HomeMy WebLinkAboutConcrete Field Report_2025-09-12-Lindbergh High School Field Improvements-25B121-01_000002Inspection Information:
Inspection Date:09/12/2025 Time Onsite:09:44 Weather Conditions:64 cloudy
Inspection Performed: Concrete
Subcontractor:J Scott Continuous or Periodic:Continuous Inspection
Sheet(s):Location / Area:(2) Baseball Dug outs/(1) Softball dug out
Details:(1) F240 Dug Out Plan View Level / Elevation:Ground level
Approved Plans Dated:
Report Profile:
Any Deficiencies Noted:Yes No Deficiencies Cleared:Yes No
RFI:Yes No Show Up:Yes No
Retest / Reinspection:Yes No Standby:Yes No
Remarks:
CONCRETE PLACEMENT: Continuous Inspection
MTC inspected reinforcing steel prior to concrete placement. 6x6x10/10 WWM was placed in accordance with detail F240.
Clearance from subgrade to reinforcing was accomplished during the duration of the pour.
MTC inspector on site, as requested, to observe the placement of approximately 14 CY of concrete with Mix Design ID #1240AFG
supplied by Miles into dug out slab on grade at the location noted above.
One set of five (4” x 8”) cylinders was cast for compressive strength test specimens. Refer to Report #4940/ Set2 for field test
results and for more information.
Concrete was placed via trucks’ chute, and finished by hand.
Notable item:
Air content initially tested at 2.3%, minimum air content required is 3.5%. (Test was taken 1/2 way through SW Dugout of the
Baseball Field). Miles QC adjusted air content prior to finishing dug outs.
To the best of MTC inspector's knowledge, the abovedescribed work was performed in general accordance with project
specifications and approved plans.
Work in progress. Additional inspection needed.
✔✔
✔✔
✔✔
✔
Concrete Field Report RCCON00000200Report #:
Burlington
777 Chrysler Drive
Burlington, WA 98233
Phone: (360) 7551990
Client:
Renton School District No. 403
300 SW 7th St
Renton, WA 98057
Project:
25B12101 (Bldg Permit: B25002218)
Lindbergh High School Field Improvements
16426 128th Avenue Southeast
Renton, WA 98059
As a mutual protection to clients, the public and ourselves, all reports are submitted as the confidential property of clients, and
authorization for publication of statements, conclusions or extracts from or regarding our reports is reserved pending our written
approval.
Page 1 of 5Page 1 of 4
Inspection Information:Inspection Date:09/12/2025 Time Onsite:09:44 Weather Conditions:64 cloudyInspection Performed: ConcreteSubcontractor:J Scott Continuous or Periodic:Continuous InspectionSheet(s):Location / Area:(2) Baseball Dug outs/(1) Softball dug outDetails:(1) F240 Dug Out Plan View Level / Elevation:Ground levelApproved Plans Dated:Report Profile:Any Deficiencies Noted:Yes No Deficiencies Cleared:Yes NoRFI:Yes No Show Up:Yes NoRetest / Reinspection:Yes No Standby:Yes NoRemarks:CONCRETE PLACEMENT: Continuous InspectionMTC inspected reinforcing steel prior to concrete placement. 6x6x10/10 WWM was placed in accordance with detail F240.Clearance from subgrade to reinforcing was accomplished during the duration of the pour.MTC inspector on site, as requested, to observe the placement of approximately 14 CY of concrete with Mix Design ID #1240AFGsupplied by Miles into dug out slab on grade at the location noted above.One set of five (4” x 8”) cylinders was cast for compressive strength test specimens. Refer to Report #4940/ Set2 for field testresults and for more information.
Concrete was placed via trucks’ chute, and finished by hand.
Notable item:
Air content initially tested at 2.3%, minimum air content required is 3.5%. (Test was taken 1/2 way through SW Dugout of the
Baseball Field). Miles QC adjusted air content prior to finishing dug outs.
To the best of MTC inspector's knowledge, the abovedescribed work was performed in general accordance with project
specifications and approved plans.
Work in progress. Additional inspection needed.
Images:
✔✔✔✔✔✔
✔
Concrete Field Report RCCON00000200Report #:
Burlington
777 Chrysler Drive
Burlington, WA 98233
Phone: (360) 7551990
Client:
Renton School District No. 403
300 SW 7th St
Renton, WA 98057
Project:
25B12101 (Bldg Permit: B25002218)
Lindbergh High School Field Improvements
16426 128th Avenue Southeast
Renton, WA 98059
As a mutual protection to clients, the public and ourselves, all reports are submitted as the confidential property of clients, and
authorization for publication of statements, conclusions or extracts from or regarding our reports is reserved pending our written
approval.
Page 2 of 5Page 2 of 4
Inspection Information:Inspection Date:09/12/2025 Time Onsite:09:44 Weather Conditions:64 cloudyInspection Performed: ConcreteSubcontractor:J Scott Continuous or Periodic:Continuous InspectionSheet(s):Location / Area:(2) Baseball Dug outs/(1) Softball dug outDetails:(1) F240 Dug Out Plan View Level / Elevation:Ground levelApproved Plans Dated:Report Profile:Any Deficiencies Noted:Yes No Deficiencies Cleared:Yes NoRFI:Yes No Show Up:Yes NoRetest / Reinspection:Yes No Standby:Yes NoRemarks:CONCRETE PLACEMENT: Continuous InspectionMTC inspected reinforcing steel prior to concrete placement. 6x6x10/10 WWM was placed in accordance with detail F240.Clearance from subgrade to reinforcing was accomplished during the duration of the pour.MTC inspector on site, as requested, to observe the placement of approximately 14 CY of concrete with Mix Design ID #1240AFGsupplied by Miles into dug out slab on grade at the location noted above.One set of five (4” x 8”) cylinders was cast for compressive strength test specimens. Refer to Report #4940/ Set2 for field testresults and for more information.Concrete was placed via trucks’ chute, and finished by hand.Notable item: Air content initially tested at 2.3%, minimum air content required is 3.5%. (Test was taken 1/2 way through SW Dugout of theBaseball Field). Miles QC adjusted air content prior to finishing dug outs.To the best of MTC inspector's knowledge, the abovedescribed work was performed in general accordance with projectspecifications and approved plans.Work in progress. Additional inspection needed.Images:✔✔✔✔✔✔✔
Concrete Field Report RCCON00000200Report #:
Burlington
777 Chrysler Drive
Burlington, WA 98233
Phone: (360) 7551990
Client:
Renton School District No. 403
300 SW 7th St
Renton, WA 98057
Project:
25B12101 (Bldg Permit: B25002218)
Lindbergh High School Field Improvements
16426 128th Avenue Southeast
Renton, WA 98059
As a mutual protection to clients, the public and ourselves, all reports are submitted as the confidential property of clients, and
authorization for publication of statements, conclusions or extracts from or regarding our reports is reserved pending our written
approval.
Page 3 of 5Page 3 of 4
Inspection Information:Inspection Date:09/12/2025 Time Onsite:09:44 Weather Conditions:64 cloudyInspection Performed: ConcreteSubcontractor:J Scott Continuous or Periodic:Continuous InspectionSheet(s):Location / Area:(2) Baseball Dug outs/(1) Softball dug outDetails:(1) F240 Dug Out Plan View Level / Elevation:Ground levelApproved Plans Dated:Report Profile:Any Deficiencies Noted:Yes No Deficiencies Cleared:Yes NoRFI:Yes No Show Up:Yes NoRetest / Reinspection:Yes No Standby:Yes NoRemarks:CONCRETE PLACEMENT: Continuous InspectionMTC inspected reinforcing steel prior to concrete placement. 6x6x10/10 WWM was placed in accordance with detail F240.Clearance from subgrade to reinforcing was accomplished during the duration of the pour.MTC inspector on site, as requested, to observe the placement of approximately 14 CY of concrete with Mix Design ID #1240AFGsupplied by Miles into dug out slab on grade at the location noted above.One set of five (4” x 8”) cylinders was cast for compressive strength test specimens. Refer to Report #4940/ Set2 for field testresults and for more information.Concrete was placed via trucks’ chute, and finished by hand.Notable item: Air content initially tested at 2.3%, minimum air content required is 3.5%. (Test was taken 1/2 way through SW Dugout of theBaseball Field). Miles QC adjusted air content prior to finishing dug outs.To the best of MTC inspector's knowledge, the abovedescribed work was performed in general accordance with projectspecifications and approved plans.Work in progress. Additional inspection needed.Images:
Reported By:Tyler McDonald Reviewed By:Kevin Walters
✔✔✔✔✔✔✔
Concrete Field Report RCCON00000200Report #:
Burlington
777 Chrysler Drive
Burlington, WA 98233
Phone: (360) 7551990
Client:
Renton School District No. 403
300 SW 7th St
Renton, WA 98057
Project:
25B12101 (Bldg Permit: B25002218)
Lindbergh High School Field Improvements
16426 128th Avenue Southeast
Renton, WA 98059
As a mutual protection to clients, the public and ourselves, all reports are submitted as the confidential property of clients, and
authorization for publication of statements, conclusions or extracts from or regarding our reports is reserved pending our written
approval.
Page 4 of 5Page 4 of 4