2" x 14" REDUCING
314" ROMEX
W.
FRONT VIEW
ROMEX CONNECTION
WITH LOCKNUT
REDUCING
WASHER
C%lr)C VICIAl
ARM, SEE STD DETAIL 117.3
LUMINAIRE ARM SIDE VIEW
��Y o STRAIN RELIEF- DETAIL STD. PLAN— 118
�' o � PUBLIC WORKS
+ + APPROVED:
DEPARTMENT sp4/4/2024
F N 1 DATE
1 4:2
1TV]
DocuSign Envelope ID: 9D9BODA8-0385-4664-AE66-57BFF1561D7F �CKET CABLE, #10
AWG. SPLICES BETWEEN FUSE
HOLDER AND LUMINAIRE FIXTURE
SHALL NOT BE ALLOWED
FUSE KITS QUICK DISCONNECT 3 AMP
IN LINE FUSE KITS S.E.C. OR EQUAL,
ONE PER CURRENT CARRYING
REFER TO WSDOT LOCKING CONDUCTOR. APPLIES TO LUMINAIRE
LID STANDARD DUTY AND RECEPTACLE WIRING ----x
JUNCTION BOX TYPES 1 &
2 STANDARD PLAN J-40.10
SPLICE KITS CLEAR EPDXY SPLICE
KITS ON ALL THRU WIRE RUNS —
CONCRETE PAD OR
SIDEWALK PER STD PLAN 120 —�
24 (MIN) COVER #8 BARE COPPER
GROUND WIRE
GROUND LUG
GROUND 11
CLAMP II
2" PVC CONDUIT
TO LUMINAIRE
/TO RECEPTACLE
120VAC RECEPTACLE WIRING, IF
APPLICABLE. WIRING SIZE PER
CONTRACT
TO LUMINAIRE
-GREEN INSULATED WIRE, SIZED
TO MATCH THE LARGEST
CURRENT CARRYING CONDUCTOR.
TERMINATE AT LUMINAIRE
GROUND LUG
UFER GROUND,
NON —INSULATED #4 AWG
STRANDED COPPER,
PROVIDE 3' MIN. SLACK.
ROUTE FROM GROUNDING
1 — EQUIPMENT GROUNDLL=1 Iii LUG TO
"
WIRE W/GREEN INSULATION REBAR. CONNEECTIOTO
FROM SERVICE CABINET, REBAR USING AN ACORN
SEE NOTE 2, THIS SHEET 5/CLAMP
GROOUN
2 — LIGHTING SYSTEM UN D ROD COPPER CLAD CONCRETE FOUNDATION
WIRES TO CONTACTOR
(SIZED AS REQ'D.)
2 — 120VAC RECEPTACLE SYSTEM
WIRES TO SERVICE CABINET, IF
APPLICABLE (SIZED AS REQ'D.)
NOTES:-
1 . THIS DETAIL DEPICTS THE BASIC LUMINAIRE ELECTRICAL WIRING SYSTEM. ADDITIONAL ELECTRICAL EQUIPMENT MAY VARY.
2. MINIMUM GROUND WIRE SIZE SHALL BE #8, AS SHOWN ABOVE. IF CURRENT CARRYING CONDUCTORS ARE LARGER THAN
#8, THE MINIMUM GROUND WIRE SIZE SHALL MATCH THE LARGEST WIRE SIZE OF THE CURRENT CARRYING CONDUCTORS.
3. EQUIPMENT GROUND WIRE & BARE WIRE SHALL BE SECURELY FASTENED TO THE GROUND LUG INSIDE THE POLE
HANDHOLE. ALL BONDING & GROUNDING CONNECTIONS SHALL REMAIN ACCESSIBLE FOR INSPECTION AND MAINTENANCE.
4. IF THE FIXTURE MANUFACTURER HAS MADE PROVISIONS FOR THE ATTACHMENT OF A GROUND WIRE, A GREEN INSULATED
WIRE, SIZED TO MATCH THE LARGEST CURRENT CARRYING CONDUCTORS, SHALL BE RUN FROM THE FIXTURE TO THE POLE
GROUND LUG.
5. ALL CONDUIT SHALL BE PVC SCHEDULE 80.
c Y LUMINAIRE ELECTRICAL
�'\ �� PUBLIC WORKS WIRING SYSTEM STD. PLAN — 119
. ° . APPROVED: Martin
DEPARTMENT •Pastucha 7/27/2022
'p� ��
N
DATE
N.112IMM •►
i �-
SURVEYED:
DESIGNED:
NS
DRAWN:
NS
CHECKED:
BP
AP P R APPROVED:
BP
SCALE:
NONE
ONE INCH
AT FULL SCALE
IF NOT ONE INCH
SCALE ACCORDINGLY
VERTICAL* NAVD 1988
HORIZONTAL NAD 1983/1991
Alf�
DATUM
DocuSign Envelope ID: 9D9BODA8-0385-4664-AE66-57BFF1561D7F
7'-0"
0
C
e�
0 0
MIN. MIN.
LUMINAIRE POLE JUNCTION BOX
CONCRETE PAD,
PLAN VIEW BROOM FINISH
LUMINAIRE POLE
CONCRETE PAD
4"
JUNCTION BOX
LUMINAIRE CONCRETE
FOUNDATION
SIDE VIEW
LUMINAIRE CONCRETE PAD DETAIL
GENERAL NOTES:
1. LUMINAIRE CONCRETE PAD SHALL BE USED IN AREAS
OUTSIDE OF SIDEWALK
2. CONCRETE CLASS FOR LUMINAIRE CONCRETE PAD SHALL
BE PER STD PLAN 135
3. TOP OF LUMINAIRE FOUNDATION ELEVATION SHALL BE
LOCATED AT BOTTOM OF LUMINAIRE CONCRETE PAD
ELEVATION OR BOTTOM OF SIDEWALK ELEVATION
4. LUMINAIRE POLE AND JUNCTION BOX TYPE PER PLAN
5. LUMINAIRE CONCRETE PAD ACCOMMODATES TYPE 1 AND
TYPE 2 JUNCTION BOXES ONLY
LUMINAIRE POLE JUNCTION BOX
CONCRETE SIDEWALK
PLAN VIEW PER STD PLAN 102
LUMINAIRE POLE
CONCRETE SIDEWALK
PER STD PLAN 102
JUNCTION BOX
LUMINAIRE CONCRETE
FOUNDATION
SIDE VIEW
LUMINAIRE WITH SIDEWALK DETAIL
CONCRETE PAD
JUNCTION BOX
/ PLAN VIEW
4"
CONCRETE PAD �I
JUNCTION BOX SIDE VIEW
INDIVIDUAL JUNCTION BOX PAD DETAIL
Y a� LUMINAIRE CONCRETE STD. PLAN — 120
� PUBLIC WORKS PAD/SIDEWALK AND APPROVED:
p z DEPARTMENT JUNCTION BOX CONCRETE PAD Martin Pastucha 7/27/2022
N 1 DATE
CITY OF
IR RENTON
•
Planning/Building/Public Works Dept.
T-432620
IN COMPLIANCE WITH CITY OF RENTON STANDARDS
TRANSPORTATION OPERATION
cbarnes 08/07/2025 '
HAZEN HIGH SCHOOL MODERNIZATION
ELECTRICAL DETAILS
DATE:
07.11.25
PAGE:
E902
SHEET: OF:
73 OF 76