HomeMy WebLinkAbout101169204 O#914569 ROL-17_UPDATED_APPVD (2).pdfJOB SITE
JOB SITE
13101
P#2473380330
13105
P#2473380340
13109
P#2473380350
13207
P#2473390360
16203
P#2473390370
16219
P#2473390390
16225
P#2473390400
13200
P#2473390460
16117
P#2473380310
13205
P#2473390410
16121
P#2473380320
16209
P#2473390380
SE FAIRWOOD BLVD
OPEN
TRENCH ~ 10'
NEW
B
P
-
2
B
O
R
E
~
7
2
'
B
P
-
1
B
P
-
3
BP-
4
CL
CL
CL
BP-
5
BP-6
OPEN
TRENCH ~
100
B
O
R
E
~
2
5
5
'
B
O
R
E
~
1
2
0
'
BORE ~ 110'
B
O
R
E
~
7
0
'
ROW
=
5
0
'
EOP
'
4
0
'
S
E
1
6
2
N
D
P
L
132
N
D
P
L
S
E
13
1
S
T
P
L
S
E
1
3
2
N
D
P
L
S
E
TREE/BUSH
TRIMMING
REQUIRED
1
A
AØ - 10521 FROM (V03
317024-167072) TO BE
CUT/SPLICED AND
RE-ROUTED TO NEW
J-BOX (J02)
BØ - 10524 FROM (V02
317008-167086) TO BE
CUT/SPLICED AND
RE-ROUTED TO NEW
J-BOX (J02)
W.
O
:
1
0
1
1
6
9
2
0
4
POTELCO - PM, Inc.DESIGNED BY
MAKE NO CHANGES TO THIS JOB WITHOUT PRIOR APPROVAL
Notify Customers and Service Area
48 HRS Prior To Planned Outages
ORDER#NOTIF#PROJECT PHASE
MAINTENENCE
O & M
SUPERIOR
FAILED SILICONE
REMOVAL
EXPENSE
11972548 101169204
-
108151859
-
594158016
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
FOREMAN (CHECK BOX WHEN COMPLETED)
PSE Equipment LOCKED/SECURED & Work Area left in CLEAN/SAFE Condition.
Grid, Cable, and Switch numbers INSTALLED & VERIFIED.
Field Changes RED-LINED on As-built.
Indicate correct FUSE SIZE on As-built & VERIFY proper PHASE.
Foreman's Signature _______________________________________________
Print Name ___________________________________ Date ______________
Material VERIFIED and CHANGES noted on Paperwork.
Total PRIMARY Cable noted on As-built.
Company ID#'s RECORDED in correct location on As-built.
Deviations noted on the As-built and their reason.
I certify that the work performed meets PSE's standards and procedures
and that all quality requirements are met.
No
No
No
Yes
Yes
Yes
"Flagging Required"
"Outages Required"
"Locates Required"
No
No
Yes
Yes
"Joint Trench Coordination Req'd"
"Vegetation Management Req'd"
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
R. MILLER 253-355-6930 5/14/25
L. NEELY 253-569-2523 5/14/25
---
R. MILLER 253-355-6930 5/14/25
RW-133189 RENTON
O#914569 ROL17 CREW2 13203 SE 164
REPLACE CABLES 10521 & 10523, INSTALL NEW J-BOX
16225 132ND PL SE., RENTON, WA 98058
O#914569 -
-101169204
AS NOTED 1 OF 2
KING COUNTY --QCSOKE
NW-27-05-23 --
2305E106 2305E136 2305E106 ROL-17
N/A N/A N/A
N/A N/A N/A
N/A N/A N/A
L. NEELY 253-569-2523 8/14/25
OVERHEAD CIRCUIT MAP: 2305E136
SCALE: 6" = 1 MILE
SITE PLAN
SCALE: 1:50'
VAULT & EQUIPMENT TABLE
SITE GRID
NUMBER VAULT SIZE & COVER TYPE & SIZE
EQUIPMENT IN VAULT
PRIMARY
BUSHINGS TRANSFORMER
ID NUMBERS
(COMPANY ID)
REMARKS
LB DC
J01 316936
167135
EXISTING
JUNCTION BOX
J-BOX BELOW GRADE
W/ 3-4 POS. J-BUS
EXISTING
2 -
J02
NEW
316990
167084
HH 4'-8" X 4'-8" X
3'-6"
W/3' AS DOOR
MATID:7663900
J-BOX BELOW
GRADE
W/ 2-4 POS. J-BUS
MATID: 7625900
5 - INSTALL NEW 4'-8" x 4'-8" x 3'-6" J-BOX
WIRE CREW TO INSTALL GRID NUMBERS
V01 316980
167087
EXISTING
VAULT
37.5kVA PM XFMR
120/240V
EXISTING
--
V02 317008
167086
EXISTING
VAULT
37.5kVA PM XFMR
120/240V
EXISTING
--NOT SHOWN, NORTH OF V01
V03 317024
167072
EXISTING
VAULT
50kVA PM XFMR
120/240V
EXISTING
--NOT SHOWN, NORTH OF V01
TOTALS :7 -
ABANDONED / REMOVE / REPLACED CABLE SCHEDULE
CABLE
NO.
SAP
EQUIP
LOCATIONS CABLE
(LF) EST
EXISTING CABLE
MFG. NAME
EXISTING CABLE
MFG. DATE
ABANDONED
CABLE LEFT IN
PLACE
ABANDON
CIRCUITRYFROMTO
10521 10651964 J01 V01 710 YES NO
10523 10651978 J01 V01 760 YES NO
TOTAL CIRCUIT FEET 1,470'
VICINITY MAP
SITE SPECIFIC NOTES
V01
-INSTALL NEW PRIMARY ELBOW (1) (6041.1000 - ELB10J)
J02 (NEW J-BOX)
-INSTALL NEW J-BOX 15 KV, 5 X 5 X 4 (6055.1010 JBOX1AS), LOCATION MARKED
-INSTALL 2-4 POS J-BUSES (MID: 7625900)
-INSTALL (5) 1/0 ELBOWS (6041.1000 ELB10J)
-INSTALL NEW GRID NUMBER (316990-167084)
J01 - J02 (NEW)
-INSTALL 1-4" CONDUIT 710'± (L_____')
-PULL NEW 2-1Ø PRIMARY CABLES APROX 725'± (L_____')
-INSTALL NEW CABLE TAGS (EJY184 & EJY185)
V01 - J02 (NEW)
-INSTALL 1-2" CONDUIT 10'± (L_____')
-PULL NEW 1Ø PRIMARY JUMPER APROX 15'± (L_____')
-INSTALL CABLE TAG (EJY186)
J01 TO V01
-CUT AND ABANDON IN PLACE CABLE 10521 APROX 710± (L_____')
-CUT AND ABANDON IN PLACE CABLE 10523 APROX 800± (L_____')
V01 - V03 (317024-167072) LOCATED NORTH
-CUT & RE-ROUTE EXISTING CABLE 10521 INTO NEW J-BOX J02
V01 - V02 (317008-167086) LOCATED NORTH
-CUT & RE-ROUTE EXISTING CABLE 10524 INTO NEW J-BOX J02
VOLUME OF DISTURBANCE TABLE
TYPE DESCRIPTION PROPERTY
CLASSIFCATION
SIZE (FT)REM CU YD
(APPX)GRAVEL FILL
CU YD (APPX)
COMMON SURFACE
TYPES
REMARKS
BP-1 BORE PIT ROW 2 X 8 X 3 1.8 1.8 ASPHALT
BP-2 BORE PIT ROW 2 X 8 X 3 1.8 1.8 ASPHALT
BP-3 BORE PIT ROW 2 X 8 X 3 1.8 1.8 ASPHALT
BP-4 BORE PIT ROW 2 X 8 X 3 1.8 1.8 ASPHALT
BP-5 BORE PIT ROW 2 X 8 X 3 1.8 1.8 ASPHALT
BP-6 BORE PIT ROW 2 X 8 X 3 1.8 1.8 ASPHALT
OPEN TRENCH TRENCH PVT PROP 1 X 10 X 3 0.2 0.2 ASPHALT
OPEN TRENCH TRENCH ROW 1 X 100 X 3 0.2 0.2 ASPHALT
1-PH J-BOX VAULT EXC PVT PROP 8X8X4.33 10.3 7.1 GRASS
TOTAL PVT PROP CU YDS (APPX)10.6 7.3
TOTAL ROW CU YDS (APPX)3.8 3.8
TOTAL CU YDS (APPX)14.3 11.1
12'
A - 132ND PL SE, SE 162ND PL & 131ST PL SE (LOOKING NORTH)
NOT TO SCALE
SOUTHBOUND LANE NORTHBOUND LANE
EOPCL
50'ROW
SIDEWALK
12'1'5'
KING COUNTY ROW LEGEND
STREET CENTER LINECL
RIGHT OF WAY
BORE PATH
BORE PIT
BORE PIT"BP"-
PROPERTY LINE
EASEMENT
POT HOLE
OPEN TRENCH
→···→→···→DRAINAGE SLOPE
BUSHESTREE
POT HOLE"PH"-
EOP
ROW
SIDEWALK
1'5'
S
E
1
6
2
N
D
P
L
132
N
D
P
L
S
E
SE FAIRWOOD BLVD
13
1
S
T
P
L
S
E
1
3
2
N
D
P
L
S
E
NEW
21 lbs
33 lbs
NEW 1-2"
EJY186 - BØ
JUMPER
EJY184 - AØ
EJY185 - BØ
NEW 1-4"
2
7
0
l
b
s
2
8
9
l
b
s
AØ - 58378
BØ - 58379
CØ - 58380
EXISTING TO
REMAIN
AØ - 58089
BØ - 58088
EXISTING
TO REMAIN
CØ - 58086
EXISTING TO
REMAIN
AØ - 10521 FROM (V03
317024-167072) TO BE
CUT/SPLICED AND
RE-ROUTED TO NEW
J-BOX (J02)
BØ - 10524 FROM (V02
317008-167086) TO BE
CUT/SPLICED AND
RE-ROUTED TO NEW
J-BOX (J02)
AØ58378
BØ58379
CØ58380
EXISTING TO
REMAIN
CØ - 58086
EXISTING
TO REMAIN
AØ58089
BØ58088
EXISTING TO
REMAIN
AØ - 10521
BØ - 10523
ABANDON IN
PLACE
AØ - 10521 FROM (V03
317024-167072) TO BE
CUT/SPLICED AND
RE-ROUTED TO NEW
J-BOX (J02)
BØ - 10524 FROM (V02
317008-167086) TO BE
CUT/SPLICED AND
RE-ROUTED TO NEW
J-BOX (J02)
JUMPER
EJY186 - BØ
NEW
EJY184 - AØ
EJY185 - BØ
NEW
AØ58089
BØ58088
EXISTING TO
REMAIN
AØ - 58378
BØ - 58379
CØ - 58380
EXISTING TO
REMAIN
CØ - 58086
EXISTING TO
REMAIN
AØ - 10521 FROM (V03
317024-167072) TO BE
CUT/SPLICED AND
RE-ROUTED TO NEW
J-BOX (J02)
BØ - 10524 FROM (V02
317008-167086) TO BE
CUT/SPLICED AND
RE-ROUTED TO NEW
J-BOX (J02)
W.
O
:
1
0
1
1
6
9
2
0
4
POTELCO - PM, Inc.DESIGNED BY
MAKE NO CHANGES TO THIS JOB WITHOUT PRIOR APPROVAL
Notify Customers and Service Area
48 HRS Prior To Planned Outages
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
R. MILLER 253-355-6930 5/14/25
L. NEELY 253-569-2523 5/14/25
---
R. MILLER 253-355-6930 5/14/25
RW-133189 RENTON
O#914569 ROL17 CREW2 13203 SE 164
REPLACE CABLES 10521 & 10523, INSTALL NEW J-BOX
16225 132ND PL SE., RENTON, WA 98058
O#914569 -
-101169204
AS NOTED 2 OF 2
KING COUNTY --QCSOKE
NW-27-05-23 --
2305E106 2305E136 2305E106 ROL-17
N/A N/A N/A
N/A N/A N/A
N/A N/A N/A
L. NEELY 253-569-2523 8/14/25
ONE-LINE CONDUIT DIAGRAM
SCALE: 1:100'
PRIMARY CABLE & CONDUIT TABLE (FOREMAN TO COMPLETE)
LOCATION CONDUIT PRIMARY CABLE QTY OF LUBE
(gal.)REMARKS
FROM TO SIZE
(in)QTY
DESIGN
LENGTH
(ft)
ACTUAL
LENGTH
(ft)
TYPE BENDS PULL
(lbs)
PULL
REV
(lbs)
SIZE
DESIGN
LENGTH
(ft)
ACTUAL
LENGTH
(ft)
CABLE NUMBERS MANUFACTURING INFORMATION For Feeder Cable Only
Check applicable box
DB120 HDPE SCH 80 90 45 22 11 A B C MANUFACTURER COMPOUND YEAR TAPE CN #4/0 NEU DESIGN AS
BUILT
J01 J02 4 1 710 270 289 1/0 AL JKT 725 EJY184 -4.4
J01 J02 ---270 289 1/0 AL JKT 725 EJY185 --
V01 J02 2 1 10 1/0 AL JKT 15 -EJY186 0.1
TOTAL 4"710'TOTAL 1Ø 1,450'4.4
TOTAL 2"10'TOTAL 1Ø 15'TOTAL LUBE 4.5
PRE - UG MAP: #2305E106,109
SCALE: 1:100'
POST - UG MAP: #2305E106,109
SCALE: 1:100'