HomeMy WebLinkAboutWTR2703149_31 3/4"C, 3#8 (48OV) TO
EXTERIOR PANEL XUJ9-1 /2A,
j 4B, 6C (SEE SHEET U06 FOR
' CONTINUATION)
O
0 � � POWER
W 3 CORD
1KVA 2KVA 120V CONSTRUCTION NOTES
S i SUMP
PUMP INSTALL (2) 3/4" SCH 80 PVC CONDUITS IN TRENCH WITH
MINIMUM 24 INCHES OF COVER FROM TOP OF CONDUIT TO
FINISH GRADE. PLACE CONDUIT IN TRENCH WITH CONTROL
DENSITY FILL APPROXIMATELY 6 INCHES ABOVE AND BELOW.
SEPARATE CONDUITS BY A MINIMUM OF 12 INCHES. PLACE
MARKER TAPE IN TRENCH ON TOP OF FILL. BACK FILL
�sTst REMAINING TRENCH SPACE WITH NATIVE FILL.
3 INSTALL (1 ) 3/4" SCH 80 CONDUIT IN MINIMUM 12" WIDE
TRENCH WITH MINIMUM 36" OF COVER FROM TOP OF
CONDUIT TO FINISH GRADE. PLACE CONDUIT IN TRENCH
WITH CONTROL DENSITY FILL APPROXIMATELY 6 INCHES
3/4"C, METER A i 3/4"C, ABOVE AND BELOW. PLACE MARKER TAPE IN TRENCH ON
INTERCONNECT 3#12 (120V) TOP OF FILL. BACK FILL REMAINING TRENCH SPACE WITH
CABLE NATIVE FILL.
SEAL CONDUIT PENETRATIONS WITH GROUT OR SILICONE
SEALANT TO LIMIT WATER PENETRATION.
METER VAULT
ELECTRICAL PLAN
NOT TO SCALE —
24"
INSTALL 3/4" EXTERIOR
PLYWOOD BACKER BOARD IN
+ BACK OF ENCLOSURE WITH
4-1 /4" SST BOLTS (HEADS EQUIPMENT LIST
ON OUTSIDE)
O2 3 0 METER TRANSMITTER
(FURNISHED WITH METER)
36" 0 CHART RECORDER z
� m
rz
5 0 NEMA 3R ENCLOSURE, PAINTED y o
O ATTACH WITH 4-3/8" STEEL, ,� m z
304 SST MB 36 H x 24 W x 12 D y
+ + 0 120V POWER (3#12) AND SIGNAL x
WIRE (FURNISHED WITH METER) 1
o
THREADED FLANGE, c� N
TOP AND BOTTOM 4-20mA SIGNAL WIRE, BELDEN N
4" SCH 40 GALV 2—CONDUCTOR WIRE WITH SHIELD 1
STEEL PIPE, SEE NOTE IN FLEX CONDUIT (J,�
►,
ATTACH WITH 4-3/8" O Qvoucx 2tLEQ-rI%GLz ►Ks1oa Qmcwsoev > C ~
36 304 SST WEDGE ANCHORS ro
36"x36"x7-1 /2" CONC BASE
y
TQ.e,N►s•, n�� e•so cyaar taco Qoa a �,
(MIN 2500 PSI), REINFORCED
SLOPE TO WITH 4 4# BARS E.W.
DRAIN, TYP
j
a
d d
Lb d
Q Q I
d Q
NOTE:
imi
SOLVENT CLEAN EXPOSED THREADS AND COAT
4 WITH COLD GALVANIZING COMPOUND. W= 314932
� C .
METER READOUT z
RECORD DRAWINGS
ENCLOSURE 2 PREPARED BY WHPACIFIC, �'
FEBRUARY 2010, BASED ��o ,per o3osss a
NOT TO SCALE U30 ON CONTRACTOR RECORDS. .��SsG1 STV, G1�
I
EXPIRES 06/06/07
'3 1 RECORD DRAWING HCS 3.12.10MSV SuwEYED`:`sR SCALE. HORIZONTAL-L:N�VD 1988 �� DATE'4 17 06
BHC Consultants, LLC AS SHOWN •. CITY 0 E CITY OF RENTON / /
WHPdClfll( ■ 720 Third Avenue, Suite 1200 DESIGNED:
SOUTH LAKE WASHINGTON FlELDBOOK:
Seattle, Washington 98104-1820 DRAWN: �D R E N TO N ROADWAY IMPROVEMENTS PAGE.
" 12100 NE 195th St,Ste 300 lei■ Tel: (206) 505-3400 ONE INCH DATUM DRAWNG No.
Bothell,WA 98011 CONSULTANTS Fax: (206) 505-3406 1 1 1 1 CHECKED: AT FULL SCALE Planning/Building/Public Works Dept. METER VAULT U31
425-951-4800 Fax 425-951-4808 LCA IF NOT ONE INCH
www.whpacific.com Formerly Division of Berryman&Henigar NO. REVISION BY DATE LAPPR APPROVED: SCALE ACCORDINGLY SHEET,. OF,
L�, ELECTRICAL 117 205
t