HomeMy WebLinkAboutR-435491DocuSign Envelope ID: 9D9BODA8-0385-4664-AE66-57BFF1561D7F —, CKET CABLE, #10
AWG. SPLICES BETWEEN FUSE
HOLDER AND LUMINAIRE FIXTURE
SHALL NOT BE ALLOWED
TO LUMINAIRE
FUSE KITS QUICK DISCONNECT 3 AMP TO RECEPTACLE
IN LINE FUSE KITS S.E.C. OR EQUAL,
ONE PER CURRENT CARRYING 120VAC RECEPTACLE WIRING, IF
REFER TO WSDOT LOCKING CONDUCTOR. APPLIES TO LUMINAIRE APPLICABLE. WIRING SIZE PER
LID STANDARD DUTY AND RECEPTACLE WIRING CONTRACT
JUNCTION BOX TYPES 1 & TO LUMINAIRE
2 STANDARD PLAN J-40.10 GROUND LUG GREEN INSULATED WIRE, SIZED
SPLICE KITS CLEAR EPDXY SPLICE TO MATCH THE LARGEST
KITS ON ALL THRU WIRE RUNS CURRENT CARRYING CONDUCTOR.
CONCRETE PAD OR TERMINATE AT LUMINAIRE
SIDEWALK PER STD PLAN 120 GROUND LUG
1� -
,�-
24-(MIN) COVER #8 BARE COPPER UFER GROUND,
GROUND WIRE GROUND II II NON -INSULATED #4 AWG
CLAMP II II STRANDED COPPER,
II PROVIDE 3' MIN. SLACK.
1 -EQUIPMENT GROUND 2" PVC CONDUIT II II ROUTE FROM GROUNDING
WIRE W/GREEN INSULATION � �J LUG TO FOUNDATION
REBAR. CONNECT TO
FROM SERVICE CABINET,
REBAR USING AN ACORN
SEE NOTE 2, THIS SHEET CLAMP
2 - LIGHTING SYSTEM 5/8"x8' COPPER CLAD
GROUND ROD CONCRETE FOUNDATION
WIRES TO CONTACTOR
(SIZED AS REQ'D.)
2 - 120VAC RECEPTACLE SYSTEM
WIRES TO SERVICE CABINET, IF
APPLICABLE (SIZED AS REQ'D.)
NOTES:
1. THIS DETAIL DEPICTS THE BASIC LUMINAIRE ELECTRICAL WIRING SYSTEM. ADDITIONAL ELECTRICAL EQUIPMENT MAY VARY.
2. MINIMUM GROUND WIRE SIZE SHALL BE #8, AS SHOWN ABOVE. IF CURRENT CARRYING CONDUCTORS ARE LARGER THAN
#8, THE MINIMUM GROUND WIRE SIZE SHALL MATCH THE LARGEST WIRE SIZE OF THE CURRENT CARRYING CONDUCTORS.
3. EQUIPMENT GROUND WIRE & BARE WIRE SHALL BE SECURELY FASTENED TO THE GROUND LUG INSIDE THE POLE
HANDHOLE. ALL BONDING & GROUNDING CONNECTIONS SHALL REMAIN ACCESSIBLE FOR INSPECTION AND MAINTENANCE.
4. IF THE FIXTURE MANUFACTURER HAS MADE PROVISIONS FOR THE ATTACHMENT OF A GROUND WIRE, A GREEN INSULATED
WIRE, SIZED TO MATCH THE LARGEST CURRENT CARRYING CONDUCTORS, SHALL BE RUN FROM THE FIXTURE TO THE POLE
GROUND LUG.
5. ALL CONDUIT SHALL BE PVC SCHEDULE 80.
DocuSign Envelope ID: 9D9BODA8-0385-4664-AE66-57BFF1 561 D7F
T-O"
MIN.
LUMINAIRE POLE
\ / Ll -o _
MIN.
JUNCTION BOX
CONCRETE PAD,
PLAN VIEW BROOM FINISH
LUMINAIRE POLE
CONCRETE PAD
1 4•
JUNCTION BOX
LUMINAIRE CONCRETE
FOUNDATION
SIDE VIEW
LUMINAIRE CONCRETE PAD DETAIL
GENERAL NOTES:
1. LUMINAIRE CONCRETE PAD SHALL BE USED IN AREAS
OUTSIDE OF SIDEWALK
2. CONCRETE CLASS FOR LUMINAIRE CONCRETE PAD SHALL
BE PER STD PLAN 135
3. TOP OF LUMINAIRE FOUNDATION ELEVATION SHALL BE
LOCATED AT BOTTOM OF LUMINAIRE CONCRETE PAD
ELEVATION OR BOTTOM OF SIDEWALK ELEVATION
4. LUMINAIRE POLE AND JUNCTION BOX TYPE PER PLAN
5. LUMINAIRE CONCRETE PAD ACCOMMODATES TYPE 1 AND
TYPE 2 JUNCTION BOXES ONLY
LUMINAIRE POLE J JUNCTION BOX
CONCRETE SIDEWALK
PLAN VIEW PER STD PLAN 102
LUMINAIRE POLE
CONCRETE SIDEWALK
PER STD PLAN 102
JUNCTION BOX
LUMINAIRE CONCRETE
FOUNDATION
SIDE VIEW
LUMINAIRE WITH SIDEWALK DETAIL
CONCRETE PAD - V-0"
JUNCTION BOX - PLAN VIEW
a"
i
CONCRETE PAD -
JUNCTION BOX - SIDE VIEW
INDIVIDUAL JUNCTION BOX PAD DETAIL
DocuSign Envelope ID: 9D9BODA8-0385-4664-AE66-57BFF 1561 D7F
INSTALL DECAL NUMBERS/LETTERS VERTICALLY.
DECAL NUMBERSAETTERS, SEE NUMBERING
EXAMPLE, THIS SHEET. SHALL BE INSTALLED IN
DRY WEATHER, 50' F OR ABOVE-,
0
3
4
a
- J
=a
C
cD
5
iQ
6
m
zw
ZDZ
«V�VNG EXAMPLE
J
1-3/4- TO 2"
ROADWAY SCALE DECAL
LUMINAIRE ELECTRICAL t Y LUMINAIRE CONCRETE Y
-� STD. PLAN - 119 �� 0 STD. PLAN - 120 v� 0
PUBLIC WORKS WIRING SYSTEM PUBLIC WORKS PAD/SIDEWALK AND PUBLIC WORKS
. . APPROVED: . . APPROVED: + .
DEPARTMENT MartlaPasma,a 7/27/2022 I 5. p DEPARTMENT JUNCTION BOX CONCRETE PAD Ma-rtinPastucha 7/27/2022 p DEPARTMENT
DATE N 1 O DATE F N S O
+ 0/
z' {
o�v �O
C1 a
n(--
`0
c�
zx
W
m
a
M
w
u
LABEL THE STREET FACING SIDE OF THE CABINET
WITH ADDRESS NUMBER (W/O STREET NAME) USING
AN ENGRAVED PHENOLIC NAMEPLATE WITH 2" HIGH
BLACK LETTERING ON WHITE BACKGROUND. ATTACH
NAMEPLATE WITH ADHESIVE
THE METER DOOR SHALL BE REMOVABLE.
UNLESS SPECIFIED IN THE PLANS, THE
METER DOOR HINGE SHALL BE LOCATED
ON LEFT SIDE OF THE CABINET
METER
BASE
MAIN
CONTROL
LTG.
GROUND
FAULT
RECEPT
WIRING SCHEMATIC
120/24OV. SINGLE PHASE. 3 WIRE
PHOTO
CELL
TEST
SWITCH
ELEVATION
40"
72"
SECTION
0
I
SERVICE 16" 16"
WIREWAY
DEADFRONT
8"
4"f 13"
16«
8
2" TYP.
FOOTPRINT
O NOTES PER STANDARD PLAN 122.2
DocuSign Envelope ID: F09FD439-BD22-4654-ABD3-E56OAA1 F5959
c u�Ilu�r.� I �c nh.uL.l.r.
O
METERBASE: 200 AMP, 4 JAW, MANUAL BYPASS, B-LINE U264
W/ 5"1 JAW AT 9:00 POSITION
O
PANELBOARD: 120/240 VAC, 125 AMP COPPER BUS, 1 PHASE, 3 WIRE, 18 CKT, IOK AIC
MAIN BREAKER: 200 AMP FRAME, 200 AMP TRIP, 2 POLE, EATON ED2200
BOLT -ON BRANCH BREAKERS, EATON TYPE BAB:
2 - 20/2 ILLUMINATION A, B
1 - 20/1 ITS
1 - 20/1 GROUND FAULT RECEPTACLE
1 - 40/1 SIGNAL (IF PRESENT)
I - 40/1 AUXILLIARY SIGNAL (IF PRESENT)
2 - 6012 SMALL CELL BRANCH
1 - 15/1 CONTROL
3 - 20/1 SPARE
3O
CONTACTOR: NEMA LIGHTING RATED, 30 AMP 4 POLE, 120 VAC COIL,
SQD 8910DPA34VO2 -1 RE.QUIRE:D
O
PHOTO ELECTRIC CELL: 1800 WATT, 120 VAC, TWIST LOCK, ALR #SST-IES-UL
MOUNTED INSIDE CABINET BEHIND WIREGLASS WINDOW
SO
PHOTO -CELL BYPASS SWITCH:
SPDT, 15 AMP, RATED (UP TO) 277 VAC (FED THROUGH TERMINAL BLOCK)
6O
GROUND FAULT RECEPTACLE: 20 AMP, 125 VAC, DUPLEX
CABINET:
CONSTRUCTION:
NEMA TYPE 3R, OUTDOOR PADMOUNT, 1/8" 5052-H32 ALUMINUM CONSTRUCTION, OPEN BOTTOM
FRAMED WITH 2" ANGLE, 2 SCREENED AND GASKETED VENTS, REMOVABLE EQUIPMENT
MOUNTING PAN, CABINET GROUND WIT]I MINIMUM BONDING WIRE TO NEUTRAL
DOORS:
IIEAVY-DUTY CONCEALED HINGES (LIFT-OFF TYPE),STAINLESS STEEL VAULT IIANDLES WITH
ROLLER RODS THAT PROVIDE. 3-POINT COMPRESSION ON CLOSED CELL NEOPRENE GASKET,
"BEST"LUCK ON LOWER DISTRIBUTION DOOR WITH CARD HOLDER,
PADLOCKABLE UPPER METER DOOR WITH POLISHED SAFETY GLASS WINDOW
DEADFRONT:
I IINGED AND SECURED WITII QUARTER -TURN FASTENERS
FINISH:
MILL FINISH ALUMINUM
I Rt:OUIRED
UL LISTED PER STANDARD #508A
"SUITABLE FOR USE AS SERVICE ENTRANCE"
NOTE:
1. SIGNAL BREAKER(S) SHALL BE ADDED WHEN APPLICABLE
+ I+ PUBLIC WORKS
, DEPARTMENT
SERVICE CABINET NOTES
PLAN - 122.2
I ar ins astucIJ68/2o2i 14. 3
U
V,
90.
PEDESTRIAN SCALE
CURB DECAL
TRAFFIC
FLOW
DECAL 0111MA71011
FOR POLO lI10M1N ON STD /LAM IILI
i:�
3L_PEDESTRIAN
PEDESTRIAN SCALE
DECAL SCALE 7CURB
CURB DECAL
TRAFFIC TRAFFIC
FLOW FLOW
DECAL ORIENTATION
P01t POLES SHOWN ON WI PLAN 1172
PEDESTRIAN SCALE
ate. DECAL
n5 ROADWAY SCALE
DECAL
TRAFFIC
FLOW
DECAL 011NfA110N
POR POLES 51101111 oN STD PLAN 117.1 S 117.1A
0�
s'
PEDESTRIAN SCALE DECAL
DECAL NOTES:
1. DECALS SHALL BE REFLECTORIZED, GOTHIC FONT. GOLD OR WHITE LEGEND ON
BLACK BACKGROUND
LUMINAIRE STANDARD DECAL STD. PLAN - 121
NUMBERING SYSTEM APPROVED:
7/27/2022 I �:
Martin Paslucha
DATE
R/W LINE
SIDEWALK
CURB
� ROADWAY
CURB '
SIDEWALK
R/W LINE
10' !.!IN. Ot ROADWAY
CLEARANCE FROM DRIVEWAY
ALTERNATE PLAN VIEW
2' TO 4'
OVERHANG
S-6"
�FACE OF
CURB TO
CENTER SL'
CF POLE I
DEWALK
' o %i
PLANTER STRIP
STREET LIGHT CONDUIT
TRENCH DEPTH 24'
TYPICAL STREET LIGHT
FOUNDATION LOCATION
H 1 25' 1 30' 1 35' 44'
SL 1B'-3" 23'-3" J 28'-3"
T 1 0.188 1 0.188 10.219 0.219
2' TO 4'
TAPERED ALUM. POLE 'T' WALL OVERHANG 1'-2"
ALLOY 6C63-T6 SATIN GROUND ANISH
'H'
HANDHOLE 4"x6' OPENING
VI/COVER & S.S. SCREWS
GROUND LUG INSIDE POLE
INSIDE POLE
1 -6"
(LL
O 0 5�1
STREET LIGHT CONDUIT---' t
TRENCH DEPTH 24"
ALTERNATE STREET CROSS SECTION
'SL'
Y STD. PLAN 124
O
n �+ PUBLIC V�ORKS LIGHT BASE AND JUNCTION BOX Nh( VEu:
.. DEPARTMENT LOCATION
6
,TL
T Z111-AL
ARCHITECTURE + PLANNIING + DISIC
6211 ROOSEVELT WAY
NORTHEAST
SEATTLE, WA 98115
tel: (206) 522-3830
fax: (206) 522-2456
F W:B
ENGINEERS= 00
N
Travis Fitzmaurice Wartelle 00
Balangue Engineers Inc. r
1200 Westlake Ave. N., #509 O
Seattle, WA 98109 O^ '
p:206-285-7228 info@tf-wb.coni u,
N
U
00
0
C)
0
C)
1
N
I..L
0Y)
C)
C)
C)
I
N
Q
Z)
PERMIT
RESUBMI TTAL
No. Description Date:
6 City Comments 8/21/25
Project Title:
0
O
L ~
LU
W
W
Q Q
Z
o
z
�
2-7
O
W L
W
w
y
Z
W _ O
LLJ
0-1
5�
TRANSPORTATION OPERATION
cbarnes 09/23/2025
:0:1
Sheet Title:
DETAILS - ELECTRICAL
Scale: As indicated
Project No.: 21-12
Date : 8/21/25
Sheet Number:
EIA
R-435491