HomeMy WebLinkAboutAP_IFC 100_W_en_IECEx_090923__ IECEx Certificate
of Conformity
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com
Certificate No.: IECEx KEM 09.0042X issue No.:O', Certificate history:
Status: Current
Date of Issue: 2009-09-23 Page 1 of 4
Applicant: Krohne Altometer
Kerkeplaat 12
3313 LC Dordrecht
The Netherlands
Electrical Apparatus: Signal Converter
Optional accessory:
Type of Protection: a[ia]mb,tD
Marking: Ex a[ia]mb IIC T4
Ex tD A21 IP64 T 135°C
Approved for issue on behalf of the IECEx T.Pijpker
Certification Body:
Position: Certification Ma a er
Signature:
(for printed version)
Date: 2,00 o _ ,L 3
1.This certificate and schedule may only be reproduced in full.
2.This certificate is not transferable and remains the property of the issuing body.
3.The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
Certificate issued by:
KEMA Quality B.V.
Utrechtseweg 310
6812 AR Arnhem
The Netherlands
IECEx Certificate
of Conformity
Certificate No.: IECEx KEM 09.0042X
Date of Issue: 2009-09-23 Issue No.:0
Page 2 of 4
Manufacturer: Krohne Altometer
Kerkeplaat 12
3313 LC Dordrecht
The Netherlands
Manufacturing Iocation(s):
This certificate is issued as verification that a sample(s), representative of production,was assessed and tested and
found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products
covered by this certificate,was assessed and found to comply with the IECEx Quality system requirements.This
certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational
Documents as amended.
STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified
documents,was found to comply with the following standards:
IEC 60079-0 : 2004 Electrical apparatus for explosive gas atmospheres-Part 0: General requirements
Edition:4.0
IEC 60079-11 : 2006 Explosive atmospheres-Part 11:Equipment protection by intrinsic safety"i"
Edition:5
IEC 60079-18 : 2004 Electrical apparatus for explosive gas atmospheres-Part 18: Construction,test and
Edition: 2.0 marking of type of protection encapsulation'm'electrical apparatus
IEC 60079-7 : 2006-07 Explosive atmospheres-Part 7: Equipment protection by increased safety"e"
Edition:4
IEC 61241-0 : 2004 Electrical apparatus for use in the presence of combustible dust-Part 0: General
Edition: 1 requirements
IEC 61241-1 : 2004 Electrical apparatus for use in the presence of combustible dust-Part 1: Protection by
Edition: 1 enclosures"0'
This Certificate does not indicate compliance with electrical safety and performance requirements other than those
expressly included in the Standards listed above.
TEST&ASSESSMENT REPORTS:
A sample(s)of the equipment listed has successfully met the examination and test requirements as recorded in
Test Report:
N L/KEM/ExTR09.0043/00
Quality Assessment Report:
N L/KEM/QAR09.0012/00
IECEx Certificate
of Conformity
Certificate No.: IECEx KEM 09.0042X
Date of Issue: 2009-09-23 Issue No.:0
Page 3of4
Schedule
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
The Signal Converter type IFC 100 W for wall mounting is intended for the supply of the field coils
of electro magnetic flowmeters and for the conversion of the electrode measurement signals into a
4-20 mA output signal (with HART communication).
CONDITIONS OF CERTIFICATION:YES as shown below:
-The ambient temperature range and electrical data see are not marked on the nameplate.See Attachment for details.
-The field coil circuit shall be connected to a passive load only.
IECEx Certificate
of Conformity
Certificate No.: IECEx KEM 09.0042X
Date of Issue: 2009-09-23 Issue No.:0
Page 4 of 4
Additional information:
Annexe: Attachment 1 to IECEx.doc