAL OF THE MODULES FROM THE DELIVERY
TRUCK THROUGH 'FINAL CONSTRUCTION'. FINAL CONSTRUCTION IS ACHIEVED WHEN ALL MODULES ARE SET, FULLY
BACKFILLED, AND WHEN FINAL FINISHED GRADES ARE REACHED. THE CONTRACTOR IS RESPONSIBLE FOR ANY
COUNTERMEASURES NECESSARY TO RESIST UPLIFT/BUOYANCY BEFORE 'FINAL CONSTRUCTION' IS ACHIEVED.
2. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT PROPER/ADEQUATE EQUIPMENT IS USED
TO SET/INSTALL THE MODULES.
3. STORMTRAP MODULES CAN BE PLACED ON A LEVEL, 6" FOUNDATION OF J" AGGREGATE EXTENDING 2'-0" PAST THE
OUTSIDE OF THE SYSTEM (SEE DETAIL 1) AND SHALL BE PLACED ON PROPERLY COMPACTED SOILS (SEE SHEET 1.1
FOR SOIL BEARING CAPACITY REQUIREMENTS), AND IN ACCORDANCE WITH ASTM C891 STANDARD PRACTICE FOR
INSTALLATION OF UNDERGROUND PRECAST UTILITY STRUCTURES.
4. THE STORMTRAP MODULES SHALL BE PLACED SUCH THAT THE MAXIMUM SPACE BETWEEN ADJACENT MODULES DOES
NOT EXCEED }" (SEE DETAIL 2). IF THE SPACE EXCEEDS J", THE MODULES SHALL BE RESET WITH APPROPRIATE
ADJUSTMENT MADE TO LINE AND GRADE TO BRING THE SPACE INTO SPECIFICATION.
5. STORMTRAP MODULES ARE NOT WATERTIGHT. IF A WATERTIGHT SOLUTION IS REQUIRED, CONTACT STORMTRAP FOR
RECOMMENDATIONS. THE WATERTIGHT APPLICATION IS TO BE PROVIDED AND IMPLEMENTED BY THE CONTRACTOR. THE
CONTRACTOR IS RESPONSIBLE TO ENSURE THAT THE SELECTED WATERTIGHT SOLUTION PERFORMS AS SPECIFIED BY THE
MANUFACTURER.
6. THE HORIZONTAL JOINT BETWEEN THE TOP AND BASE LEG CONNECTIONS OF ALL PERIMETER STORMTRAP MODULES
SHALL BE SEALED WITH PREFORMED MASTIC JOINT TAPE ACCORDING TO ASTM C891, 8.8 AND 8.12. (SEE DETAIL 3).
THE MASTIC JOINT TAPE DOES NOT PROVIDE A WATERTIGHT SEAL.
7. ALL EXTERIOR ROOF AND EXTERIOR VERTICAL WALL JOINTS BETWEEN ADJACENT STORMTRAP MODULES SHALL BE
SEALED WITH B" WIDE PRE -FORMED, COLD -APPLIED, SELF -ADHERING ELASTOMERIC RESIN, BONDED TO A WOVEN ,
HIGHLY PUNCTURE RESISTANT POLYMER WRAP, CONFORMING TO ASTM C891 AND SHALL BE INTEGRATED WITH PRIMER
SEALANT AS APPROVED BY STORMTRAP (SEE DETAILS 2, 4, & 5). THE JOINT WRAP DOES NOT PROVIDE A WATERTIGHT
SEAL. THE SOLE PURPOSE OF THE JOINT WRAP IS TO PROVIDE A SILT AND SOIL TIGHT SYSTEM. THE ADHESIVE
EXTERIOR JOINT WRAP SHALL BE INSTALLED ACCORDING TO THE FOLLOWING INSTALLATION INSTRUCTIONS:
7.1. USE A BRUSH OR WET CLOTH TO THOROUGHLY CLEAN THE OUTSIDE SURFACE AT THE POINT WHERE JOINT WRAP
IS TO BE APPLIED.
7.2. A RELEASE PAPER PROTECTS THE ADHESIVE SIDE OF THE JOINT WRAP. PLACE THE ADHESIVE TAPE (ADHESIVE SIDE
DOWN) AROUND THE STRUCTURE, REMOVING THE RELEASE PAPER AS YOU GO. PRESS THE JOINT WRAP FIRMLY
AGAINST THE STORMTRAP MODULE SURFACE WHEN APPLYING.
8. IF THE CONTRACTOR NEEDS TO CANCEL ANY SHIPMENTS, THEY MUST DO SO 48 HOURS PRIOR TO THEIR SCHEDULED
ARRIVAL AT THE JOB SITE. IF CANCELED AFTER THAT TIME, PLEASE CONTACT THE PROJECT MANAGER.
9. IF THE STORMTRAP MODULE(S) IS DAMAGED IN ANY WAY PRIOR, DURING, OR AFTER INSTALL, STORMTRAP MUST BE
CONTACTED IMMEDIATELY TO ASSESS THE DAMAGE AND TO DETERMINE WHETHER OR NOT THE MODULE(S) WILL NEED
TO BE REPLACED. IF ANY MODULE ARRIVES AT THE JOBSITE DAMAGED DO NOT UNLOAD IT; CONTACT STORMTRAP
IMMEDIATELY. ANY DAMAGE NOT REPORTED BEFORE THE TRUCK IS UNLOADED WILL BE THE CONTRACTOR'S
RESPONSIBILITY.
10. STORMTRAP MODULES CANNOT BE ALTERED IN ANY WAY AFTER MANUFACTURING WITHOUT WRITTEN CONSENT FROM
STORMTRAP.
SURVEYED:
DESIGNED:
JAJ
DRAWN:
DJD/AJJ
CHECKED:
JAJ
BY DATE AP P R APPROVED:
JAJ
SCALE:
N/A
ONE INCH
AT FULL SGALE
IF NOT ONE INCH
SCALE ACCORDINGLY
VERTICAL: NAVD 1988
HORIZONTAL: NAD 1983/1991
DATUM
STORMTRAP END PANEL
8" WIDE JOINT N
(SEE NOTI
6 Y,IUL JVIIYI
(SEE N(
TOP OF STORMTRAP
�• I
(SEE .._._
DETAIL 2
CITY OF
RENTON
Planning/Building/Public Works Dept.
5.-0"
5'-D"
ALLOWABLE MAX GRADE = 457.64'
ALLOWABLE MIN GRADE = 455.39'
3.64
�6" INSIDE HEIGHT = 453.50'
ELEV. = 453.00
10'-0" DOUBLETRAP
LEV. = 444.00'
'STEM INVERT = 443.50'
6" STONE BASE
;SEE SHEET 4.0)
DETAIL 3
DETAIL 1
StormTrap•
na00 Us1m a, Dff1PJ/AN~m4V=0
1287 WINCHAM PARKWAY
ROMEOVILLE, IL 60446
P.815-941-4549 / F.331-3183347
ENGINEER INFORMATION:
Jacobson Consulting Engineers
255 S. King St.
Suite 800
Seattle, WA 98104
206-426-2600
PROJECT INFORMATION:
Hazen High School
1101 Hoquiam Ave NE
Renton, WA 98059
CURRENT ISSUE DATE:
6/12/2025
ISSUED FOR:
CONSTRUCTION
EV
DATE:
ISSUED FOR:
BY:
XX/)O(/XX
CONSTRUCTION
DG
5
5/19/2025
APPROVAL
SB
4
5/13/2025
APPROVAL
SB
3
3/19/2025
PREUMINARV
ZM
2
2/11/2025
PREUMINARY
ZM
1
10/25/2024
PRELIMINARY
DO
SCALE:
NTS
SHEET TITLE:
DOUBLETRAP
DESIGN
CRITERIA
SHEET NUMBER:
1.1
StormTrap-
IrseOs Us1m a D4whs140~4m4AriN0
1287 WINDHAM PARIMIAY
ROME(MLLE, IL 60446
P.815-941-4549 / F.331-3183347
ENGINEER INFORMATION:
Jacobson Consulting Engineers
255 S. King St.
Suite 800
Seattle, WA 98104
206-426-2600
PROJECT INFORMATION:
Hazen High School
1101 Hoquiam Ave NE
Renton, WA 98059
CURRENT ISSUE DATE:
6/12/2025
ISSUED FOR:
CONSTRUCTION
REV.
DATE:
ISSUED FOR:
BWN
XX/XX/XX
CONSTRUCTION
DG
5
5/19/2025
APPROVAL
SB
4
5/13/2025
APPROVAL
SB
3
3/19/2025
PRELIMINARY
ZM
2
2/11/2025
PRELIMINARY
ZM
1
10/25/2D24
PRELIMINARY
DG
SCALE:
NTS
SHEET TITLE:
DOUBLETRAP
STONE BASE
(SEE NOTE 3) INSTALLATION
(
SPECIFICATION
I" OVERHANG SHEET NUMBER:
:E NOTE 3)
30
NTS
StormTrap Details R-432636
IN COMPLIANCE WITH CITY OF RENTON STANDARDS
DEVELOPMENT ENGINEERING
msippo 08/07/2025
HAZEN HIGH SCHOOL MODERNIZATION
DRAINAGE DETAILS
07.1 1 .2025
PAGE:
C316