Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
AD_IFC 300__en_Profibus_110207_4001086601_R01
+ 2.497 -, 8-�NL M IFC 300 SuppLementary Signal converter for electromagnetic flowmeters Description of PROFIBUS interface PROFIBUS PA: PROFIBUS device with MBP Physical Interface and PA Profile 3.0 (V3.0.2/ 100811) PROFIBUS DP: PROFIBUS device with RS485 Physical Interface and PA Profile 3.0 (V3.0.2/ 100811) 801988 ©KROHNE 02/2011-4001086601 -AD IFC 300 PROFIBUS R01 en KROHNE ■ CONTENTS 1 Safety instructions 4 1.1 Scope of the document..................................................................................................... 4 1.2 Scope of delivery...............................................................................................................4 1.3 Special notes ....................................................................................................................4 2 PROFIBUS DP 5 2.1 Software history ............................................................................................................... 5 2.2 System configuration of PROFIBUS DP network............................................................. 6 2.3 Electrical connection for DP signal converter................................................................. 7 2.4 Technical data................................................................................................................... 9 2.5 GSD files for the data transfer....................................................................................... 10 2.5.1 Cyclic data exchange............................................................................................................. 10 2.5.2 Baud rate............................................................................................................................... 10 2.5.3 Ident.-No. supported............................................................................................................. 10 2.5.4 Manufacturer specific GSD files: KR024500.GSD and KR014500.GSD................................ 11 2.5.5 Differencies of the manufacturer specific GSD files: KR024500.GSD and KR014500.GSD. 13 2.5.6 Profile specific GSD file: PA039740.GSD.............................................................................. 13 2.5.7 Using the display menu to distinguish between Rev 1 and Rev 2........................................ 13 3 PROFIBUS PA 14 3.1 Software history ............................................................................................................. 14 3.2 System configuration of PROFIBUS PA network........................................................... 16 3.3 Electrical connection for PA signal converter............................................................... 17 3.4 Technical data................................................................................................................. 18 3.5 GSD files for the data transfer....................................................................................... 19 3.5.1 Cyclic data exchange............................................................................................................. 19 3.5.2 Ident.-No. supported............................................................................................................. 19 3.5.3 Manufacturer specific GSD files: KR024501.GSD and YP024501.GSD................................. 20 3.5.4 Profile specific GSD file: PA139740.GSD.............................................................................. 22 3.5.5 Using the display menu to distinguish the current revision of the device (PA)...................23 3.6 Signal converter IFC 300 PROFIBUS PA with MBP interface as replacement for older signal converter IFC 090 PA.................................................................................................. 23 3.6.1 Ident.-No. supported............................................................................................................. 23 3.6.2 Manufacturer specific GSD files (PA): KROHF401.GSD and YP01 F401.GSD for the older sig- nal converter IFC090 with PROFIBUS MBP interface.................................................................... 23 4 Application profile 25 4.1 Function blocks .............................................................................................................. 25 4.2 Data structure of function block output values ............................................................. 25 4.2.1 Float value............................................................................................................................. 25 4.2.2 Status value........................................................................................................................... 26 4.3 Diagnosis parameter...................................................................................................... 28 4.3.1 Diagnosis............................................................................................................................... 28 4.3.2 DIAGNOSIS (if "Classic Status" and "Diagnosis" selected)..................................................28 4.3.3 DIAGNOSIS_EXTENSION (if "Classic Status" and "Diagnosis" selected) ............................30 4.3.4 Mapping of DIAGNOSIS—EXTENSION bits into DIAGNOSIS bits...........................................31 2 www.krohne.com 02/2011 -4001086601 -AD IFC 300 PROFIBUS R01 en CONTENTS ■ 5 Profibus settings 34 5.1 Menu A, quick setup ....................................................................................................... 34 5.2 Menu B, test.................................................................................................................... 34 5.3 Menu C, setup................................................................................................................. 35 5.4 Menu D, service.............................................................................................................. 38 6 Notes 39 02/2011 -4001086601 -AD IFC 300 PROFIBUS R01 en www.krohne.com 3 U SAFETY INSTRUCTIONS Emam 1 .1 Scope of the document These instructions are supplementary to the signal converter Handbook. For all other data, use the relevant chapters of the Handbook. If you do not have this document, please contact the nearest office or download them from the manufacturer's internet site. a /NFORMA T/ON! The information in this chapter only contains the data applicable to PROFIBUS communication. The technical data in the Handbook shall be valid in its current version,provided that it is not rendered invalid or replaced by this supplement. 1 .2 Scope of delivery The information in this chapter only contains the data applicable to PROFIBUS communication. The technical data in the Handbook shall be valid in its current version, provided that it is not rendered invalid or replaced by this supplement. A device for PROFIBUS communication is supplied with: • Supplementary instructions for PROFIBUS communication • PROFIBUS device data files (GSD) on a CD-ROM supplied with the device 1 .3 Special notes Don't switch off (power off) the signal converter immediately after manual change of parameter values: • Please wait approx. 10 seconds before you switch off the signal converter after you have done both a parameter download via PROFIBUS or a manual change of a parameter value via the local display. • Please wait approx. 15 seconds before you switch off the signal converter after you have carried out a "Factory Reset" (PROFIBUS "Coldstart")via PROFIBUS or local display. "Deactivation of the Service Parameter Lock" of the signal converter via PROFIBUS: • After writing down the service password (via PROFIBUS) the "Deactivation of the Service Parameter Lock"will last at least 10 minutes if the internal password timer of the signal converter won't be retriggered by writing this password again. The "Deactivation of the Service Parameter Lock"will be terminated at once by a PROFIBUS Coldstart/Warmstart or if the internal password timer of the signal converter elapsed. 4 www.krohne.com 02/2011 -4001086601 -AD IFC 300 PROFIBUS R01 en PROFIBUS DP 2.1 Software history Issued Signal converter Application program System integration Mth./ Hardware Firmware Hardware Software Driver Version Model name year AL 04/05 Signal V1.1.3/050413 Simatic HW Config GSD KR014500.GSD IFC300(RS485) 09/05 converter V1.2.0/060215 PCS7 manuf. Rev.1 with other specific RS485 other SPS Software of interface+ of other other SPS GSD PA039740.GSD Flow with 1AI, PA Profile manufact. manufact. profile 1TOT(PhyL 0) 3.0 specific (special) Laptop - DD - - (Ident.-No.) - DTM>_ - - 01/06 Signal V2.0.0/060112 Simatic HW Config GSD KR014500.GSD* IFC300(RS4851 converter V2.0.0/060126 PCS7 manuf. KR024500.GSD Rev.1 with other specific IFC300(RS485) RS485 other SPS Software of Rev.2 interface+ of other other SPS PA Profile manufact. manufact. GSD PA039740.GSD Flow with 1AI, 3.0 profile 1TOT(PhyL 0) (special) specific Laptop/PC PDM DID 13P*DD0300.03** - (>_6.0 SP31 (Ident.-No.) Pactware DTM>_ GFP*DTM1.3.1 - FDT1.2 04/08 Signal V3.0.2/080422 Simatic HW Config GSD KR014500.GSD* IFC300(RS4851 converter PCS7 manuf. KR024500.GSD Rev.1 with other specific IFC300(RS485) RS485 other SPS Software of Rev.2 interface+ of other other SPS PA Profile manufact. manufact. GSD PA039740.GSD Flow with 1Al. 3.0 profile 1TOT(PhyL 0) specific Laptop/PC PDM DID 13P*DD0300.03** - (>_6.0 SP31 (Ident.-No.) Pactware DTM>_ GFP*DTM1.3.1 - FDT1.2 02/2011-4001086601-AD IFC 300 PROFIBUS R01 en www.krohne.com 5 p PROFIBUS DP Issued Signal converter Application program System integration Mth./ Hardware Firmware Hardware Software Driver Version Model name year 01/11 Signal V3.0.2/100811 Simatic HW Config GSD KR014500.GSD* IFC300(RS485) converter PCS7 manuf. KR024500.GSD Rev.1 with other specific IFC300(RS485) RS485 other SPS Software of Rev.2 interface+ of other other SPS PA Profile manufact. manufact. GSD PA039740.GSD Flow with 1Al, 3.0 profile 1TOT(PhyL 0) specific Laptop/PC PDM DD 13P*DD0300.03** - (>_6.0 SP3) (Ident.-No.) Pactware DTM>_ GFP*DTM1.3.1 - FDT1.2 13P*DTM1.0.7 - FDT1.2 *: If the GSD file "KR014500.GSD" is used, there will be supported only a limited amount of functions by the software version (V1.2.0/060215 or V2.0.0/060112): I&M functions and fail safe mode are not accessible. For full support of all profile specific or manufacturer specific functions/parameters use the GSD file "KR024500.GSD". GFP*: Generic Flow PROFIBUS 13P*: IFC300 PROFIBUS **: PDM 5.2 PDM 6.0 2.2 System configuration of PROFIBUS DP network The following diagram shows a typical network configuration with PROFIBUS devices with RS485 interface in a non-hazardous environment. The PROFIBUS devices with RS485 interface do not need any segment coupler. They are connected directly to the PROFIBUS DP network. ��7� 10 02 Figure 2-1:PROFIBUS DP network 1) SPS 2� PROFIBUS DP with max. 12 Mbit/s 3� Signal converter 44) Other devices with PROFIBUS RS485 interface 6 www.krohne.com 02/2011 -4001086601 -AD IFC 300 PROFIBUS R01 en I PROFIBUS DP p 2.3 Electrical connection for DP signal converter a /NFORMA T/ON! For a detailed description of the electrical connections please refer to the standard signal converter handbook. Signal converter terminals B B- C C- D D- PROFIBUS designation T +B -A -T +B -A 0 (4) 0 10 Termination positive (2) TxD+/RxD+ second connection 03 TxD-/RxD- second connection 40 Termination negative (5) TxD+/RxD+first connection © TxD-/RxD- first connection External connection with spur +5v R1 R2 R1 I I I I B B- C C- D D- ACA UT/ON! QSpurs are not allowed at high data rates! 0 I = 110 nH R1 =390Q R2 = 220Q 02/2011 -4001086601 -AD IFC 300 PROFIBUS R01 en www.krohne.com 7 p PROFIBUS DP � � M M M External connection at last device with active internal bus termination +5V - R1 R2 R1 I I I I B B- C C- D D- + - I = 110 nH R1 =390Q R2 = 220Q External connection to a trunk +5V - R1 R2 R1 I I I I B B- C C- D D- n212 1� e.g. incoming data lines 2Z e.g.outgoing data lines I = 110 nH R1 =390Q R2 = 220Q 8 www.krohne.com 02/2011 -4001086601 -AD IFC 300 PROFIBUS R01 en PROFIBUS DP 2.4 Technical data Hardware Type PROFIBUS RS485 interface according to IEC 61158-2 Connection Dependent of polarity; please note at electrical connection! Software GSD GSD file on CD-ROM or from internet site Device profile PA Profile compact class B,V 3.0 Address range 0...126(default 1261 0...125 via PROFIBUS service set slave add 0...126 via local display 126 via factory reset=2712 Local control Local display and operator interface at device SAPS 2 x MS1 SAPS—acyclic interface to PLC 3 x MS2 SAPs—the number of MS2 Service Access Points is typically equal to the maximum number of master class 2 tools Function blocks 1 x TB=Transducer Block:contains the parameters and functions defined in PA Profile 3.0 1 x PB=Physical Block:contains the parameters defined in PA Profile 3.0 5 x Al=Analog Input Blocks:contains the parameters defined in PA Profile 3.0 3 x TOT=Totalizer Function Blocks:contains the parameters defined in PA Profile 3.0 02/2011-4001086601-AD IFC 300 PROFIBUS R01 en www.krohne.com 9 p PROFIBUS DP Er�= 2.5 GSD files for the data transfer A PROFIBUS GSD ZIP file (e.g. GSD-31777813.zip; including both all GSD files and additional data files) you can get on a CD ROM or can be downloaded from the internet. The GSD file contains information that will be needed for project planning of the PROFIBUS communication network. The relevant data files (e.g.____.bmp/____.dib) must be loaded into the bus configuration system/master system before start-up of the bus system. 2.5.1 Cyclic data exchange During network configuration the user has to define which function block outputs of the signal converter should be transferred cyclically to the master. Network configuration will be done using one of the GSD files described before.The order of transmission of a function block always remains the same even if a function block is defined as an "Empty" block (if so, no function block output data will be sent to the master and all function block outputs following the empty block will move up one position). 2.5.2 Baud rate Supported baud rates are listed in the GSD file (see below). After power-on or PROFIBUS timeout a baud rate search is active to detect the current transfer speed on the bus. It is not necessary to set the baud rate manually. If the data transmission rate is changed during operation the baud rate search will not be started by the device. A new power-up or a manual interruption of the PROFIBUS communication is required to activate the baud rate search in this case. 2.5.3 Ident.-No. supported The signal converterwith PROFIBUS RS485 interface is based on PROFIBUS PA Profile V 3.0.The device supports two Ident-No.: • Ident-No. "4500hex" belongs to the GSD file KR014500.GSD and KR024500.GSD and includes the complete functionality of the electromagnetic flowmeter. • The application of the manufacturer independent Ident-No. "9740hex" (GSD file "PA039740.GSD") provides interchangeability of devices, i.e. an exchange of electromagnetic flowmeters of different vendors. Please follow the instructions in the manual of the host supplier when installing the GSD File you need and the additional files (____.bmp and ____.dib) into the PLC. a /NFORMA T/ON! 1 If separated by the bus configuration system the device entry of the PROFIBUS RS485 interface with PA Profile 3.0 will be located within the slave family PROFIBUS PA. 10 www.krohne.com 02/2011 -4001086601 -AD IFC 300 PROFIBUS R01 en PROFIBUS DP p 2.5.4 Manufacturer specific GSD files: KR024500.GSD and KR014500.GSD The manufacturer delivers the GSD files with the entire device functionality, which is listed as follows: Block Default configuration KR024500.GSD Default number Function block output:value and KR014500.GSD unit status Ident-No.4500 1 Volume Flow AI-FB m3/h 2 Volume Totalizer Totalizer-FB m3 3 Volume Totalizer Totalizer-FB m3 4 Mass Totalizer Totalizer-FB kg 5 Mass Flow AI-FB kg/s 6 Speed Flow AI-FB m/s 7 Coil Temperature AI-FB K 8 Conductivity AI-FB S/m X Electronic Temperature AI-FB °C X Supply AI-FB V (internal supply voltage for the PROFIBUS interface) • AI: Analog Input Function Block • FB: Function Block • X: Block number 1, 5, 6, 7 or 8 There will be two additional output values available by changing the function block channel parameters of the above mentioned "Analog Input Function Blocks". There are separate settings to select the units for local display and PROFIBUS. Modifications of the units of the display will have no effect on the data transferred via PROFIBUS. A master class 2 tool is required to modify the units for PROFIBUS transfer. a /NFORMA T/ON! 1 During network configuration the user has to define which function block outputs of the signal converter should be transferred cyclically to the master. This is performed by a bus configuration tool[e.g. "HW- Config"for PC-S7from Siemensl. This tool offers specific functions as follows: 1. It is possible to configure an "Empty"block fthe code of an "Empty"block is defined as OxOOJ on each block number. This implies:no data are transmitted in the cyclic data telegram for this block. 2. There is NO "Totalizer f TOTI"function block allowed on block position 1, 5, 6, 7and 8!On these positions, only an 'Analog Input fAH"function block or an "Empty"block is allowed! (Note:All codes supported by 'Analog Input W"-and "Totalizer f TOTI"— function blocks will be found in the corresponding GSD files.J 3. There is NO 'Analog Input fAIJ-function block allowed on block position 2, 3 and 4!On these positions, only a "Totalizer fTOTI"function block or an "Empty"block is allowed! 4. There is a choice of 7 different totalizer functions, which can be allocated to the blocks 2, 3 and/or 4. 02/2011 -4001086601 -AD IFC 300 PROFIBUS R01 en www.krohne.com 11 PROFIBUS DP Definition of totalizer functions Total cyclic transfer of the totalizer value with status to the master SetTot+Total cyclic transfer of the totalizer value with status to the master+cyclic control data from master to the device via the parameter SetTot ModeTot+Total cyclic transfer of the totalizer value with status to the master+cyclic control data from master to the device via the parameter ModeTot SetTot+ModeTot+Total cyclic transfer of the totalizer value with status to the master+cyclic control data from master to the device via the parameters SetTot and ModeTot(in the given order) SetTot cyclic control data from master to the device via the parameter SetTot ModeTot cyclic control data from master to the device via the parameter ModeTot SetTot+ ModeTot cyclic control data from master to the device via the parameters SetTot and ModeTot(in the given order) Both, the Byte SetTot and ModeTot are cyclically sent from the master to the device if these bytes are inserted as output data via the PLC configurator.The meaning of these control bytes are as follows: Function of control bytes SetTot SetTot=0 Totalizer is totalizing. SetTot= 1 Totalizer will be reset to 0 and stays at 0 until SetTot is switched back again to 0. If the value of SetTot changes from "1" to"0"the totalizer starts counting from 0. SetTot=2 Totalizer is set to the value defined by PresetTot. PresetTot can be written via an acyclic master(totalizer in block 2=Slot 2 Index 32; totalizer in block 3=Slot 3 Index 32;totalizer in block 4=Slot 4 Index 32). If the value of SetTot changes from "2"to"0"the totalizer starts counting from the current value defined by PresetTot. SetTot> 2 Not allowed.Value is ignored;totalizer remains in its last valid setting. ModeTot ModeTot=0 Totalizer totalizes positive and negative values. ModeTot= 1 Totalizes only positive values. ModeTot=2 Totalizes only negative values. ModeTot=3 Totalizer is stopped, no totalization will be done. ModeTot=248 Totalizes all values as positive, negative values will be multiplied with -1.0. ModeTot=249 Totalizes all values as negative,positive values will be multiplied with -1.0. All other values of ModeTot not allowed.Value is ignored; totalizer remains in its last valid setting. The standard block configuration may be changed by the customer but using the default settings is highly recommended. If the standard block configuration should be changed by the customer an acyclic master tool or the device display menu must be used to change the "channel parameter"value of the block which should be connected to another transducer output value. 12 www.krohne.com 02/2011 -4001086601 -AD IFC 300 PROFIBUS R01 en PROFIBUS DP p 2.5.5 Differencies of the manufacturer specific GSD files: KR024500.GSD and KR014500.GSD KR024500.GSD KRO14500.GSD (includes the complete functionality) (functions are only partially supported) GSD Revision 5.02 GSD Revision 3 PROFIBUS-PA Profile 3.Ox and I&M PROFIBUS PA Profile 3.Ox Ident_Maintenance_supp= 1 (==supported)Fail—Safe (Extended DP-Features) - C2 Max Data Len= 132 C2 Max Data Len= 128 Max_Initiate_PDU_Length = 132 Max_Initiate_PDU_Length= 128 Unit_Diag_Bit(82)= "DP- measurement not Unit_Diag_Bit(82) = "reserved (82)" available" Unit_Diag_Bit(83) = "reserved (83)" Unit_Diag_Bit(83) = "DP- power fail" 2.5.6 Profile specific GSD file: PA039740.GSD The functionality of the profile specific GSD file is limited. This GSD file includes only two blocks: Block Standard configuration PA039740.GSD Default number Function block output value Ident-No. 9740 unit 1 Volume Flow AI-FB m3/h 2 Volume Totalizer Totalizer-FB m3 The device has to be switched from full functionality (manufacturer specific) to interchangeable basic configuration (profile specific) by using both a master class 2 tool or the device display menu WENT_NUMBER_SELECTOR: Slot 0, Index 40; change byte value to 01. In the next step, the device has to be configured using the PA039740.GSD file. 2.5.7 Using the display menu to distinguish between Rev 1 and Rev 2 Rev 1 [= = DP signal converter (RS485) Rev 11 and Rev 2 [= = DP signal converter (RS485) Rev 21 Use the display to open the Fct. 3.5 of the signal converter(if not available, see below Rev 1).You will get the following information: • KROHNE Ident.-No. (of the assembled PROFIBUS PCB) • Software revision (of the PROFIBUS software) • Date of production (of the PROFIBUS device) Your device is Rev 1, if • the Fct. No. mentioned above is not available • the indicated software revision number is = 1.0.x Your device is Rev 2, if • the indicated software revision number is = 1.1.x • the indicated software revision number is>_2.0 02/2011 -4001086601 -AD IFC 300 PROFIBUS R01 en www.krohne.com 13 PROFIBUS PA 3.1 Software history Issued Signal converter Application program System integration Mth./ Hardware Firmware Hardware Software Driver Version Model name year AL 01/06 Signal V2.0.0/060112 Simatic HW Config GSD KR024501.GSD IFC300 (MBP) converter V2.0.0/060126 PCS7 manuf. Rev.2 with MBP other specific for interface+ other SPS Software of stand. PA Profile of other other SPS DP/PA 3.0 manufact. manufact. segment coupler GSD YP024501.GSD YPOIFC300 manuf. (MBP) Rev.2 specific for S K2/S K3 segment coupler of P&F GSD PA139740.GSD Flow with 1AI, profile 1TOT(PhyL 1) specific Laptop/PC PDM DD I3P*DD0300.03** - (>_6.0 SP3) (Ident.-No.) Pactware DTM>_ GFP*DTM1.3.1 - FDT1.2 04/08 Signal V3.0.2/080422 Simatic HW Config GSD KR024501.GSD IFC300 (MBP) converter PCS7 manuf. Rev.2 with MBP other specific for interface+ other SPS Software of stand. PA Profile of other other SPS DP/PA 3.0 manufact. manufact. segment coupler GSD YP024501.GSD YPOIFC300 manuf. (MBP) Rev.2 specific for S K2/S K3 segment coupler of P&F GSD PA139740.GSD Flow with 1AI, profile 1TOT(PhyL 1) specific Laptop/PC PDM DD I3P*DD0300.03** - (>_6.0 SP31 (Ident.-No.) Pactware DTM>_ GFP*DTM1.3.1 - FDT1.2 14 www.krohne.com 02/2011 -4001086601 -AD IFC 300 PROFIBUS R01 en PROFIBUS PA , Issued Signal converter Application program System integration Mth./ Hardware Firmware Hardware Software Driver Version Model name year 01/11 Signal V3.0.2/100811 Simatic HW Config GSD KR024501.GSD IFC300 (MBP) converter PCS7 manuf. Rev.2 with MBP other specific for interface+ other SPS Software of stand. PA Profile of other other SPS DP/PA 3.0 manufact. manufact. segment coupler GSD YP024501.GSD YPOIFC300 manuf. (MBP) Rev.2 specific for S K2/S K3 segment coupler of P&F GSD PA139740.GSD Flow with 1A1, profile 1TOT(PhyL 1) specific Laptop/PC PDM DD 13P*DD0300.03** - (>_6.0 SP31 (Ident.-No.) Pactware DTM>_ GFP*DTM1.3.1 - FDT1.2 13P*DTM1.0.7 - FDT1.2 GFP*: Generic Flow PROFIBUS 13P*: IFC300 PROFIBUS **: PDM 5.2 PDM 6.0 02/2011-4001086601-AD IFC 300 PROFIBUS R01 en www.krohne.com 15 p PROFIBUS PA 3.2 System configuration of PROFIBUS PA network The following diagram shows a typical instrumentation with PROFIBUS PA devices with MBP interface in hazardous and non-hazardous locations, including connections of conventional devices (e.g. with 4...20 mA signals) in a PROFIBUS network. As a rule, the PROFIBUS PA segment is connected to a segment coupler which, among other things, carries out the conversion to the PROFIBUS DP bus line. It should be mentioned that the segment coupler is normally set to a fixed baud rate on the DP side. 10 OO 03 '` IIIII II ��IIIIIII ❑ ❑ ,---- ---------o- o ❑ I �X Figure 3-1:PROFIBUS PA network 1� Control system (PLC);class 1 master 2� Engineering or operation control tool;class 2 master 3� PROFIBUS DP network with max. 12 Mbit/s 44) PROFIBUS PA segment coupler DP/PA 5� Device with PROFIBUS PA interface,31.25 kbit/s © HART®device (7 More devices with 4...20 mA ® Analogue I/O module 16 www.krohne.com 02/2011 -4001086601 -AD IFC 300 PROFIBUS R01 en PROFIBUS PA 3.3 Electrical connection for PA signal converter a /NFORMA T/ON! For a detailed description of the electrical connections please refer to the standard signal converter handbook. External connection with spur 1� D- I D C- C �2 PA- T Device internal terminal names 2� External bus connections External connection to a trunk 1� D- D C- C (2 PA- PA+ PA- PA+ 9) Device internal terminal names 2� External bus connections �3 e.g. incoming data lines 4� e.g.outgoing data lines Alternative wiring because the current linkage between the device and the PROFIBUS PA cable is independent of polarity 1� D- D C- C (2) PA+ PA- 1T Device internal terminal names 2� External bus connection 02/2011-4001086601-AD IFC 300 PROFIBUS R01 en www.krohne.com 17 PROFIBUS PA /NFORMA T/ON! 1 Although the PROF/BUS MBP technology supports power supply via the PROF/BUS line the "signal converter PROF/BUS MBP interface"will operate only if the additional power supply for the device is connected/available. Fora detailed description please check the signal converter handbook. Refer also to the PROFIBUS PA user and installation guideline(lNersion 2.2, February 2003 PNO order no. 2.0921. 3.4 Technical data Hardware Type PROFIBUS RS485 interface according to IEC 61158-2 with 31.25 kbits/s;voltage mode Connection Independent of polarity at electrical connection Base current 10.5 mA FOE Yes,separate fault disconnection electronics provided (FDE=Fault Disconnection Electronics) Fault current 6 mA(fault current=max.continuous current—base current) Starting current <12 mA Ex approval Ex is IIC or Ex ib IIC/IIB, FISCO Device For detailed information refer to standard product documentation. Software GSD GSD file on CD-ROM or from internet site Device profile PA Profile compact class B,V 3.0 Address range 0...126(default 1261 0...125 via PROFIBUS service set slave add 0...126 via local display 126 via factory—reset=2712 Local control Local display and operator interface at device SAPs 2 x MS1 SAPs—acyclic interface to PLC 3 x MS2 SAPS—the number of MS2 Service Access Points is typically equal to the maximum number of master class 2 tools Function blocks 1 x TB=Transducer Block:contains the parameters and functions defined in PA Profile 3.0 1 x PB=Physical Block:contains the parameters defined in PA Profile 3.0 5 x Al=Analog Input Blocks:contains the parameters defined in PA Profile 3.0 3 x TOT=Totalizer Function Blocks:contains the parameters defined in PA Profile 3.0 18 www.krohne.com 02/2011 -4001086601 -AD IFC 300 PROFIBUS R01 en PROFIBUS PA 3.5 GSD files for the data transfer A PROFIBUS GSD ZIP file (e.g. GSD-31777813.zip; including both all GSD files and additional data files) you can get on a CD ROM or can be downloaded from the internet. The GSD file contains information that will be needed for project planning of the PROFIBUS communication network. The relevant data files (e.g.____.bmp/____.dib) must be loaded into the bus configuration system/master system before start-up of the bus system. 3.5.1 Cyclic data exchange During network configuration the user has to define which function block outputs of the signal converter should be transferred cyclically to the master. Network configuration will be done using one of the GSD files described before.The order of transmission of a function block always remains the same even if a function block is defined as an "Empty" block (if so, no function block output data will be sent to the master and all function block outputs following the empty block will move up one position). 3.5.2 Ident.-No. supported The signal converter with PROFIBUS MBP interface is based on PROFIBUS PA Profile V 3.0. The device supports three Ident-No.: • Ident-No. "4501 hex" belongs to the GSD file KR024501.GSD and YP024501.GSD and includes the complete functionality of the electromagnetic flowmeter. • The application of the manufacturer independent Ident-No. "9740hex" (GSD file "PA039740.GSD") provides interchangeability of devices, i.e. an exchange of electromagnetic flowmeters of different vendors. • Ident-No. "F401 hex" For detailed information refer to Signal converterlFC300PROFIBUSPA with MBPinterface as replacement for oldersignal converter lFC 090 PA on page 23. Please follow the instructions in the manual of the host supplier when installing the GSD File you need and the additional files (_ .bmp and .dib) into the PLC. a /NFORMA T/ON! If separated by the bus configuration system the device entry of the PROFIBUS MBP interface with PA Profile 3.0 will be located within the slave family PROFIBUS PA. 02/2011 -4001086601 -AD IFC 300 PROFIBUS R01 en www.krohne.com 19 p PROFIBUS PA 3.5.3 Manufacturer specific GSD files: KR024501.GSD and YP024501.GSD The KR024501.GSD file is for use with the standard DP/PA coupler and the YP024501.GSD file is for use with the transparent DP/PA coupler SK2/SK3 of Pepped & Fuchs (up to 12 MBaud on the DP segment). a /NFORMA T/ON! For devices with MBP interface there are always two types of GSD files in our GSD compilation: • One standard GSD file fora standard DP/PA segment coupler with file name: WRO....GSD- One special GSD file specific for the segment coupler SK2/SK3 of Pepperl& Fuchs with file name: "YPO....GSD" It should be noted that both GSD files support device functionality as described below: Block Default configuration KR024501.GSD Default number Function block output:value and YP024501.GSD unit status Ident-No.4501 1 Volume Flow AI-FB m3/h 2 Volume Totalizer Totalizer-FB m3 3 Volume Totalizer Totalizer-FB m3 4 Mass Totalizer Totalizer-FB kg 5 Mass Flow AI-FB kg/s 6 Speed Flow AI-FB m/s 7 Coil Temperature AI-FB K 8 Conductivity AI-FB S/m X Electronic Temperature AI-FB °C X Supply AI-FB V (internal supply voltage for the PROFIBUS interface) • AI: Analog Input Function Block • FB: Function Block • X: Block number 1, 5, 6, 7 or 8 There will be two additional output values available by changing the function block channel parameters of the above mentioned "Analog Input Function Blocks". There are separate settings to select the units for local display and PROFIBUS. Modifications of the units of the display will have no effect on the data transferred via PROFIBUS. A master class 2 tool is required to modify the units for PROFIBUS transfer. 20 www.krohne.com 02/2011 -4001086601 -AD IFC 300 PROFIBUS R01 en PROFIBUS PA a /NFORMA T/ON! 1 During network configuration the user has to define which function block outputs of the signal converter should be transferred cyclically to the master. This is performed by a bus configuration tool[e.g. "HW- Config"for PC-S7from Siemensl. This tool offers specific functions as follows: 1. It is possible to configure an "Empty"block(the code of an "Empty"block is defined as OxOOJ on each block number. This implies:no data are transmitted in the cyclic data telegram for this block. 2. There is NO "Totalizer(TOTI"function block allowed on block position 1, 5, 6, 7and 8!On these positions, only an Analog Input(AH"function block or an "Empty"block is allowed! (Note:All codes supported by 'Analog Input fAH"-and "Totalizer(TOTI"— function blocks will be found in the corresponding GSD files.J 3. There is NO 'Analog Input(AIJ""function block allowed on block position 2, 3 and 4!On these positions, only a "Totalizer(TOTI"function block or an "Empty"block is allowed! 4. There is a choice of 7 different totalizer functions, which can be allocated to the blocks 2, 3 and/or 4. Definition of totalizer functions Total cyclic transfer of the totalizer value with status to the master SetTot+Total cyclic transfer of the totalizer value with status to the master+cyclic control data from master to the device via the parameter SetTot ModeTot+Total cyclic transfer of the totalizer value with status to the master+cyclic control data from master to the device via the parameter ModeTot SetTot+ ModeTot+Total cyclic transfer of the totalizer value with status to the master+cyclic control data from master to the device via the parameters SetTot and ModeTot(in the given order) SetTot cyclic control data from master to the device via the parameter SetTot ModeTot cyclic control data from master to the device via the parameter ModeTot SetTot+ ModeTot cyclic control data from master to the device via the parameters SetTot and ModeTot (in the given order) 02/2011 -4001086601 -AD IFC 300 PROFIBUS R01 en www.krohne.com 21 PROFIBUS PA Both,the Byte SetTot and ModeTot are cyclically sent from the Master to the device if these bytes are inserted as output data via the PLC configurator.The meaning of these control bytes are as follows: Function of control bytes SetTot SetTot=0 Totalizer is totalizing. SetTot= 1 Totalizer will be reset to 0 and stays at 0 until SetTot is switched back again to 0. If the value of SetTot changes from "1" to"0"the totalizer starts counting from 0. SetTot=2 Totalizer is set to the value defined by PresetTot. PresetTot can be written via an acyclic master(totalizer in block 2=Slot 2 Index 32; totalizer in block 3=Slot 3 Index 32;totalizer in block 4=Slot 4 Index 32). If the value of SetTot changes from "2"to"0"the totalizer starts counting from the current value defined by PresetTot. SetTot> 2 Not allowed.Value is ignored;totalizer remains in its last valid setting. ModeTot ModeTot=0 Totalizer totalizes positive and negative values. ModeTot= 1 Totalizes only positive values. ModeTot=2 Totalizes only negative values. ModeTot=3 Totalizer is stopped, no totalization will be done. ModeTot=248 Totalizes all values as positive, negative values will be multiplied with -1.0. ModeTot=249 Totalizes all values as negative,positive values will be multiplied with -1.0. All other values of ModeTot not allowed. Value is ignored; totalizer remains in its last valid setting. The standard block configuration may be changed by the customer but using the default settings is highly recommended. If the standard block configuration should be changed by the customer an acyclic master tool or the device display menu must be used to change the "channel parameter"value of the block which should be connected to another transducer output value. 3.5.4 Profile specific GSD file: PA139740.GSD The functionality of the profile specific GSD file is limited. This GSD file includes only two blocks: Block Standard configuration PA139740.GSD Default number Function block output value Ident-No. 9740 unit 1 Volume Flow AI-FB m3/h 2 Volume Totalizer Totalizer-FB m3 The device has to be switched from full functionality to interchangeable basic configuration by using one of both a master class 2 tool (IDENT_NUMBER_SELECTOR: Slot 0, Index 40; change byte value to 0) or the device display menu. In the next step, the device has to be configured using the PA039740.GSD file. 22 www.krohne.com 02/2011 -4001086601 -AD IFC 300 PROFIBUS R01 en I = M PROFIBUS PA 3.5.5 Using the display menu to distinguish the current revision of the device (PA) Use the display to open the Fct. B3.5 or C5.8.2 of the signal converter. You will get the following information: • KROHNE Ident.-No. (of the assembled PROFIBUS PCB) • Software revision (of the PROFIBUS software) • Date of production (of the PROFIBUS device) 3.6 Signal converter IFC 300 PROFIBUS PA with MBP interface as replacement for older signal converter IFC 090 PA 3.6.1 Ident.-No. supported Ident.-No. "F401hex":This Ident.-No. supports a compatibility mode concerning the cyclic data transfer (cyclic measurement values and diagnosis) if the IFC300 with PROFIBUS MBP interface will be used for replacement of an "IFC090PA". It is not necessary to adapt the PLC configuration. Communication functions are restricted to those functions supported by IFC090 converters. Take care to set the "IFC300 PROFIBUS MBP interface" parameters in a way to get the same behaviour as of "IFC090PA" concerning calculation of measuring values and totalizers (this has to be done manually). 3.6.2 Manufacturer specific GSD files (PAS: KROHF401.GSD and YP01 F401.GSD for the older signal converter IFC090 with PROFIBUS MBP interface The PROFIBUS signal converter with MBP Interface operating in the IFC090 compatibility mode ensures operation with a PLC system with software parameters based on the IFC090PA. This option is important for those customers who do not want to change the parameters in the PLC software after having replaced the IFC090PA by an IFC300 with PROFIBUS MBP interface. The existing GSD files of the IFC090PA ("KROHF401.GSD" or"YP01 F401.GSDI can still be used. In this application, the compatibility mode of the IFC300 with PROFIBUS MBP interface has to be selected (display menu D2.9- Identification No. -> choose IFC090); some other entries have to be performed in a next step. The overall situation is described using the following example: Consider an "IFC090PA"standard configuration based on IFS...FLUX* flow sensor and "IFC090PA" flow signal converter. Consider the following two options for replacements (IFS ....FLUX= IFS flow sensor compliant with IFC090PA): 1. The IFC090PA flow signal converter will be replaced by an IFC300 PROFIBUS MBP interface flow signal converter. The IFS ...FLUX flow sensor is kept. 2. In addition to 1., also the IFS ...FLUX flow sensor will be replaced by an OPTIFLUX flow sensor. Options for flow IFC 300 PROFIBUS signal Integration into the PLC sensor installation: converter with MBP PLC via PROFIBUS PA parameter set Option 1.: IFS...FLUX interface —> a) IFC090PA.GSD in the Ctrl software of the Option 2.: OPTIFLUX de=rePA ROFIBUS b) IFC300(MBP).GSD PLC so software a) no change b) change 02/2011 -4001086601 -AD IFC 300 PROFIBUS R01 en www.krohne.com 23 p PROFIBUS PA For both replacements 1. and 2., there are 2 options how to deal with the GSDs. In order to provide communication between "IFC300 with PROFIBUS MBP interface"and the PLC,you may- in principle—use the GSD of the "IFC090PA" ("KROHF401.GSD" or "YP01 F401.GSD") and —alternatively - the GSD of the "IFC300 with PROFIBUS MBP interface" ("KR024501.GSD" or "YP024501.GSD"). However, both sets of GSDs, when applied, do not provide the same level of functionality in the PLC. The available PROFIBUS functionality of the "IFC300 with PROFIBUS MBP interface" in the PLC as function of installed flow sensor and GSD used for integration into the PLC is as follows: Installed flow sensor Integration into the PLC via IFC090PA.GSD IFC300 with PROFIBUS MBP KROHF401.GSD interface GSD KR024501.GSD IFS...FLUX flow sensor "IFC090PA" profile 2 functionality "IFC300 with PROFIBUS MBP (Option 1.) interface"functionality(some "IFC300 with PROFIBUS MBP interface"self-test functions not available) OPTIFLUX flow sensor(Option 2.) "IFC090PA" profile 2 functionality "IFC300 with PROFIBUS MBP interface"functionality How to deal with the PA The "IFC090PA" parameter set The "IFC090PA" parameter set parameter set in the PLC Ctrl for the PLC Ctrl software can be for the Ctrl software has to be software used as existing in the PLC adapted with reference to the interface of"IFC300 with PROFIBUS MBP interface" If the GSDs of the "IFC090PA" ("KROHF401.GSY or "YP01 F401.GSY) are used... • The IFC090PA parameter set for the PLC control software will be maintained, i.e. there is no adaptation needed with reference to the replaced interface of the IFC300 with PROFIBUS MBP interface. • In this usage of the GSD the PA Profile 2.0 functionality is provided in the PLC for both replacements, i.e. it is not possible to reset the PA totalizer via the PLC. If the GSD of "IFC300 with PROFIBUS MBP interface" (KR024501.GSD or YP024501.GSD) is used... • The IFC090PA parameter set for the PLC control software has to be adapted with reference to the IFC300 PROFIBUS MPB interface. • In this usage of the GSD the PA Profile 3.0 functionality is provided and all diagnostic features of the "IFC300 with PROFIBUS MBP interface" are being made available. 24 www.krohne.com 02/2011 -4001086601 -AD IFC 300 PROFIBUS R01 en APPLICATION PROFILED 4.1 Function blocks The PROFIBUS MBP interface is based on the PROFIBUS PA Profile Version 3.0 and supports the following blocks: • 1 physical block. This block contains the parameters defined in PA Profile 3.0. • 1 transducer block for electromagnetic flow devices. This block provides the parameters and functions defined in PA Profile 3.0. • 5 Analog Input (AI) function blocks. As default:Volume Flow/ Mass Flow/Speed Flow/Coil Temperature/Conductivity. • 3 totalizer (TOT) function blocks. As default the first two totalizers will totalize volume and the third one will totalize mass. 4.2 Data structure of function block output values The data structure of function block outputs consists of 5 bytes: a 4 byte float value (Float Format according IEEE Standard 754 Short Real Number) followed by a 1 byte status value. If all 8 function block outputs have been configured (see above), 40 bytes will be transmitted. 4.2.1 Float value Example of float format Byte n Byte n+1 Bit7 Bit6 Bit? Bit6 VZ 27 26 25 24 23 22 21 20 2-1 2-2 2-3 2-4 2-5 2-6 2-7 Exponent Mantissa Byte n+2 Byte n+3 Bit7 Bit7 2-8 2-9 2-10 2-11 2-12 2-13 2-14 2-15 2 16 2 17 2-18 2-19 2-20 2-21 2-22 2-23 Mantissa Mantissa Example (binary): 40 FO 00 00 (hex) = 0100 0000 1111 0000 0000 0000 0000 0000 Formula: value = (-1)vz * 2(Exponent—1271 * (1 + Mantissa) value = (-1)o * 2(129—127) * (1 + 2-1 + 2-2+ 2-3) value = 1 * 4 * (1 + 0.5 + 0.25 + 0.125) value = 7.5 02/2011 -4001086601 -AD IFC 300 PROFIBUS R01 en www.krohne.com 25 APPLICATION PROFILE 4.2.2 Status value The meanings of the status byte (unsigned integer) are described in the following tables. Qua!it Quality substatus Limits Gr Gr QS QS QS QS Qu Qu 27 26 25 24 23 22 21 20 0 0 =bad 0 1 =uncertain 1 0 =good (Non Cascade) 1 1 =good (Cascade) - not supported Status = bad Quality Quality substatus Limits Gr Gr QS QS QS QS Qu Qu 27 26 25 24 23 22 21 20 0 0 0 0 0 0 =non-specific 0 0 0 0 0 1 =configuration error 0 0 0 0 1 0 =not connected 0 0 0 0 1 1 =device failure 0 0 0 1 0 0 =sensor failure 0 0 0 1 0 1 =no communication (last usable value) 0 0 0 1 1 0 =no communication (no usable value) 0 0 0 1 1 1 =out of service Status = uncertain Quality Quality substatus Limits Gr Gr QS QS QS QS Qu Qu 27 26 25 24 23 22 21 20 0 1 0 0 0 0 =non-specific 0 1 0 0 0 1 =last usable value 0 1 0 0 1 0 =substitute-set 0 1 0 0 1 1 =initial value 0 1 0 1 0 0 =sensor conversion not accurate 0 1 0 1 0 1 =engineering unit violation (unit not in the valid set) 0 1 0 1 1 0 =sub-normal 0 1 0 1 1 1 =configuration error 0 1 1 0 0 0 =simulated value 26 www.krohne.com 02/2011 -4001086601 -AD IFC 300 PROFIBUS R01 en APPLICATION PROFILE p Status = good (Non Cascade) Quality Quality substatus a Limits Gr Gr QS QS QS QS Qu Qu 27 26 25 24 23 22 21 20 1 0 0 0 0 0 =ok 1 0 0 0 0 1 =update event 1 0 0 0 1 0 =active advisory alarm (priority< 8) 1 0 0 0 1 1 =active advisory alarm (priority> 8) 1 0 0 1 0 0 =unacknowledged update event 1 0 0 1 0 1 =unacknowledged advisory alarm 1 0 0 1 1 0 =unacknowledged critical alarm 1 0 1 0 0 0 =initiate fail safe 1 0 1 0 0 1 =maintenance required Status = Limits Quality Quality substatus Limits Gr Gr QS QS QS QS Qu Qu 27 26 25 24 23 22 21 20 0 0 =ok 0 1 =low limited 1 0 =high limited 1 1 =constant Check the first two quality bits in order to get the quality information of the measurement value: • Good (Non Cascade):function block output value is ok and can be used without restrictions • Good (Cascade):will not be supported, because it is not applicable for the device • Uncertain:function block output value can be used but the accuracy can not be guaranteed (e.g. function block outputs value has been frozen or A/D converter is saturated or out of range) • Bad:function block output value is bad - don't use it for process control! The "Qua lity-Substatus" and "Limit" bits will be used for further diagnostics or limit checking. /NFORMA T/ON! The status should be monitored because a number will be transmitted even if the status of the measurement value is bad or uncertain. This is the only way to check the quality of the transmitted measurement values. 02/2011-4001086601-AD IFC 300 PROFIBUS R01 en www.krohne.com 27 APPLICATION PROFILE 4.3 Diagnosis parameter 4.3.1 Diagnosis Parameter DIAGNOSIS will contain detailed information of the device, bitwise coded. More than one message possible at once (as below-mentioned). If MSB of byte 4 is set to 1 than more diagnose information is available in the DIAGNOSIS—EXTENSION parameter. The manufacturer specific parameter"DIAGNOSIS—EXTENSION"will contain bitwise coded more detailed information of the internal status conditions and error conditions of the PROFIBUS device. The corresponding GSD file will contain all messages supported by this device - have a look at the UNIT DIAG BIT(i) definitions. 4.3.2 DIAGNOSIS (if "Classic Status" and "Diagnosis" selected) ` L N O' N -0 L Gl O C E N E C .0 C 0 ++ !0 L N C O m to c 0 1 0 DIA HW ELECTR 0 Hardware failure electronics 1 DIA HW MECH 0 Hardware failure mechanics 2 DIA_TEMP_MOTOR 0 Motor temperature too high 3 DIA_TEMP_ELECTR 0 Electronic temperature too high 4 DIA MEM CHKSUM 0 Memory error 5 DIA MEASUREMENT 0 Measurement failure 6 DIA NOT INIT 0 Device not initialized 7 DIA INIT ERR 0 Device initialization failed 2 0 DIA ZERO ERR 0 Zero point error 1 DIA_SUPPLY 0 Power supply failed 2 DIA CONF INVAL 0 Configuration invalid 3 DIA_WARMSTART A 0 Restart(warmstart) 4 DIA COLDSTART A 0 Coldstart(with default data) 5 DIA MAINTENANCE R 0 Maintenance required 6 DIA CHARACT R 0 Characteristics invalid 7 IDENT_NUMBER_VIOLATION R 0 Ident. No.violation: Set to 1 if the Ident Number of the running cyclic data transfer and the value of physical block IDENT NUMBER—SELECTOR parameter are different 28 www.krohne.com 02/2011 -4001086601 -AD IFC 300 PROFIBUS R01 en APPLICATION PROFILE L L 41 N +�+ C- N E N E C76 0 C EM .0 - - L z Q M M DL N C G V V O m un c 0 omiftL 3 0 Reserved 0 Reserved for use by PNO 1 Reserved 0 Reserved for use by PNO 2 Reserved 0 Reserved for use by PNO 3 Reserved 0 Reserved for use by PNO 4 Reserved 0 Reserved for use by PNO 5 Reserved 0 Reserved for use by PNO 6 Reserved 0 Reserved for use by PNO 7 Reserved 0 Reserved for use by PNO 4 0 Reserved 0 Reserved for use by PNO 1 Reserved 0 Reserved for use by PNO 2 Reserved 0 Reserved for use by PNO 3 Reserved 0 Reserved for use by PNO 4 Reserved 0 Reserved for use by PNO 5 Reserved 0 Reserved for use by PNO 6 Reserved 0 Reserved for use by PNO 7 EXTENSION—AVAILABLE 0 Extension available: More diagnose information available in the Diagnosis—Extension parameter(if available) 02/2011-4001086601-AD IFC 300 PROFIBUS R01 en www.krohne.com 29 APPLICATION PROFILE 4.3.3 DIAGNOSIS_EXTENSION (if "Classic Status" and "Diagnosis" selected) L � N � L d E °' E +' L c : c E a� c .0 E U *� = o O m toaA6M U AM6m M 1 0 ADC_ELEC_TEMPERATURE (S) electronic temperature 1 ADC—GAIN—ERROR (S) gain error 2 ADC_F_FREQ_T00_HIGH (S)field frequency too high 3 Reserved 4 ADC COIL TEMPERATURE (S)coil temperature 5 ADC F CURR DEVIATION (S)field current deviation 6 ADC F COIL BRIDGED (S)field coil bridged 7 ADC F COIL BROKEN (S)field coil broken 2 0 ADC—ELECTRODE—NOISE (S) electrode noise 1 ADC—FLOW—PROFILE (S)flow profile 2 ADC—LINEARITY (S) linearity 3 ADC ELECTRODE SYM (S)electrode symmetry 4 Reserved 5 Reserved 6 ADC—PIPE—NOT—FULL (S) pipe not full 7 ADC—EMPTY—PIPE-0 (S) empty pipe (Uncertain) 3 0 Reserved 1 ADC FIELD FREQ_HIGH (F)field frequency too high 2 ADC—EMPTY—PIPE-1 (F)empty pipe (Application Error) 3 ADC—DC—OFFSET (F) DC Offset 4 Reserved 5 ADC_FIELD_CURR_LOCAL (F)field current local 6 ADC—SENSOR—LOCAL M sensor local 7 ADC—SENSOR—GLOBAL (F)sensor global 4 0 ADC—FLOW—EXCEED—LIMO (F)flow exceeding limit 1 ADC FLOW EXCEED LIM1 (F)flow exceeding limit 2 MEAS AVAILABLE NO (1) measurement value not available 3 POWER ON ERROR (1) power fail 4 ADC—TEST—SENSOR (C)test sensor 5 ADC WARNING W1 (S) uncertain measurement 6 ADC_WARNING_W2 (F)application error 7 ADC—SENSOR—ELECTRONIC (F)sensor electronic 30 www.krohne.com 02/2011 -4001086601 -AD IFC 300 PROFIBUS R01 en APPLICATION PROFILE L L � L d E E +' L c :3 n E a� c M E U *' = o O m N U mkmw 5 0 BM_TEST_ACTIV (C) checks in progress(global) 1 BM_MEAS_UNC (S) uncertain measurement(global) 2 BM APP ERROR (F)application error(global) 3 BM_DEV_ERROR (F)error in device(global) 4 NO BASIC DEVICE COM (F)int.communication timeout 5 PARA UPDATE ERROR (F)parameter update error 6 PARA UPDATE IN PROGRESS update in progress 7 ERROR_CPU_CM (F)CPU failure 6 0 ERROR—EEPROM (F) EEPROM failure 1 CYCLE_EEPROM (S) EEPROM cycle overflow 2 ERROR_CPU_MEM (F)CPU Memory failure 3 ERROR_RAM_EXT (F)ext. RAM failure 4 ERROR FRAM (F) FRAM failure 5 CYCLE—FRAM (S) FRAM cycle overflow 6 ERROR_FLASH_EXT (F)external Flash failure 7 ERROR_SPC4 (F)SPC4 failure *: for a more detailed description of the above-mentioned subparameters please check the signal converter handbook (section: Status messages and diagnostic information) (F): Device Error (F):Application Error (S): Uncertain measurement/measurement out of specification (C): Simulation of the measured value (1): Information 4.3.4 Mapping of DIAGNOSIS—EXTENSION bits into DIAGNOSIS bits How to read this table: If e.g. an ADC—EMPTY—PIPE-0 error has been detected by the device itself the below-mentioned DIAGNOSIS EXTENSION bits will be set: • DIAGNOSIS EXTENSION (Octet 2/ Bit 7): ADC EMPTY PIPE 0 • DIAGNOSIS EXTENSION (Octet 4/ Bit 5): ADC WARNING W1 • DIAGNOSIS EXTENSION (Octet 5/ Bit 1): BM MEAS UNC These bits will be mapped to the below-mentioned DIAGNOSIS bits (which will be set additionally): • DIAGNOSIS (Octet 1 /Bit 5): DIA MEASUREMENT • DIAGNOSIS (Octet 4/Bit 7): EXTENSION AVAILABLE 02/2011-4001086601-AD IFC 300 PROFIBUS R01 en www.krohne.com 31 APPLICATION PROFILE DIAGNOSIS-EXTENSION DIAGNOSIS 1 2 3 ... 4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 0 ... 6 7 c o w J m Z W > J_ w N X Q Q �I a L V U O J = W t- d' Z Q Z H LU W Q a, J W �I wl v Z w w1 J I N N a Z w a s I cn —I I o a LL Z O m I I g g x Q t— t— w a Z J a Z m c E xx z o N e X X W Ln L) vv Z W fl- m m W 0 X o m cn o 0 0 0 0 0 0 0 0 0 0 0 0 0 0 w w 1 0 ADC_ELEC_TEMPERATURE X X 1 ADC-GAIN-ERROR X 2 ADC_F_FREQ_T00_HIGH X X 3 Reserved 4 ADC-COIL-TEMPERATURE X X 5 ADC_F_CURR_DEVIATION X X 6 ADC_F_COIL_BRIDGED X X 7 ADC_F_COIL_BROKEN X X 2 0 ADC-ELECTRODE-NOISE X X 1 ADC-FLOW-PROFILE X X 2 ADC-LINEARITY X X 3 ADC_ELECTRODE_SYM X X 4 Reserved 5 Reserved 6 ADC_PIPE_NOT_FULL X 7 DC-EMPTY-PIPE-0 X X 3 0 Reserved 1 ADC_FIELD_FREQ_HIGH X X 2 ADC-EMPTY-PIPE-1 X X 3 ADC-DC-OFFSET X X 4 Reserved 5 ADC_FIELD_CURR_LOCAL X 6 ADC SENSOR LOCAL X 7 ADC-SENSOR-GLOBAL X 32 www.krohne.com 02/2011 -4001086601 -AD IFC 300 PROFIBUS R01 en APPLICATION PROFILE 13 DIAGNOSIS—EXTENSION DIAGNOSIS 1 2 3 ... 4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 0 ... 6 7 c o W � J m z W > J VLu J H ZLu I N L L U U O J = W H a' a' z H a z ~ m Q N W W a' U m w aI aI UI N zI WI C) a aI 0 Z z O f0 3: �I w w W W 0 ~ w M 0 a o a = zI N c E o x x f X z z ry cn U 3 U U z a, c Q I I I I I I I —I I I I I I I I Z a� W U :3a_ a_ a_ a_ a_ a_ a_ a_ a_ a_ a_ a_ a_ a_ Q_ W tn O m (n B 0 c 0 0 0 0 E E 2 a' a' W 4 0 ADC—FLOW—EXCEED—LIMO X X 1 ADC_FLOW_EXCEED_LIM1 X X 2 MEAS_AVAILABLE NO X 3 POWER ON ERROR X 4 ADC—TEST—SENSOR X 5 ADC_WARNING_W1 X X 6 ADC_WARNING_W2 X X 7 ADC—SENSOR—ELECTRONIC X 5 0 BM_TEST_ACTIV X 1 M—MEAS—UN IEF X X 2 BM_APP_ERROR X X 3 BM_DEV_ERROR X X 4 NO_BASIC_DEVICE_COM X X 5 PARA UPDATE ERROR X X 6 PARA UPDATE IN X X PROGRESS 7 ERROR—CPU—CM X 6 0 ERROR_EEPROM X 1 CYCLE_EEPRO M X X 2 ERROR_CPU_MEM X 3 ERROR_RAM_EXT X 4 ERROR—FRAM X 5 CYCLE—FRAM X X 6 ERROR FLASH EXT X 7 ERROR SPC4 X .:Ext_Diag (Bit 3 of Station_Status_1)will be set too! X :Corresponding DIAGNOSIS bits is set to 1 if status occured 02/2011-4001086601-AD IFC 300 PROFIBUS R01 en www.krohne.com 33 PROFIBUS SETTINGS For a detailed description of the menus and functions refer to the standard product documentation of the signal converter. Some special settings concerning the PROFIBUS features are easily operated via the local display menu (refer to the following sections). 5.1 Menu A, quick setup Function Settings/descriptions A2 Tag A2 Tag Tag descriptor of the physical block of the PROFIBUS module will be displayed.The Tag descriptor provides an application specific reference to the blocks. It will be assigned by the user of the device.The Tag descriptor is an octet string (a visible string will be preferred) consisting of 32 byte.The first 21 characters will be displayed only! A3 reset A3 reset - A3.1 reset errors This menu function can be used to reset all errors that are not removed automatically(power fail,totalizer overflow) reset?Select: no/yes no: Exit the function. yes: Resets the errors and exits the function. The following reset menus for the totalizer are only available, if the quick access has been activated in the menu "setup >device> quick setup". Each totalizer can be activated for quick access independently. A3.2 FB2 totalizer 1 For PROFIBUS devices:The totalizer can be reset to zero in this menu. A3.3 FB3 totalizer 2 A3.4 FB4 totalizer 3 A4 station address A4 station address Selects the address of the device at the PROFIBUS interface. The PROFIBUS address can also be changed using the PROFIBUS service .'set—slave—add".The input range is 0...125 according to the PROFIBUS specification.Address 126 is the default address and cannot be set via the PROFIBUS service "set slave add" - use menu instead to reset to default address. 5.2 Menu B, test [No. Function Settings/descriptions ' B3 information B3.5 PROFIBUS Available if there is a PROFIBUS interface in existence;displays the following mentioned information about the PROFIBUS interface: Ident No./software revision no.of the PROFIBUS software/production date 34 www.krohne.com 02/2011 -4001086601 -AD IFC 300 PROFIBUS R01 en PROFIBUS SETTINGS 5.3 Menu C, setup [N:0- Function Settings/descriptions 1 C3 1/0 totalizer C3.1 FB2 totalizer 1 Set function of totalizer❑ C3.2 FB3 totalizer 2 ❑stands for 1,2,3 (=totalizer 1, 2,3) C3.3 FB4 totalizer 3 C3.El.1 funct. of totalizer Select: sum totalizer(counts positive and negative values)/ +totalizer(counts only the positive values)/ -totalizer(counts only the negative values)/ hold totalizer(totalizer is stopped, no counting)/ all as positive(neg. input will be multiplied with -1.0)/ all as negative (pos.values will be multiplied with 1.0) C3.❑.2 measurement Selection of the measurement for totalizer❑ Select:volume flow/mass flow(not valid for PF(partly filled)) C3.❑.3 preset value Predefines a threshold (using high low limit value of the totalizer affected; the THRESHOLD bit will be set in the long status information bytes of the interface if the actual value of the totalizer is outside these limits.This can be also used for a status output. C3.❑.4 reset totalizer The current value of the totalizer can be set to zero. Select: no/yes(reset totalizer 1...3) C3.❑.5 error behaviour Defines the behaviour of this function block in case of errors. Select: hold meas.value/ignore error/stop totalizer hold meas.value:Totalization is continued based on the last incoming value with good status before the first occurrence of bad status. ignore error:Totalization is continued using the input values despite the bad status.The status is ignored. stop totalizer:Totalization is stopped during occurrence of bad status of incoming values. C3.❑.6 information Serial no. of the 1/0 board,software version no.and production date of the circuit board will be displayed C4 1/0 PROFIBUS C4 1/0 PROFIBUS Using the menu functions mentioned below you will be able to control basically the five analog input blocks of this PROFIBUS device.These five menus are identical so they are grouped together and their functions are described in one go. C4.1 FB1 analog inp. There are 5 analog input blocks. C4.2 FB5 analog In El stands for the 5 analog input blocks: FB1 (❑= 1), FB5(❑=2), FB6(❑=3), g p• FB7(❑=4)and FB8(❑=5) C4.3 FB6 analog inp. C4.4 FB7 analog inp. C4.5 FB8 analog inp. C4.❑.1 measurement Select measurement for the analog input blocks: flow speed/volume flow/mass flow not valid for PF(partly filled))/coil temperature/conductivity(not valid for PF(partly filled)and CAP (capacitive))/temperature(electronic temperature)/supply(internal supply voltage for PROFIBUS interface) C4.0.2 time constant Set time constant for this function block(❑). 02/2011-4001086601-AD IFC 300 PROFIBUS R01 en www.krohne.com 35 PROFIBUS SETTINGS Function Settings/descriptions FEL3 error behaviour Defines the behaviour of this function block in case of errors. Select: hold value/ignore error/replace value hold value: Last valid OUT value stored will be used as OUT value. ignore error:OUT has the wrong calculated value and status"Bad" as calculated. replace value:The"replacement value"will be used as OUT value. C4.❑.4 replacement value Available, if the error behaviour"replace value" is selected. Defines the value that replaces the measured value at this function block in case of an error. C5 device C5.1.1 Tag Tag descriptor of the physical block of the PROFIBUS module will be displayed.The Tag descriptor provides an application specific reference to the blocks. It will be assigned by the user of the device.The Tag descriptor is an octet string (a visible string will be preferred) consisting of 32 byte.The first 21 characters will be displayed only! C5.3 1. meas. page Setting of the measurement for the 1 st measuring page. C5.3.2 measurement 1.1ine Specify measurement for 1st line. Select:volume flow/mass flow(not valid for PF(partly filled))/diagnosis value/flow speed/coil temperature/conductivity(not valid for PF(partly filled))and CAP(capacitive))/level(only valid for PF(partly filled)) C5.3.8 measurement 2.line Specify measurement of 2nd line(only available if this 2.line is activated) Select: bar graph (for the measurement selected in the first line)/volume flow/mass flow(not valid for PF(partly filled))/diagnosis value/flow speed/FB2 totalizer 1 /FB3 totalizer 2/FB4 totalizer 3/conductivity(not valid for PF(partly filled)and CAP(capacitive))/coil temperature/operating hours/level(only valid for PF(partly filled)) C5.3.10 measurement 3.line Specify measurement of 3rd line(only available if this 3.line is activated) Select:volume flow/mass flow(not valid for PF(partly filled))/diagnosis value/flow speed/coil temperature/conductivity(not valid for PF(partly filled) and CAP(capacitive))/FB2 totalizer 1 /FB3 totalizer 2/ FB4 totalizer 3/operating hours/level(only valid for PF(partly filled))/ current input A/current Input B C5.4 2. meas. page Setting of the measurement for the second measuring page. For PROFIBUS devices this page shows only the PROFIBUS values FB1...FB8. C5.4.1 measurement 1.line Select the measurement of the 1st,2nd and 3rd line: C5.4.3 measurement 2.line F61 analog inp./FB2 totalizer 1 /FB3 totalizer 2/FB4 totalizer 3/FB6 C5.4.5 measurement 3.line analog inp./F67 analog inp./FB8 analog inp. C5.4.2 format Mine Fixed number of digits after the decimal point or automatic,where the C5.4.4 format 2.line number of digits is automatically adjusted to the available space. C5.4.6 format 3.line C5.6 special functions - 05.6.1 reset errors This menu function can be used to reset all errors that are not removed automatically(power fail,totalizer overflow) reset?Select: no/yes C5.6.2 save settings Save current settings. Select: break(exit function without saving)/backup 1 (save in storage Location 1)/backup 2(save in storage location 2) Query:continue copy?(cannot be undone) Select: no (exit function without saving)/yes(copy current settings to storage backup 1 or backup 21 36 www.krohne.com 02/2011 -4001086601 -AD IFC 300 PROFIBUS R01 en PROFIBUS SETTINGS Function Settings/descriptions C5.6.3 load settings Load saved settings. Select: break(exit function without loading)/factory settings (load in state as delivered)/backup 1 (load data from storage location I/backup 2(load data from storage location 21/load sensor data (factory settings of calibration data] Query:continue copy?(cannot be undone) Select:no(exit the function without saving)/yes(load data from the selected storage location) C5.8 physical block This menu is only available, if a PROFIBUS interface is present. C5.8.1 station address Selects the PROFIBUS station address of the device. The PROFIBUS address can also be changed using the PROFIBUS service ..set—slave—add".The input range is 0...125 according to the PROFIBUS specification.Address 126 is the default address and cannot be set via the PROFIBUS service "set slave add" - use menu instead to reset to default address. C5.8.2 information Available if there is a PROFIBUS interface in existence;displays the following mentioned information about the PROFIBUS interface: Ident No./software revision no.of the PROFIBUS software/production date C5.8.3 diag.extension Content of the PROFIBUS diagnosis extension is displayed. C5.8.4 diag.extension 2 Content of the additional, internal diagnosis stored is displayed. C5.8.6 diag.extension h h=history Content of the PROFIBUS diagnosis extension is displayed. Shows diagnosis information of all diagnosis bits,which are set again since the last delete. C5.9 quick setup Activate quick access in quick setup menu; default setting:quick setup is active(yes) Select:yes(switched on)/no (switched off) C5.9.1 reset totalizer 1 The reset can be activated in the"quick setup"to get a quick access of the C5.9.2 reset totalizer 2 function. Select:yes (activated)/no (switched off) C5.9.3 reset totalizer 3 02/2011-4001086601-AD IFC 300 PROFIBUS R01 en www.krohne.com 37 PROFIBUS SETTINGS 5.4 Menu D, service This menu is protected. You will need to use the service password to gain access. No. ILFunction Settings/descriptions D2 service parameters In this menu all functions related to different data sets can be found. D2.1 cold start Resetting of the signal converter can be done here but all changes up to this point are automatically stored and cannot be discarded. Select: no(terminates the function)/yes(performs the reset and leaves the setting model D2.2 save factory data Copies the actual data into the factory setting;this overwrites the factory settings done during calibration! Query:save settings?(cannot be undone) Select: break(exit function without saving)/factory settings (saves the settings as factory settings) Query:continue copy?(cannot be undone) Select: no (exit function without saving)/yes(copy current settings to the selected storage location) D2.9 Identification No. Sets different device modes for the cyclic communication of the PROFIBUS interface. Select:signal converter(the normal settings incl.all manufacturer specific parameters are supported)/profile (uses only the profile defined functions, no extras, only profile specific parameters are supported)/IFC090 (compatibility mode) D2.10 PB cold start Initiates a PROFIBUS cold start. During a PROFIBUS cold start nearly all parameter values of the whole device will be set to their default values(Exceptions are the PROFIBUS address and the identification No.).The cold start will be carried out without disconnecting an already established connection to a PROFIBUS master system. Query: reset?(to default values)=cold start begins Select: no(terminates the function)/yes(PROFIBUS cold start will be carried out at once;the setting mode is terminated) D2.12 diag. extension h h=history Delete the stored history. Query: reset?=reset history to 0) Select: no(no change)/yes(all saved data are deleted) 38 www.krohne.com 02/2011 -4001086601 -AD IFC 300 PROFIBUS R01 en NOTES A 02/2011-4001086601-AD IFC 300 PROFIBUS R01 en www.krohne.com 39 r� r . rti,y • •• M• • • •• AW to ri KROHNE product overview • Electromagnetic flowmeters • Variable area flowmeters • Ultrasonic flowmeters • Mass flowmeters s • Vortex flowmeters 3 • Flow controllers 0 • Level meters • Temperature meters • Pressure meters 0 • Analysis products • Measuring systems for the oil and gas industry LL • Measuring systems for sea-going tankers a 0 0 U LL O a Head Office KROHNE Messtechnik GmbH Ludwig-Krohne-Str. 5 D-47058 Duisburg (Germany) 0 Tel.:+49 (0)203 301 0 N Fax:+49 (0)203 301 10389 0 z infofdkrohne.de & The current list of all KROHNE contacts and addresses can be found at: KROHNE Y o www.krohne.com