Loading...
HomeMy WebLinkAboutWTR2700682 14ATERy1AIN EXT. W-632 I Maolewood Pl . S.E. & S.E. 6th St. - DUPLEX ' BEGINNING OF FILE RUTInx 2oomw l, /afer mot ih mot eo �� Pl. sE S t 14f it K April A. 1962 Mr. Sigi Ullrich SCS holdings P.O. Box 964 Renton, Washington 911055 SUBJECT: Fire Flow Analysis for the Proposed Duplexes at Maplewood Place SE and SE Sixth Street Dear Sigi: This letter summarizes the fire flo. capability of the City Of Renton's rater sysUu to supply the proposed duplexes at Maplewood Place SE and SE Sixth Street. A con"ter analysis simulating a fire at this button was perfonwed for the purpose of deterwinin,g the fire fluty capability of the City's system. The artlysls was bated upon the existing Renton water system with the addition of an 8-Inch water Min ext"Sion on the Maple Valley Highway (SR 169). from SE Fifth Street to Mooroe Avenue $E as shown on the attached figure. Results of this analysis Indicate that the available fire flow it the sitt of the proposed devetopamnt is approximately 1.020 galiont per minute (9pm), at a residual pressure or ?O pounds per square inch (psi) In the ma In adjacent to the property. The fire flow capability for the analysis was based on Insurance Service Officv's (ISO) criteria, which it used by the Washington Survey and Rating Bureau, the local reting umpmy. in accordloKe with ISO criteria, the water system was simulated experiencing a maximum day derand wits, the single largest source of supply, Mall Ma. P, out of service (I.e. , due to failure, maintenance, Ott), A summary of the operational Condltlons used In the analysis is as follow o Minimum service pressure of 30 psi in the service area during normal demands and 20 psi during fire demands. o Walls 1, 2, and S are in operation while Wall B Is Out of service. o Springbroo► Springs Is tuppiying the systemi at 1.300 s m. tag Mark@s StrW.p O Box 1 t60.Kmk4nQ NRaeMngton 9B0J7(2O6f Biz 6a00 MR. Siyi 011rich saw I !, 1962 Page Two 0 Talbot MIT pow station is op.rtting at I Sm go. o me mt. pliwt pum station is "Oretiog at 1,700 "M. o The Windsor Milts puer station is OMreting at 1,9" gpw, o The 'albot MM and Mk. Olivet reservoirs arc bote in operation. R Copy Of the Carputer output has bw retained in this offict for future rafarenee. pleas@ contact a* if you have any C1#esti001% or Ccnae ga nts rerding this analysts. Sincerely, RM2 ENGINEERING, D.S. Richard M, MarWrt RMM:1 re CC: Chief JIM Matthews, Fire Marshal Ron Nelson, 9uilding Dopartwrnt Ron Olsen, Public works h � r• \. r 00 AV W 4 . � t W I ENDING ^� F FIL oe68 2 � atP rma � h FYI* ,p1eo, wowdPLS. E. Pl� x