HomeMy WebLinkAboutConcrete Field Report_2025-10-10-Lindbergh High School Field Improvements-25B121-01_000007Inspection Information:
Inspection Date:10/10/2025 Time Onsite:09:30 Weather Conditions:
Overcast/Showers 55*F
Inspection Performed: Concrete
Subcontractor:JS Scott Continuous or Periodic:Continuous Inspection
Sheet(s):F270 and E9.01 Location / Area:
SW corner site stairs and field lighting vault slab
Details:1/F270 and 1/E9.01 Level / Elevation:Foundation
Approved Plans Dated:
Report Profile:
Any Deficiencies Noted:Yes No Deficiencies Cleared:Yes No
RFI:Yes No Show Up:Yes No
Retest / Reinspection:Yes No Standby:Yes No
Remarks:
MTC onsite as requested to visually inspect reinforcing steel and concrete placement at the following location(s):
1.) Castinplace concrete for the site stairs in the south west corner of the project site.
2.) Castinplace concrete for the field lighting vault slab
MTC observed that the stairs and slab noted above was reinforced per the following details:
Site stairs per detail 1/F270
Field lighting vault slab per detail 1/E9.01
Reinforcing Steel Inspection: MTC visually inspected the reinforcing steel at the locations noted for compliance with the approved
project plans and specifications. MTC observed the reinforcing steel size, grade, type, and placement. All reinforcing steel was
observed to be ASTM A615 grade 60 reinforcing steel and welded wire mesh reinforcing.
Concrete placement observation: MTC observed the placement of 19+ cubic yards of the projectapproved concrete mix
#1250AFG delivered by Miles Ready Mix for the noted areas above. Concrete was placed via placing boom pump truck and properly
consolidated by screeding. MTC took a composite sample and cast one set of (5) 4x8 cylinders to test for the required 4000 psi
design compression. Reference MTC concrete sample #5228 project set #8 for the compression strength test results. MTC notes
the site stairs required 4000 psi and the field lighting slab required 3000 psi. The contractor used a 5000 psi approved mix design.
✔✔
✔✔
✔✔
Concrete Field Report RCCON00000700Report #:
Burlington
777 Chrysler Drive
Burlington, WA 98233
Phone: (360) 7551990
Client:
Renton School District No. 403
300 SW 7th St
Renton, WA 98057
Project:
25B12101 (Bldg Permit: B25002218)
Lindbergh High School Field Improvements
16426 128th Avenue Southeast
Renton, WA 98059
As a mutual protection to clients, the public and ourselves, all reports are submitted as the confidential property of clients, and
authorization for publication of statements, conclusions or extracts from or regarding our reports is reserved pending our written
approval.
Page 1 of 4Page 1 of 3
Inspection Information:Inspection Date:10/10/2025 Time Onsite:09:30 Weather Conditions:Overcast/Showers 55*FInspection Performed: ConcreteSubcontractor:JS Scott Continuous or Periodic:Continuous InspectionSheet(s):F270 and E9.01 Location / Area:SW corner site stairs and field lighting vault slabDetails:1/F270 and 1/E9.01 Level / Elevation:FoundationApproved Plans Dated:Report Profile:Any Deficiencies Noted:Yes No Deficiencies Cleared:Yes NoRFI:Yes No Show Up:Yes NoRetest / Reinspection:Yes No Standby:Yes NoRemarks:MTC onsite as requested to visually inspect reinforcing steel and concrete placement at the following location(s): 1.) Castinplace concrete for the site stairs in the south west corner of the project site.2.) Castinplace concrete for the field lighting vault slabMTC observed that the stairs and slab noted above was reinforced per the following details: Site stairs per detail 1/F270
Field lighting vault slab per detail 1/E9.01
Reinforcing Steel Inspection: MTC visually inspected the reinforcing steel at the locations noted for compliance with the approved
project plans and specifications. MTC observed the reinforcing steel size, grade, type, and placement. All reinforcing steel was
observed to be ASTM A615 grade 60 reinforcing steel and welded wire mesh reinforcing.
Concrete placement observation: MTC observed the placement of 19+ cubic yards of the projectapproved concrete mix
#1250AFG delivered by Miles Ready Mix for the noted areas above. Concrete was placed via placing boom pump truck and properly
consolidated by screeding. MTC took a composite sample and cast one set of (5) 4x8 cylinders to test for the required 4000 psi
design compression. Reference MTC concrete sample #5228 project set #8 for the compression strength test results. MTC notes
the site stairs required 4000 psi and the field lighting slab required 3000 psi. The contractor used a 5000 psi approved mix design.
To the best of MTC inspector's knowledge, the abovedescribed work was performed in general accordance with project
specifications and approved plans.
Work in progress. Additional inspection needed.
Images:
✔✔✔✔✔✔
✔
Concrete Field Report RCCON00000700Report #:
Burlington
777 Chrysler Drive
Burlington, WA 98233
Phone: (360) 7551990
Client:
Renton School District No. 403
300 SW 7th St
Renton, WA 98057
Project:
25B12101 (Bldg Permit: B25002218)
Lindbergh High School Field Improvements
16426 128th Avenue Southeast
Renton, WA 98059
As a mutual protection to clients, the public and ourselves, all reports are submitted as the confidential property of clients, and
authorization for publication of statements, conclusions or extracts from or regarding our reports is reserved pending our written
approval.
Page 2 of 4Page 2 of 3
Inspection Information:Inspection Date:10/10/2025 Time Onsite:09:30 Weather Conditions:Overcast/Showers 55*FInspection Performed: ConcreteSubcontractor:JS Scott Continuous or Periodic:Continuous InspectionSheet(s):F270 and E9.01 Location / Area:SW corner site stairs and field lighting vault slabDetails:1/F270 and 1/E9.01 Level / Elevation:FoundationApproved Plans Dated:Report Profile:Any Deficiencies Noted:Yes No Deficiencies Cleared:Yes NoRFI:Yes No Show Up:Yes NoRetest / Reinspection:Yes No Standby:Yes NoRemarks:MTC onsite as requested to visually inspect reinforcing steel and concrete placement at the following location(s): 1.) Castinplace concrete for the site stairs in the south west corner of the project site.2.) Castinplace concrete for the field lighting vault slabMTC observed that the stairs and slab noted above was reinforced per the following details: Site stairs per detail 1/F270Field lighting vault slab per detail 1/E9.01 Reinforcing Steel Inspection: MTC visually inspected the reinforcing steel at the locations noted for compliance with the approvedproject plans and specifications. MTC observed the reinforcing steel size, grade, type, and placement. All reinforcing steel wasobserved to be ASTM A615 grade 60 reinforcing steel and welded wire mesh reinforcing. Concrete placement observation: MTC observed the placement of 19+ cubic yards of the projectapproved concrete mix#1250AFG delivered by Miles Ready Mix for the noted areas above. Concrete was placed via placing boom pump truck and properlyconsolidated by screeding. MTC took a composite sample and cast one set of (5) 4x8 cylinders to test for the required 4000 psidesign compression. Reference MTC concrete sample #5228 project set #8 for the compression strength test results. MTC notesthe site stairs required 4000 psi and the field lighting slab required 3000 psi. The contractor used a 5000 psi approved mix design.To the best of MTC inspector's knowledge, the abovedescribed work was performed in general accordance with projectspecifications and approved plans.Work in progress. Additional inspection needed.Images:
Reported By:Mike Currie Reviewed By:Kevin Walters
✔✔✔✔✔✔✔
Concrete Field Report RCCON00000700Report #:
Burlington
777 Chrysler Drive
Burlington, WA 98233
Phone: (360) 7551990
Client:
Renton School District No. 403
300 SW 7th St
Renton, WA 98057
Project:
25B12101 (Bldg Permit: B25002218)
Lindbergh High School Field Improvements
16426 128th Avenue Southeast
Renton, WA 98059
As a mutual protection to clients, the public and ourselves, all reports are submitted as the confidential property of clients, and
authorization for publication of statements, conclusions or extracts from or regarding our reports is reserved pending our written
approval.