COPPER WIRING SCHEDULE
CONDUIT WIRE
2" SCH 80 2#8
2" SCH 80 LOCATE WIRE ONLY
2" SCH 80 3#2 (POWER)
rnnnnnFNT.
WITH #8 GROUND WIRE
FUTURE STREET LIGHT
TO PSE 240V VAULT
2" SCH 80 1 LOCATE WIRE ONLY I SPARE
LIGHT FIXTURE SCHEDULE
LOCATION OF MANUFACTURER
LUMINAIRE
LUMEC STREET LIGHT: TR20 80W48LED 4K LE3F UNV BKTX (SEE
STANDARD PLAN 117.1, 117.1A, 117.2)
SE LUMEC PED LIGHT: TR20 35W32LED 4K LE3F UNV BKTX (SEE
PETROVITSKY STANDARD PLAN 117.1, 117.1A, 117.2)
ROAD POLE: 40' TAPERED ALUMINUM WITH BASE COVER (SEE STANDARD
PLAN 117.1, 117.1 A)
CLAMP -ON BRACKET (4'): (SEE STANDARD PLAN 117.3)
CLAMP -ON BRACKET (8'): (SEE STANDARD PLAN 117.3)
LEGEND
ARTERIAL STREET LIGHT POLE, LUMINAIRE, JUNCTION BOX &
FOUNDATION. REFERENCE CITY OF RENTON STANDARD PLANS
ON SHEETS SL3 AND SL4 AND STREET LIGHT SCHEDULE ON SHEET
SL1. IN ADDITION, REFERENCE SECTION 4-6-060 (1) (ILLUMINATION)
OF THE CITY OF RENTON GUIDELINES & STANDARDS FOR STREET
LIGHTING DESIGN OF RESIDENTIAL AND ARTERIAL STREET. (ORD.
SL1
5517, 12-14-2009; ORD. 5675, 12-3-2012)
EXISTING PSE LUMINAIRE
EX1, EX2
JUNCTION BOX WITH ANTI SLIP LOCKING LID. (SEE WSDOT TYPE 1
J-40.10-02 STANDARD DWGS). PROVIDE 1" TACK WELDS AT BOTH
ENDS OF THE J-BOX LID
JUNCTION BOX WITH ANTI SLIP LOCKING LID. (SEE WSDOT TYPE 2
a
J-40.10-02 STANDARD DWGS). PROVIDE 1" TACK WELDS AT BOTH
ENDS OF THE J-BOX LID
-
UNDERGROUND CONDUIT & WIRE
Q
CONDUIT/WIRE RUN NUMBER. SEE SCHEDULES ON SHEET SL1
FOR ADDITIONAL INFORMATION
SERVICE CABINET & FOUNDATION REFERENCE CITY OF RENTON
STANDARD PLANS ON SHEET SL3 AND SL4
STREET LIGHT SCHEDULE
STREET POLE ID EASTING NORTHING STATION OFFSET MOUNTING ARM
LIGHT NO. STREET NO. ** ** ** HEIGHTS LENGTHS CIRCUIT TYPE/WATT/DIST. LUMINAIRE TYPE BASE
EX1 SE PETROVITSKY ROAD EXISTING PSE POLE,ARM AND LUMINAIRE
EX2 SE PETROVITSKY ROAD EXISTING PSE POLE,ARM AND LUMINAIRE
SL1 SE PETROVITSKY ROAD 4+87 32.8' LT 35-6" / 16-6" 8' STREET/ 1 LED/80W/TYPE III SEE FIXTURE SCHEDULE FIXED
4' SIDEWALK LED/35W/TYPE III THIS SHEET
STATIONS/OFFSETS ARE APPROXIMATE. CONTRACTOR SHALL CONFIRM ANY ADJUSTMENTS WITH ALL TRADES AND ENGINEER PRIOR TO IMPLEMENTING.
** POLE ID, EASTING AND NORTHING VALUES SHALL BE PROVIDED BY ERIC CUTSHALL (CITY OF RENTON) FOR INCORPORATION INTO AS -BUILD PLANS AND INSTALLED BY THE
CONTRACTOR IN ACCORDANCE WITH COR STD PLAN 121.
TRES WEST ENGINEERS, INC.
2702 SOUTH 42ND STREET, SUITE 301
tj vv TACOMA, WA 98409-7315
w Phone:253.472.3300
Q TRES WEST www.treswest.com
w ENGINEERS
` ViNAL
4/2/2025
1 1 CITY OF RENTON REVISIONS (2/2f
NO. I REVISION
SURVEYED:
DESIGNED:
DPH
DRAWN:
DPH
DPH 4/2/25 JCM CHECKED:
JCM
BY I DATE I APPR APPROVED: JCM
GENERAL NOTES
1. ELECTRICAL CONTRACTOR TO FIELD VERIFY AND
COORDINATE EXACT LOCATION OF LIGHT POLES AND
JUNCTION BOXES PRIOR TO ROUGH -IN. LIGHT POLES AND
JUNCTION BOXES SHALL BE LOCATED OUT OF DRIVEWAYS.
IN ADDITION, COORDINATE WITH ALL WATERLINES,
METERS, SEWER, STORM AND TREE LOCATIONS WHERE
APPLICABLE PRIOR TO ROUGH -IN.
STREET LIGHT CONSTRUCTION
1. ALL WORKMANSHIP, MATERIALS AND TESTING SHALL BE IN
ACCORDANCE WITH WSDOT STANDARDS SPECIFICATIONS
AND NATIONAL ELECTRICAL CODE (NEC).
2. ELECTRICAL PERMITS AND INSPECTIONS FROM CITY OF
RENTON ARE REQUIRED FOR ALL STREET LIGHTING
INSTALLATIONS WITHIN THE CITY OF RENTON. THE
CONTRACTOR IS RESPONSIBLE FOR OBTAINING PERMITS
PRIOR TO CONSTRUCTION. THESE PERMITS ARE
AVAILABLE FROM THE ELECTRICAL PERMIT COUNTER AT
CITY OF RENTON DEVELOPMENT SERVICES DIVISION 1055
SOUTH GRADY WAY, RENTON, WA 98057. PRIOR TO
INSTALLATION OF ANY MATERIALS THE ELECTRICAL
CONTRACTOR SHALL SUBMIT A COPY OF THE ELECTRICAL
PERMIT AND THE APPROVED PLANS AND DOCUMENTATION.
3. MODIFICATIONS OF ANY PORTION OF THE LIGHTING
SYSTEM ARE PROHIBITED WITHOUT PRIOR APPROVAL BY
THE CITY.
4. LIGHTING SERVICE CABINET SHALL BE PER CITY OF
RENTON STANDARD PLANS. SEE SHEET SL4.
5. SERVICE ENTRANCE CONDUCTORS SHALL BE A MINIMUM
SIZE OF #2 COPPER. ALL LIGHTING WIRE SHALL BE
STRANDED COPPER WITH A MINIMUM SIZE OF #8 WITH
INSULATION SUITABLE OF WET LOCATIONS. PHASING TAPE
WILL NOT BE ALLOWED.
6. ALL WIRE SHALL BE INSTALLED IN SCHEDULE 80 PVC
CONDUIT WITH A MINIMUM DIAMETER OF 2". SCHEDULE 80
PVC OR GALVANIZED STEEL CONDUIT SHALL BE INSTALLED
UNDER ROADWAYS. ALL CONDUIT SHALL BE INSTALLED IN
THE "UTILITY DITCH" OR AS OTHERWISE DIRECTED BY THE
CITY.
7. ALL SPLICES SHALL BE IN THE THE NEAREST JUNCTION
BOX. WIRE NUTS WILL NOT BE ALLOWED. ALL SPLICES
WILL BE MADE WITH TYPE C COPPER FITTINGS, CENTERED
AND ENCASED IN A 3-M SCOTCHCAST EPDXY KIT, RATED AT
600 VOLTS, TYPE 82-A1, 82-B1 OR CITY APPROVED EQUAL.
8. IF MORE THAN ONE CIRCUIT PASSES THROUGH A JUNCTION
BOX, EACH IS TO HAVE A PVC SLEEVE CLEARLY
IDENTIFYING THE CIRCUIT. A 500-VOLT MEGGER TEST WILL
BE PERFORMED BY THE ELECTRICAL CONTRACTOR ON
EACH CIRCUIT BETWEEN CONDUCTOR AND GROUND PRIOR
TO ACCEPTANCE OF THE LIGHTING SYSTEM. THE
INSULATION RESISTANCE SHALL NOT BE LESS THAN 6
MEGA -OHMS TO GROUND 2,500 FEET AND OVER AND SHALL
NOT BE LESS THAN 8 MEGA -OHMS UNDER 2,500 FEET. A
FUNCTIONAL TEST SHALL BE PERFORMED TO THE
SATISFACTION OF THE CITY, IN WHICH IT IS
DEMONSTRATED TO THE CITY THAT EACH AND EVERY PART
OF THE SYSTEM FUNCTIONS AS SPECIFIED OR INTENDED
HEREIN.
SCALE:
1 "=20'-0"
ONE INCH
AT FULL SCALE
IF NOT ONE INCH
SCALE ACCORDINGLY
VERTICAL: NAVD 1988
HORIZONTAL: NAD 1983/1991
DATU M
• C TY OF
RENTON
•
Planning/Building/Public Works Dept.
9. EACH LUMINAIRE POLE SHALL HAVE AN SEC IN -LINE, FUSED,
WATER TIGHT ELECTRICAL DISCONNECT LOCATED AT THE
BASE OF THE POLE. ACCESS TO THESE DISCONNECTS
SHALL BE THROUGH THE HAND -HOLE ON THE POLE. THE
HAND -HOLE SHALL BE FACING AWAY FROM ONCOMING
TRAFFIC FROM THE ADJACENT STREET. LOAD SIDE OF
IN -LINE FUSE TO LUMINAIRE HEAD SHALL BE POLE AND
BRACKET CABLE, TWO CONDUCTOR, 19 STRAND COPPER
#10 AND SHALL BE SUPPORTED AT THE END OF THE
LUMINAIRE ARM BY AN APPROVED MEANS. FUSE, SIZE,
DISCONNECT INSTALLATION AND GROUNDING IN POLE
SHALL CONFORM TO WSDOT STANDARDS.
10. JUNCTION BOXES SHALL BE INSTALLED PER WSDOT
STANDARD PLAN J-40.10-03 IN ALL STREET LIGHTING
INSTALLATIONS. ALL JUNCTION BOXES SHALL HAVE
GALVANIZED LIDS. JUNCTION BOX LOCATION SHALL BE
APPROVED BY THE CITY PRIOR TO INSTALLATION. NO
CONDUIT RUN SHALL BE MORE THAN 200 FEET BETWEEN
JUNCTION BOXES. A JUNCTION BOX SHALL BE LOCATED
WITHIN 10 FEET OF EACH LUMINAIRE POLE AND AT EVERY
ROAD CROSSING. NO CONDUIT SHALL BE INSTALLED IN
THE ROADWAY EXCEPT AT DESIGNATED ROAD CROSSINGS
CONDUIT ENTERING THE JUNCTION BOX SHALL BE
PERPENDICUALR TO THE SIDES OF THE BOX AND A
MINIMUM OF 6 BUT NO MORE THAN 8 INCHES BELOW THE
LID. BOXES SHALL BE CLEARLY AND INDELIBLY MARKED AS
LIGHTING BOXES BY THE LEGEND "L.T." OR "LIGHTING". ALL
JUNCTION BOXES SHALL BE SUPPORTED BY A MINIMUM
6-INCH CRUSHED GRAVEL PAD.
11. AFTER INSTALLATION AND BEFORE ACCEPTANCE BY THE
CITY, ALL POLES SHALL BE FREE OF DENTS AND MARKS.
SONOTUBE SHALL BE REMOVED TO BELOW GROUND LEVEL.
POLE BASES SHALL BE GROUTED AND ALL LUMINAIRE
HEADS SHALL BE PLUMB AND LEVEL.
12. CONDUIT SHALL EXTEND BETWEEN 3 AND 6 INCHES ABOVE
THE CONCRETE BASE.
T-417301
N
c�
O
O
N
LX
O
M
0
O
N
Q
J
LO
O
O
O
O
N
IN COMPLIANCE WITH CITY OF RENTON STANDARDS (j)
LLCu
DEVELOPMENT ENGINEERING G
��
msippo 05/15/2025 O=
z
SUNRIDGE TOWNHOMES II
COVER SHEET
[n
DATE: w
4/2/2025 (D
FIELDBOOK: Q
PAGE:
DRAWING NO: it
SL1 z
SHEET: OF:
0
2 37
Cn