CERTIFICATE OF COMPLIANCE
HAZARDOUS (CLASSIFIED) LOCATION ELECTRICAL EQUIPMENT
This certificate is issued for the following equipment:
OPTIFLUX 1000-DIV2 VN174abcdefghijk/mn. Primary Head.
NI / I /2/ABCD/T6; Type 4X, Type 6, *Type 6P; *IP68
S/ II, III /2 / FG/T6; Type 4X, Type 6, *Type 6P; *IP68
a= Nominal Diameter: 5, 6, 8, B, C, E, F or H.
b = Nominal Pressure: A or B.
c=Approval: 5
d = Systems Design: 1, 2, 3, 4, 6, A or C.
e = Converter Model: C or D.
f= Mounting Material: Not Safety Relevant
g = Grounding ring material: Not Safety Relevant
h = Electrodes: 0.
i = Protection Class: 0 or 2.
j = Cable: 2 (Type 6P); Other—Not Safety Relevant
k= Cable Length: Not Safety Relevant
I = Calibration: Not Safety Relevant
m = Construction requirements: Not Safety Relevant
n = QA/QC requirements: Not Safety Relevant
Special conditions of use:
1. OPTIFLUX Primary Head must be used with the IFC 300 F-DIV2, IFC 300 F(h)-DIV2 or IFC 090-F
DIV2 signal converters.
2. I.S. Electrodes when used with IFC 300 F-DIV2, IFC 300 F(h)-DIV2 or IFC 090-F DIV2 signal
converters.
3. *Enclosure Type 6P& 1P68 rating only applies when configured with Stainless Steel Connection Box.
3022275
Page 1 of 9
CfM 00rouals
OPTIFLUX 2000-DIV2 VN144abcdefghijklmnop Primary Head.
NI / I /2/ABCD/T6; Type 4X, Type 6, *Type 6P; *IP68
S/ II, III /2 / FG /T6; Type 4X, Type 6, *Type 6P; *IP68
a = Nominal diameter: 4, 5, 6, 7, 8, A, B, C or D
b= Nominal pressure: 3, 4, 5, A or B
c=Approval: 5
d = Cable connection: 1, 2, 4, 6, A or C
e = Converter model: C or D
f= Lining: not safety relevant
g = Electrode: 1, 3 or 6
h = Construction of electrodes: 1
i = Housing/flange material: 1, 3 or 4
j = Protection class/dimension: 0 or 2
k= Cable: 2 (Type 6P); Other-Not Safety Relevant
I = Cable length: not safety relevant
m = Calibration: not safety relevant
n = G-P-Ring/Material: not safety relevant
o= Special: 0
p= Module/labeled: 1
Special conditions of use:
1. OPTIFLUX Primary Head must be used with the IFC 300 F-DIV2, IFC 300 F(li)-DIV2 or IFC 090-F
DIV2 signal converters.
2. /.S. Electrodes when used with IFC 300 F-DIV2, IFC 300 F(l)-DIV2 or IFC 090-F DIV2 signal
converters.
3. *Enclosure Type 6P&IP68 rating only applies when configured with Stainless Steel Connection Box.
OPTIFLUX 2000-DIV2 VN154abcdefghijklmnop Primary Head.
NI / I /2/ABCD/T6; Type 4X, Type 6, *Type 6P; *IP68
S/ II, III /2/ FG/T6; Type 4X, Type 6, *Type 6P; *IP68
a= Nominal diameter: E, F, G, H, K, L, M or N
b= Nominal pressure: 2, 3, 4, 5, A or B
c=Approval: 5
d = Cable connection: 1, 2, 4, 6, A or C
e= Converter model: C or D
f= Lining: not safety relevant
g = Electrode: 1, 3 or 6
h = Construction of electrodes: 1
i = Housing /flange material: 1, 3 or 4
j = Protection class\dimension: 0 or 2
k= Cable: 2 (Type 6P); Other-Not Safety Relevant
I = Cable length: not safety relevant
m = Calibration: not safety relevant
n = G-P-Ring /Material: not safety relevant
o = Special: 0
p = Module/labeled: 1
Special conditions of use:
1. OPTIFLUX Primary Head must be used with the IFC 300 F-DIV2, IFC 300 F(/i)-DIV2 or IFC 090-F DIV2
signal converters.
2. 1.S. Electrodes when used with IFC 300 F-DIV2, IFC 300 F(li)-DIV2 or IFC 090-F DIV2 signal
converters.
3. *Enclosure Type 6P&IP68 rating only applies when configured with Stainless Steel Connection Box.
3022275
Page 2 of 9
C[M pprouals
OPTIFLUX 2000-DIV2 VN164abcdefghijklmnop Primary Head.
NI I I /2/ABCD/T6; Type 4X, Type 6, *Type 6P; *IP68
S/ II, III /2/ FG/T6; Type 4X, Type 6, *Type 6P; *IP68
a= Nominal diameter: up to a maximum of 120" at 276 psi
b = Nominal pressure: 1, 2 or A
c=Approval: 5
d = Cable connection: 1, 2, 4, 6, A or C
e= Converter model: C or D
f= Lining: not safety relevant
g = Electrode: 1, 3 or 6
h = Construction of electrodes: 1
i = Housing/flange material: 1, 3 or 4
j = Protection class/dimension: 0 or 2
k= Cable: 2 (Type 613); Other-Not Safety Relevant
I = Cable length: not safety relevant
m = Calibration: not safety relevant
n = G-P-Ring /Material: not safety relevant
o = Special: 0
p = Module/labeled: 1
Special conditions of use.-
1. OPTIFLUX Primary Head must be used with the IFC 300 F-DIV2, IFC 300 F(fl)-DIV2 or IFC 090-F DIV2
signal converters.
2. /.S. Electrodes when used with IFC 300 F-DIV2, IFC 300 F(/i)-DIV2 or IFC 090-F DIV2 signal
converters.
3. *Enclosure Type 6P&IP68 rating only applies when configured with Stainless Steel Connection Box.
OPTIFLUX 4000-DIV2 VN024abcdefghijklmnop Primary Head.
NI / I /2/ABCD/T6; Type 4X, Type 6, *Type 6P; *IP68
S/II, III /2/ FG/T6; Type 4X, Type 6, *Type 6P; *IP68
a = Nominal diameter: 1, 2, 3, 5, 6 or 7
b = Nominal pressure: A or B
c=Approval: 5
d = Cable connection: 1, 2, 4 or A
e= Converter model: C or D
f= Lining: not safety relevant
g = Electrode: 1, 2, 3, 4, 5, 6, 7, G or U
h = Construction of electrodes: 1
i= Housing /flange material: 1, 3, 4, E, G, K, M or N
j = Protection class/dimension: 0 or 2
k = Cable: 2 (Type 6P); Other-Not Safety Relevant
I = Cable length: not safety relevant
m = Calibration: not safety relevant
n = G-P-Ring/Material: not safety relevant
o= Special: 0
p= Module I labeled: 1
Special conditions of use.-
1. OPTIFLUX Primary Head must be used with the IFC 300 F-DIV2, IFC 300 F(/i)-DIV2 or IFC 090-F DIV2
signal converters.
2. /.S. Electrodes when used with IFC 300 F-DIV2, IFC 300 F(/i)-DIV2 or IFC 090-F DIV2 signal
converters.
3. *Enclosure Type 6P& IP68 rating only applies when configured with Stainless Steel Connection Box.
3022275
Page 3 of 9
IM Approvals
OPTIFLUX 4000-DIV2 VN034abcdefghijklmnop Primary Head.
NI / I /2 /ABCD/T6; Type 4X, Type 6, *Type 6P; *IP68
S/ Il, III /2 /FG/T6; Type 4X, Type 6, *Type 6P; *IP68
a = Nominal diameter: 1, 2, 3, 4, 5, 6, 7, 8, A, B, C or D
b= Nominal pressure: 3, 4, 5, A, B, D or E
c= Approval: 5
d = Cable connection: 1, 2, 4, 6, A or C
e= Converter model: C or D
f= Lining: not safety relevant
g = Electrode: 1, 2, 3, 4, 5, 6, 7, G or U
h = Construction of electrodes: 1
i = Housing/flange material: 1, 2, 3, 4, A, B, C, D, K, L, M or N
j = Protection class/dimension: 0 or 2
k= Cable: 2 (Type 6P);Other-Not Safety Relevant
I = Cable length: not safety relevant
m = Calibration: not safety relevant
n = G-P-Ring/Material: not safety relevant
o= Special: 0
p= Module/labeled: 1
Special conditions of use:
1. OPTIFLUX Primary Head must be used with the IFC 300 F-DIV2, IFC 300 F(h)-DIV2 or IFC 090-F
DIV2 signal converters.
2. I.S. Electrodes when used with IFC 300 F-DIV2, IFC 300 F(l)-DIV2 or IFC 090-F DIV2 signal
converters.
3. *Enclosure Type 6P&IP68 rating only applies when configured with Stainless Steel Connection Box.
OPTIFLUX 4000-DIV2 VN044abcdefghijklmnop Primary Head.
NI/I/2/ABCD/T6; Type 4X, Type 6, *Type 6P; *IP68
S/II, III /2/ FG/T6; Type 4X, Type 6, *Type 6P; *IP68
a = Nominal diameter: E, F, G, H, K, L, M or N
b = Nominal pressure: 2, 3, 4, 5, A or B
c=Approval: 5
d = Cable connection: 1, 2, 4, 6, A or C
e = Converter model: C or D
f= Lining: not safety relevant
g = Electrode: 1, 3, 4, 5, 6, 7, G, M, R or U
h = Construction of electrodes: 1
i = Housing/flange material: 1, 3, 4, A, C, D, K, M or N
j = Protection class/dimension: 0 or 2
k= Cable: 2 (Type 6P); Other-Not Safety Relevant
I = Cable length: not safety relevant
m = Calibration: not safety relevant
n = G-P-Ring/Material: not safety relevant
o= Special: 0
p = Module/ labeled: 1
Special conditions of use:
1. OPTIFLUX Primary Head must be used with the IFC 300 F-DIV2, IFC 300 F(li)-DIV2 or IFC 090-F DIV2
signal converters.
2. 1.S. Electrodes when used with IFC 300 F-DIV2, IFC 300 F(li)-DIV2 or IFC 090-F DIV2 signal
converters.
3. *Enclosure Type 6P& IP68 rating only applies when configured with Stainless Steel Connection Box.
3022275
Page 4 of 9
f M Aporovals
W, q
OPTIFLUX 4000-DIV2 VN054abcdefghijklmnop Primary Head.
NI / I /2/ABCD/T6; Type 4X, Type 6, *Type 6P; *IP68
S/ II, III /2 / FG/T6; Type 4X, Type 6, *Type 6P; *IP68
a = Nominal diameter: up to a maximum of 120" at 276 psi
b = Nominal pressure: 1, 2 or A
c=Approval: 5
d = Cable connection: 1, 2, 4, 6, A or C
e= Converter model: C or D
f= Lining: not safety relevant
g = Electrode: 1, 3, 4, 5, 6, 7, G, M, R or U
h = Construction of electrodes: 1
i = Housing/flange material: 1, 3, 4, A, C, D, K, M or N
j = Protection class/dimension: 0 or 2
k= Cable: 2 (Type 6P); Other-Not Safety Relevant
I = Cable length: not safety relevant
m = Calibration: not safety relevant
n = G-P-Ring/mat: not safety relevant
o = Special: 0
p= Module/labeled: 1
Special conditions of use:
1. OPTIFLUX Primary Head must be used with the IFC 300 F-DIV2, IFC 300 F(fl)-DIV2 or IFC 090-F DIV2
signal converters.
2. I.S. Electrodes when used with IFC 300 F-DIV2, IFC 300 F(11)-DIV2 or IFC 090-F DIV2 signal
converters.
3. *Enclosure Type 6P& IP68 rating only applies when configured with Stainless Steel Connection Box.
OPTIFLUX 5000-DIV2 VN984abcdefghijklmn Primary Head.
NI /I /2/ABCD/T6; Type 4X, Type 6, *Type 6P; *IP68
S/ll, III /2/ FG/T6; Type 4X, Type 6, *Type 6P; *IP68
a = Nominal diameter: 1, 2, 3, 5, 6, 8, B, C, E or F
b= Nominal pressure: 3, 4, 5, A or B
c=Approval: 5
d = Cable connection: 1, 2, 4, 6, A or C
e= Converter model: C or D
f= Mounting material: not safety relevant
g = G-Ring mat./gasket mat: not safety relevant
h = Electrode: 0
i = Protection class/dimension: 0 or 2
j = Cable: 2 (Type 6P); Other-Not Safety Relevant
k= Cable length: not safety relevant
I = Calibration: not safety relevant
m = Special: 0
n = Module/labeled: 1
Special conditions of use:
1. OPTIFLUX Primary Head must be used with the IFC 300 F-DIV2, IFC 300 F(h)-DIV2 or IFC 090-F DIV2
signal converters.
2. I.S. Electrodes when used with IFC 300 F-DIV2, IFC 300 F(/i)-DIV2 or IFC 090-F DIV2 signal
converters.
3. *Enclosure Type 6P&IP68 rating only applies when configured with Stainless Steel Connection Box.
3022275
Page 5 of 9
CIM001ouals
OPTIFLUX 5000-DIV2 VN244abcdefghijklmnop Primary Head. (Flange Version)
NI / I /2/ABCD/T6; Type 4X, Type 6, *Type 6P; *IP68
S/ 11,111 /2 / FG/T6; Type 4X, Type 6, *Type 6P; *IP68
a = Nominal diameter: 2, 4, 6, 7, A, B.
b = Nominal pressure: 3, 5 or A.
c=Approval: 5.
d = Cable connection: 1, 2, 4, 6, A or C.
e = Converter model: C or D.
f = Lining: not safety relevant.
g = Electrode: 0.
h = Construction of electrodes: 1.
i = Housing/flange material: 0
j = Protection class/dimension: 0 or 2.
k= Cable: 2 (Type 6P); Other- Not Safety Relevant.
I = Cable length: not safety relevant.
m = Calibration: not safety relevant.
n = G-P-Ring/Material: not safety relevant.
o= Special: 0.
p= Module/labeled: 0 or 1.
Special Conditions of Use:
1. OPTIFLUX Primary Head must be used with the IFC 300 F-DIV2, IFC 300 F(ft)-DIV2 or IFC 090-F DIV2
signal converters.
2. I.S. Electrodes when used with IFC 300 F-DIV2, IFC 300 F(h)-DIV2 or IFC 090-F DIV2 signal
converters
3. *Enclosure Type 6P&IP68 rating only applies when configured with Stainless Steel Connection Box.
OPTIFLUX 6000-DIV2 VN224abcdefghijk/mn Primary Head.
NI / I /2/ABCD/T6; Type 4X, Type 6, *Type 6P; *IP68
S/II, III /2/ FG/T6; Type 4X, Type 6, *Type 6P; *IP68
a= Nominal diameter: 1, 2, 3, 5, 6
b = Connection: 5, 6, A, B, H, K, L, M, N, P, S, T or U
c=Approval: 5
d = Cable connection: 1, 2,4, 6, A or C
e = Converter model: C or D
f= Mounting material: not safety relevant
g = G-Ring mat./gasket mat: not safety relevant
h = Electrodes: 1, 3, 4, 5, 6, 7 or A
i = Protection class/dimension: 0 or 2
j = Cable: 2 (Type 6P);Other-Not Safety Relevant
k= Cable length: not safety relevant
I = Calibration: not safety relevant
m = Special: 0
n = Module/labeled: 1
Special conditions of use.-
1. OPTIFLUX Primary Head must be used with the IFC 300 F-DIV2, IFC 300 F(/i)-DIV2 or IFC 090-F DIV2
signal converters.
2. 1.S. Electrodes when used with IFC 300 F-DIV2, IFC 300 F(Il)-DIV2 or IFC 090-F DIV2 signal
converters.
3. *Enclosure Type 6P&IP68 rating only applies when configured with Stainless Steel Connection Box.
IFC300 a VN304bcdefghijklmno Signal Converter.
XP-ANI / I /2/ABCD/T6 Ta = 65°C-8.30702.61 or 8.30702.62; NIFW*; Type 4X, Type 6
DIP-ANI / 11, III /2 / EFG/Ta = 65°C-8.30702.61 or 8.30702.62; NIFW*;Type 4X, Type 6;
AIS/ I / 1 /ABCDEFG- 8.30702.61 or 8.30702.62; Entity; Type 4X, Type 6,
3022275
Paoe 6 of 9
Curouals
For Entity Parameters and Nonincendive Field Wiring Parameters reference control drawings and,drawing
8.30702.65
" The signal converter is configured with Entity Parameters and Nonincendive Field Wiring Parameters
only when option a = F (/i)-DIV2.
a = Input/Outputs: F (/i)-DIV2 or F-DIV2
b = Type: 4 or H
c = Power Supply: 1, 4 or A
d =Approval 5.
e= Cable connection: 4, or 6
f= instruction/ Program Language: not safety relevant
g = Custody Transfer: 0
h = Process diagnostics: not safety relevant
i = Converter housing: 1 or 2
j = Labeled: 1
k= Communication Slot 101 Selection: 1, 2, 3, 4, 6, 7, 8, B, C,
D, E, F, G or H.
1 = 1 st 10 Module (102/A): 0, 1, 2, 8, A, B, C,E, F, G, H, or K.
m =2nd 10 Module (102 /B): 0, 8, A, B, C, E, F, G, H, or K
n = Reference method: 0 or 1.
o=Tagplate: Not safety relevant
Special Conditions for Use:
1) OPTIFLUX IFC 300 F signal converter electronics must be installed in explosionproof MH300C housing
and used with OPTIFLUX Primary Head.
3022275
Page 7 of 9
CIM 00ravals
OPTIFLUX a300 C—DIV2.Flowmeter.
XP/ I /2/ABCD/T6 Ta =65°C; Type 4X, Type 6
DIP / II, III /2/FG/Ta = 65°C; Type 4X, Type 6
a = Type 1, 2, 4, 5, or 6
The OPTIFLUX a300 series flowmeter is the integration of the OPTIFLUX a000—DIV2 Primary Head and
the model IFC300 F-DIV2 VN304bcdefghijklmno Signal Converter.
OPTIFLUX a300 C/I—DIV2.Flowmeter.
XP-ANI / 1 /2/ABCD/T6 Ta= 65°C—8.30702.61 or 8.30702.62; NIFW; Type 4X, Type 6
DIP-AN[ /II, 111 /2/ FG/Ta = 65°C—8.30702.61 or 8.30702,62; NIFW; Type 4X, Type 6
For Entity Parameters and Nonincendive Field Wiring Parameters reference control drawings and drawing
8.30702.65
a =Type 1, 2, 4, 5, or 6
The OPTIFLUX a300 series flowmeter is the integration of the OPTIFLUX a000—DIV2 Primary Head and
the model IFC 300 F(/i)-DIV2 VN304bcdefghijklmno Signal Converter.
Equipment Ratings:
Explosionproof for use in Class I, Division 2, Groups A, B, C and D; Dust-I g n ition proof for use in Class 11,
III, Division 2, Groups F and G indoor/outdoor hazardous (classified) locations, utilizing Type 4X, 6, or 6P
enclosure with intrinsically safe connections to Class 1, 11, 111, Division 1, Group A, B, C, D, E, F and G
hazardous (classified) locations. Temperature Class T6 Ta =65°C
Explosionproof for use in Class I, Division 2, Groups A, B, C and D; Dust-Ignitionproof for use in Class II,
111, Division 2, Groups F and G indoor/outdoor hazardous(classified) locations, utilizing Type 4X, 6, or 6P
enclosure with nonincendive field wiring connections to Class I, 11, III, Division 2, Group A, B, C, D, F and
G hazardous (classified) locations. The examination was based on the installation of the apparatus being
installed in accordance with control drawings 8,30702.61 or 8,30702.62. Temperature Class T6 Ta =65°C
FM Approved for:
KROHNE Altometer
Kerkeplaat 12,
3313 LC Dordrecht,
the Netherlands
3022275
Page 8 of 9
<:::fM Amouals
11'"'/",.d rho/11 tN "!i
G...
This certifies that the equipment described has been found to comply with the following
Approval Standards and other documents:
Class 3600 1998
Class 3610 1999
Class 3611 2004
Class 3615 1989
Class 3810 1989
Original Project ID: 3022275 Approval Granted: January 3, 2005
Subsequent Revision Reports / Date Approval Amended
Report Number Date Report Number Date
050228 March 11, 2005
050323 March 28, 2005
050715 July 21, 2005
060724 August 25, 2006
060914 November 2, 2006
3026758 February 2, 2007
070209 April 11, 2007
071001 November 13, 2007
080314 March 24, 2008
080808 October 9, 2008
081028 November 20, 2008
090622 August 11, 2009
090824 � e