HomeMy WebLinkAboutM_EQUIPMENT_DATASHEETS_20260121_v1 801 Valley Avenue N.W. Suite D, Puyallup, WA 98371 Phone: (253) 840-9900 | Fax: (800) 591-4382 REDHAHF901QP FIRE ALARM SYSTEM SUBMITTAL SITE ADDRESS: KENWORTH FIRE ALARM SYSTEM 790 GARDEN AVE RENTON WA 98057 PREPARED BY: Red Hawk Fire Protection 801 Valley Avenue NW Suite D Puyallup, WA 98371 RED HAWK FIRE PROTECTION JOB # 90166 SUBMITTAL INCLUDES: SCOPE OF WORK EQUIPMENT DATA SHEETS BATTERY CALCULATIONS CERTIFICATIONS 801 Valley Avenue N.W. Suite D, Puyallup, WA 98371 Phone: (253) 840-9900 | Fax: (800) 591-4382 REDHAHF901QP TABLE OF CONTENTS: TAB 1 ******************** SCOPE OF WORK TAB 2 ******************** FIRE ALARM PANEL TAB 3 ********************* CELL COMMUNICATOR TAB 4 ********************* SMOKE DETECTORS TAB 5 ********************* PULL STATIONS TAB 6 ********************* ADDRESSABLE MODULES TAB 7 ********************* NOTIFICATION DEVICES TAB 8 ********************* BATTERIES TAB9 ********************* BATTERY CALCULATIONS TAB 10 ********************** CERTIFICATIONS 801 Valley Avenue N.W. Suite D, Puyallup, WA 98371 Phone: (253) 840-9900 | Fax: (800) 591-4382 REDHAHF901QP Tab 1 – SCOPE OF WORK 801 Valley Avenue N.W. Suite D, Puyallup, WA 98371 Phone: (253) 840-9900 | Fax: (800) 591-4382 REDHAHF901QP SCOPE OF WORK: The intended scope of this project is to install a new fire alarm system for the North Bay only. The system will monitor the sprinkler system. Fire alarm communications will be via Cell Communicator. The system will be fully functionally tested with the new panel. OCCUPANCY TYPE: F-1 801 Valley Avenue N.W. Suite D, Puyallup, WA 98371 Phone: (253) 840-9900 | Fax: (800) 591-4382 REDHAHF901QP Tab 2 –FIRE ALARM PANEL AFC-50 Fire Alarm Control Panel 8830133 - REV H • 08/24 PAGE 1 OF 5 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com Description The AFC-50 is an analog/addressable fire alarm system with a total system capacity of 50 addresses. Additional capacity on the system is achieved using multi-point SLC modules. The control panel utilizes the exclusive Potter protocol that includes a complete line of sensors and modules. Each SLC may be comprised of any combination of smoke sensor, heat detectors or modules and allows for a total of 50 ohms of impedance and may use any wire compliant with the National Electrical Code (NEC). The AFC-50 has a 5 Amp power supply with two Notification Appliance Circuits (NACs) and two Input/Output (I/O) circuits. The NACs are rated at 3 Amps each and the I/Os are rated at 1 Amp each. Each output is regulated and power limited. In addition, each output is uniquely programmable and may be configured for steady signal, strobe synchronization, constant power, door holder power, or releasing. The strobe synchronization includes Gentex, AMSECO, System Sensor and Cooper/Wheelock and with the exclusive Quadrasync each output may have a unique brand and all strobes will flash together. The NACs may be expanded using the PSN-1000 series intelligent power supplies. Each PSN-1000 adds another 10 Amps of power, 2 additional input circuits and the AFC-50 will support up to 31 power supplies. The system will synchronize the strobes system wide. In addition, the PSN- 1000E has space to allow the installation of up to six expansion cards. The cards mount on a stacker bracket that allows access to all circuit connections. Technical Specifications Dimensions 16”W x 17”H x 3 7/8”D AC Mains 3.0 Amps @ 120 VAC 50/60 HZ2.0 Amps @ 240 VAC 50/60 HZ Enclosure 16 gauge cold rolled steel with removable locked door with Lexan viewing window Battery Standby Current-130 mA Alarm Current-200 mA• 5 Amps power for NACs, I/O, and P-Link • 3 Amps per NAC, regulated • 1 Amp per I/O circuit, regulated• Battery Charger range 8-55 Ah• Battery Charger voltage 27.3 VDC• P-Link maximum current of 1 Amp Temperature and Humidity Range 32° to 120° (0°C to 49°C) with a maximum humidity of 93% non-condensing. Standards • NFPA, 13, 15, 16, 17, 17A, 70, 72, and 750• ANSI/UL 864 - Local (L), Remote Station (RS), Central Station (CS), Propriety (PPU), Auxiliary (AUX), Type of Service: Automatic (A), Manual (M), Water flow (WF), Sprinkler Supervisory (SS), Type of Signaling: Digital Alarm Communicator (DAC), March Time (March), Non Coded (NC), Reverse Polarity (Rev Pol), Other Technologies (OT) • IBC (International Building Code) Features • 50 addresses available on this analog addressable system • Additional system capacity achieved via multi-point SLC modules • 99 software zones • NFPA 72 Compliant Smoke Sensitivity Test Built-In • System Operates as Class A or Class B for SLC, P-Link and NACs • 5 Amp Power Supply, Expandable to 310 amps • 2 NACS, Regulated, Rated at 3 Amps each, expandable to 188 • 2 Input/Output (I/O) Circuits for system flexibility rated at 1 Amp each • Strobe Synchronization and System Wide Sync for Gentex®, AMSECO®, Cooper Wheelock® and System Sensor® strobes • Dedicated Alarm, Supervisory and Trouble Relays • 4,000 Event History Buffer • Optional two line DACT with UD-2000 that can report General, Zone or Point Information • Built in IP Communicator • Ethernet Port for Programming and Network Connectivity • E-Mail System Status, Reports and Event Information • Product includes 5 year warranty. S7357165-0328:0509 NYC Fire Dept. Certificate of Approval 6256 8830133 - REV H • 08/24 PAGE 2 OF 5 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com AFC-50 Fire Alarm Control Panel SLC Loop Accessories SLC Loop Devices The control panel may be connected with up to 50 addressable devices or modules in any combination. The SLC is not restricted by any special wire requirements and may be wired with any wire that complies with the NEC. Device Description PAD Series-PD Analog Photoelectric Smoke Detector is a smoke detector with a listed obscuration of 1.1 to 3.5%/foot. UL 268 7th Edition. PAD Series-PHD Combination Analog Photoelectric Smoke/Heat Detector – a smoke detector with a listed obscuration of 1.1 to 3.5 %/foot obscuration and a fixed temperature range of 135° to 185° F heat detector. Smoke detection compliant with UL 268 7th Edition. PAD Series-PCD Combination Photoelectric Smoke/Carbon Monoxide Detector. Smoke detection compliant with UL 268 7th Edition. Carbon Monoxide detection compliant with UL 2075. PAD200-PCHD Combination Photoelectric Smoke/Heat/Carbon Monoxide Detector. Smoke detection compliant with UL 268 7th Edition. Heat detection with a fixed temperature range of 135° to 185° F and UL 521 7th Edition compliant. Carbon Monoxide detection compliant with UL 2075. PAD Series-HD Analog Fixed Temperature (135° - 185°F) or Rate-of-Rise Heat Detector (software selectable). PAD Series-DUCTR Addressable Duct Smoke Detector with Form C Relay rate at 10Amps @ 250/120VAC or 8 Amps at 30VDC. PAD Series-DUCT Addressable Duct Smoke Detector. PAD100-6DB 6” round base that is mountable to an electrical box and wired for connection to the PAD100/200 devices. PAD100-4DB 4” round base that may be mounted to an electrical box and wired for connection to the PAD100/200 devices. PAD100-IB Isolator base that interrupts a short in a SLC and prevents the short from affecting protected devices on the loop and used for connection to the PAD100/200 devices. PAD100-RB Addressable Relay Base that contains one relay controlled by the SLC. Relay at rated at 2 amps at 30 VDC or 0.5A at 125VAC. For PAD100/200 devices only. PAD100-SB Addressable Sounder Base that contains an addressable sounder module which allows for configuration of local, group, and/ or all call. For PAD100/200 devices only. PAD Series-CD Addressable CO gas detector. PAD200-DD Addressable photoelectric smoke detector for use in DUCT/DUCTR enclosure. PAD300-DD Addressable photoelectric smoke detector for use in DUCT/DUCTR enclosure or pendant mount applications. PAD100-LFSB Addressable Low Frequency Sounder Base that contains an addressable sounder module which allows for configuration of local, group, and/or all call. The LFSB complies with the Low Frequency Signal Requirements (520 Hz) and used for connection to the PAD100/200 devices. PAD100-SPKB Speaker base is a wall or ceiling mount speaker capable of 25 or 70.7 VRMS and is field selectable from 1/8W to 4W and used for connection with the PAD100/200 devices. PAD300-6DB 6” round base which is mountable to an electrical box and wired for connection to the PAD300 devices. PAD300-4DB 4” round base which is mountable to an electrical box and wired for connection to the to the PAD300 devices. PAD300-IB Isolator base that interrupts a short in a SLC and prevents the short from affecting protected devices on the loop. Used for connection to the PAD300 devices. PAD300-RB Addressable Relay Base that contains one relay controlled by the SLC. The Relay is rated 2 amps at 30 VDC or 0.5A at 125VAC and used for connection to the PAD300 devices PAD300-SB Addressable Sounder Base that contains an addressable sounder module which allows for configuration of local, group, and/or all call; and used for connection to the PAD300 devices. PAD300-LFSB Addressable Low Frequency Sounder Base that contains an addressable sounder module which allows for configuration of local, group, and/or all call. The LFSB complies with the Low Frequency Signal Requirements (520 Hz) and used for a connection to the PAD300 devices. 8830133 - REV H • 08/24 PAGE 3 OF 5 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com AFC-50 Fire Alarm Control Panel Modules Device Description PAD100-MIM Micro Input Module provides a small foot print contact module for mounting inside an enclosure. PAD100-PSSA Single Action Addressable Pull Station. PAD100-PSDA Dual Action Addressable Pull Station. PAD100-SIM Single Input Module is a standard contact module with an LED that mounts into a 4” square electrical box. PAD100-DIM Dual Input Module is a device that can monitor two distinct inputs with a single device or in a Class A mode. PAD100-TRTI Two Relay Two Input module provides two form C relays that are individually controlled by the control panel. Each relay is rated for 2 amps at 30VDC or 0.5 amps at 125VAC. Also provides two contact inputs. PAD100-NAC Notification Appliance Circuit module is an addressable remote appliance circuit controlled by the panel. PAD100-ZM Zone Module is used to connect conventional 2-wire smoke detectors to the system. PAD100-IM Isolater Module interrupts a short on the SLC and prevents the short from affecting protected devices on the loop. PAD100-RM Relay Module that provides one form C relay controlled by the control panel. Relay is rated for 2 amps at 30VDC or 0.5 amps at 125VAC. PAD100-LED Module provides a single addressable LED that is controlled by the control panel. PAD100-SM Speaker Module provides switching for two audio channels. PAD100-LEDK Addressable LED and key switch that mounts in a single gang box. PAD100-DRTS DUCTR Remote Test Switch that mounts in a single gang box and optionally supervised. For use with the PAD100-DUCTR only. PAD100-OROI One Relay One Input Module provides one form C relay and one input. The relay is rated at 2 amps at 30VDC or 0.5 amps at 125VAC. 8830133 - REV H • 08/24 PAGE 4 OF 5 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com AFC-50 Fire Alarm Control Panel SLC Features Sensor Features User Interface Ethernet/I.P. Connection P-Link The Potter protocol is a digital protocol with a proven design for reliability and noise immunity. The system does not require special cable or conductors for connection of the Signaling Line Circuit as long as the cable is compliant with NFPA 70 and NFPA 72. The system allows for Class A or Class B installations as well as “T-Taps”, with a max wiring distance of 10,000 Ft. The sensors through the fire alarm control panel provide a real time status as to the condition of the system. The smoke detector sensitivity, heat detector temperature level and drift compensation are all programmable options. The system also allows for a day/night mode where the panel automatically adjusts the sensitivity depending on the time of day. To assist in the reduction of false alarms, the smoke detectors also have a maintenance warning that sends a trouble signal when a detector is dirty to the point that it can no longer maintain the programmed sensitivity. The AFC-50 is shipped standard with an Ethernet connection. This connection is the programming port and may be connected to a building Wide Area Network (WAN) or Local Area Network (LAN). Once connected to the Internet, the panel may be selectively programmed to e-mail alarm conditions, trouble conditions, supervisory conditions, test, Event History and detector status. An e-mail may be sent to the panel and the panel will e-mail the event history, detector status, configuration file or server status to an authorized E-mail account. In addition, reminders may be set to send an e-mail for service, testing or other conditions. In addition, the Ethernet connection is UL listed as an IP communicator. The IP communicator is listed to report to the UL listed Sur-Gard III IP receiver. The IP communicator replaces the traditional less reliable alarm communicator transmitter that utilized telephone lines. The IP communicator is an active method of connection and communication to the monitoring station. The AFC-50 has a proprietary communication protocol that communicates through a RS-485 connection to field devices. Up to 32 devices may be connected to a single P-Link connection. The P-Link includes the communication terminals and regulated 24 VDC connection for the field devices. The field devices may be any of the following: PAD100-SLCE-Analog/Addressable loop expansion module RA-6075R – 2 x 16 LCD annunciator with a key pad in a locked metal enclosure. The fire alarm control panel has a 4 x 20 LCD display to provide information to the system status. The keypad has navigation keys to allow manipulation of the Menu on board the panel. The panel is shipped standard with the following LEDs: • AC Power - Green • Alarm - Red • Earth Fault - Amber • Supervisory - Amber • Silenced - Amber • Trouble - Amber • Pre-Release - Amber • Release - Red The common buttons include a Silence, Reset, Acknowledge, and Drill. All of the buttons are accessible once the locked door is opened. RA-6500R(F) – 4 x 40 LCD annunciator with a key pad in a locked metal enclosure. Flush mount version available. LED-16(F) – 16 LED annunciator with common indicators in a locked metal enclosure. Flush mount version available. PSN-1000(E) – 10 amp, remote intelligent power supply with 6 NACs, 2 Inputs and a P-Link repeater. This panel is listed in conjunction with the AFC-50 as releasing circuits. CA-6075 – Class A convertor that converts the SLC, NACs and P-Link connection UD-2000 – UL listed, Dual line telephone alarm communicator DRV-50 – LED driver expander, used to connect up to 50 LEDs in a graphic display FCB-1000 – Fire communication bridge, provides remote mounting of the Ethernet connection FIB-1000 – Fiber interface module, used to extend P-Link to multi- mode fiber (2 required) RLY-5 – Relay module, provides 5 form C relay contacts rated at 3.0 amps 24VDC/125AC SPG-1000 – Serial parallel gateway, allows for the connection to a serial or parallel printer The FIB-1000, FCB-1000 and the SPG-1000 may be installed in the stacker bracket or ordered with the optional rack mount enclosure. MC-1000 Multi-Connect allows up to sixty-three AFC series panels to share a single reporting technology. IDC-6 – Initiating device circuit provides 6 programmable inputs AE-2 – Two card expansion cabinet AE-8 – Eight card expansion cabinet AE-14 – Fourteen card expansion cabinet 8830133 - REV H • 08/24 PAGE 5 OF 5 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com AFC-50 Fire Alarm Control Panel Dimensions Model Description Stock No. AFC-50 Fire Alarm Control Panel 3992752 Replacement Board AFC-50 3992756 Ordering Information DO O R = 16 . 7 8 " BA C K B O X = 1 6 . 5 6 " DOOR = 16.07"BACKBOX = 15.77" 3.75"DEPTH = DEPTH = 3.84" TOP LEFT SIDE RIGHT SIDE BOTTOM DWG #593-1 801 Valley Avenue N.W. Suite D, Puyallup, WA 98371 Phone: (253) 840-9900 | Fax: (800) 591-4382 REDHAHF901QP Tab 3- CELL COMMUNICATOR DUAL PATH 800.229.2326 | 3225 Cumberland Blvd SE • Suite 300 • Atlanta, GA 30339 • USA | telguard.com ©2021 Telguard | Telguard and the Telguard Logo are registered trademarks of Telular Corporation. | Telular is a business unit of AMETEK, Inc. All Rights Reserved. 102021RevD COMMERCIAL FIRE Part of the full line of Telguard universal fire communicators, the TG-7FE offers two pathways to reliably transmit signals: a wired LAN connection to the Internet and 5G LTE-M cellular. It operates on panel power or via plug-in transformer. The world is changing. Copper POTS lines are disappearing, and calls are delivered over the Internet. This is a perfect example of where the TG-7FE steps in. Eliminate all Telco lines and run an Ethernet cable from the TG-7FE to the premises LAN for alarm signal delivery. And, to be sure signals get through to the central station you choose, the TG-7FE instantly falls over to reliable cellular service any time it’s needed. Telguard puts nearly four decades of alarm communications expertise into every UL Listed communicator. You stay in control, with highly configurable options that meet your needs and the requirements of your AHJ. For the most current product specifications and UL Listings visit telguard.com/tg-7fe. In Canada, cellular data may be carried by Rogers, Bell, Telus or SaskTel. CHOOSE THE COMMUNICATOR THAT BEST FITS THE NEEDS OF YOUR UPGRADE, TAKEOVER, OR NEW INSTALL PROJECT. PRODUCT FEATURES Dual communication paths - If the Internet connection is interrupted or the LAN goes down, always-on 5G cellular will immediately step in. Powers directly from the fire panel’s 12V/24V auxiliary power supply or via plug-in transformer (included). Uses LTE-M bands for 4G and 5G network compatibility, better in-building penetration, and longest product life. Interfaces with panel over a single DACT connection for universal compatibility (use TG-PEM accessory when panel has no DACT). Telguard communicators are compatible with more alarm formats than any other brand. The signal will reliably get to the central station. Specifications Power Consumption Standby: 18mA @ 24VDC 40mA @ 12VDC Transmit: 110mA @ 24VDC 200mA @ 12VDC Compatible Formats CID, SIA, Pulse (4x2, 3x1), Radionics (IIe/3a2,4), DMP Antenna: 50Ω TNC connector (female) Size (without antenna) 7.5 H x 11.5 W x 3.5 D in (19.05 x 29.21 x 8.89 cm) Available Accessories • High gain and directional antennas • Varying lengths of antenna cables • TG-PEM Power & Expansion Module UL Listings (AT&T and Verizon) • 864 Commercial Fire • 1610 Central Station ULC Listings (AT&T Only) • S559 Commercial Fire • S304 Commercial Burglary Certifications • California State Fire Marshal • FDNY approval pending 801 Valley Avenue N.W. Suite D, Puyallup, WA 98371 Phone: (253) 840-9900 | Fax: (800) 591-4382 REDHAHF901QP Tab 4- SMOKE DETECTORS PAD200-PD Photoelectric Smoke Sensor 8830172 - REV A • 5/21 PAGE 1 OF 2 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com Description The Photoelectric Smoke Sensor is a listed Analog Addressable smoke sensor compatible with fire alarm control panels that utilize the Potter Addressable Device (PAD) protocol. The PAD200-PD is a low profile smoke sensor with a wide sensitivity range. The sensor and base (not included) are made of a durable plastic in an off-white color to blend in with the ceiling. The PAD200-PD has a sensitivity range of 1.0 to 3.7 % per foot and is UL. The PAD200-PD features drift compensation and has built in dirty detector warning as well as. The PAD200-PD and the control panel communicate over a proven and robust digital communication path and the system analyzes the information at the particular device. The total polling speed is less than five (5) seconds, well under the UL requirements. The sensor is compatible with any of the PAD series sensor bases and simply twists on. The PAD200-PD is addressed using DIP switches in the rear of the sensor and can be easily programmed in the field without special tools. Setting the Address Each addressable device on the SLC loop must have a unique address from 1 to 127 to function properly. The address is set using DIP switches. Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to SLC or device. Verify the following: 1. Power to the device is removed 2. Field wiring is correctly installed. 3. Field wiring has no open or short circuits. Technical Specifications Operating Voltage 24 VDC Detector Current Draw 300 µA Alarm indicator 1 LED Alarm set-point range 1.0 to 3.7 %/ft 3.6-12 %/m Installation temperature range 32 to 120 ° F / 0 to 49 ° C Operating relative humidity range 0% to 93% (Non-condensing) Start-up time Max. 1 sec. Maximum number of addresses per loop 127 Maximum number of lighted indicators in alarm per loop.30 Color Eggshell White Weight (without base)101g (3.56oz) Dimensions (without base) Height: 1.35 in (34mm) Diameter: 3.93 in (100 mm) Features • UL 268 7th Edition • Low profile, less than 2 inches with the base • Wide selectable sensitivity range of 1.0 to 3.7%/foot • Sensor communicates sensitivity to control panel • UL listed smoke calibration and sensitivity • Optional locking tab to prevent unwanted removal • Simple DIP switch address setting, no programming tool required • LED alarm indicator • Product includes a 5 year warranty • UUKL Listed for Smoke Control 8830172 - REV A • 5/21 PAGE 2 OF 2 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com PAD200-PD Photoelectric Smoke Sensor Air Velocity Ratings Operation Sensor Sensitivity Spacing Compatible Bases Model Description Stock No. PAD200-PD Photoelectric Smoke Sensor 3992770 Ordering Information The PAD200-PD has an Open Area of Protection air velocity rating of 0 to 300 feet per minute. The system has a maximum of 30 LEDs that can be turned on simultaneously. If the system already has 30 LEDs on, the PAD200-PD will operate even though the LED may not illuminate. The PAD200-PD is an analog addressable sensor that uses one address on the Signaling Line Circuit (SLC) of a compatible fire alarm control panel. The unit communicates with the control panel as it is polled. The LEDs flash every time the unit is polled and they will flash at a fast rate if the unit is in an active status. The polling LED can be turned off if desired for less conspicuous operation. The PAD200-PD with the PAD100-4DB or PAD100-6DB has a low profile of less than two (2) inches to blend into the surrounding environment. The sensor includes an insect screen to prevent foreign objects from reaching the chamber and the can be cleaned to restore operation of a dirty detector. The PAD200-PD and the compatible control panel work in tandem to keep the sensitivity consistent. As the sensor is installed over time, the sensor compensates for the dirt in the unit until it is out of range. At that time, the panel will indicate a dirty sensor. The sensor will then have to be cleaned or replaced. The PAD200-PD can be programmed to provide a maintenance alert prior to reaching the dirty sensor level which will allow for intervention prior to the sensor going into trouble. This allows for sensor replacement or cleaning prior to a nuisance trouble occurs. NOTE: As required by NFPA, do not install the sensors until all construction is complete and the work area has been thoroughly cleaned. If the sensors have been installed in a construction environment, they should be cleaned or replaced before the system is placed into service. The PAD200-PD is UL listed with a recommended maximum spacing of 30 feet. Refer to NFPA 72 for specific information regarding detector spacing, placement and special applications. All bases will mount on a single gang, double gang, octagon, 4” square or mud ring electrical box. Device Description Stock No. PAD100-4DB 4” Standard Base 3992731 PAD100-6DB 6” Standard Base 3992732 PAD100-IB 6” base with an isolator module included. 3992730 PAD100-RB 6” base with one Form-C relay contact. 2A @ 30VDC, 0.5A @ 125VAC 3992728 PAD100-SB 6" base with sounder module included. Sound pattern is provided from external source. 3992729 PAD100-SPKB 6” base with speaker included 3992762 801 Valley Avenue N.W. Suite D, Puyallup, WA 98371 Phone: (253) 840-9900 | Fax: (800) 591-4382 REDHAHF901QP Tab 5- PULL STATIONS PAD100-PSSA/PSDA Addressable Pull StationSingle/Dual Action 8830097 - REV D • 12/18 page 1 OF 2 potter electric Signal Company, LLC • St. Louis, MO • phone: 800-325-3936 • www.pottersignal.com Description The paD100-pSSa (Single action) is activated by simply pulling the white “T” bar handle down. The paD100-pSDa (Dual action) is activated by lifting the front cover and then pulling the white “T” bar handle down. Once activated, the “T” bar cannot be reset without opening the front cover. Opening the front cover will also activate the pull station. To reset the paD100-pS Series, use the potter WS-93 key to unlock and open the front cover. Once the cover is open, push the “T” bar back into the normal position and re-secure the front cover. Application The paD100-pSSa/pSDa is compatible with potter’s Ipa and aFC/ $5& VHULHV DGGUHVVDEOH ¿UH DODUP FRQWURO SDQHOV ,W LV D QRQFRGHG addressable pull station available in either a single or dual action model and installs on a single gang box or surface mounts using the p32-BB or p32-DBB (deep) back box. Technical Specifications Operating Voltage 24.0 VDC Max SLC Standby Current 200ua Max SLC alarm Current 200ua environmental Limitations 32°F - 120°F (0° - 49°C) Indoor Only Dimensions 4.75” H x 3.25” W x 1.75” D Relative Humidity Range 0 - 93% (non-condensing) Mounting Options Single gang box or potter p32-BB/DBB Shipping Weight apS-Sa - 1.22 lbs. apS-Da - 1.46 lbs. Features • Single or Dual action versions • Durable die-cast construction • 5HVHW NH\ PDWFKHV WKH ¿UH DODUP FRQWURO SDQHOV • Compatible with Ipa Series panels • SLC Class a, Class X & Class B • product includes a 5 year warranty • UUKL Listed for Smoke Control 8830097 - REV D • 12/18 page 2 OF 2 potter electric Signal Company, LLC • St. Louis, MO • phone: 800-325-3936 • www.pottersignal.com PAD100-PSSA/PSDA Addressable Pull StationSingle/Dual Action The paD100-pS Series uses one SLC address assigned to the device. The address is set using the DIp switch located on the back of the paD100-pS device. Setting the Address Fig 1 Fig 2 Model Description Stock No. paD100-pSSa addressable pull Station, Single action 3992721 paD100-pSDa addressable pull Station, Dual action 3992720 Ordering Information P POTTER P POTTER Pull Station Front View Pull Station Back View and Wiring paD100-pSDa paD100-pSSa FACTORY WIRED CONTACTS FROM FACP OR PREVIOUS DEVICETO NEXT DEVICE 801 Valley Avenue N.W. Suite D, Puyallup, WA 98371 Phone: (253) 840-9900 | Fax: (800) 591-4382 REDHAHF901QP Tab 6- ADDRESSABLE MODULES PAD100-SIM Single Input Module 8830083 - REV D • 12/18 page 1 OF 2 potter electric Signal Company, LLC • St. Louis, MO • phone: 800-325-3936 • www.pottersignal.com Description The paD100-SIM uses one (1) SLC loop addresses when monitoring one (1) Class B circuit. The module mounts on either a 4” square or double gang box. The module is capable of monitoring one (1) Class B circuit. The paD100-SIM includes one red LeD to indicate the PRGXOH¶V VWDWXV ,Q QRUPDO FRQGLWLRQ WKH /(' ÀDVKHV ZKHQ WKH GHYLFH LV EHLQJ SROOHG E\ WKH FRQWURO SDQHO :KHQ WKH LQSXW LV DFWLYDWHG WKH /(' ZLOO ÀDVK DW D IDVW UDWH Application The paD100-SIM is compatible with potter’s Ipa and aFC/aRC VHULHV DGGUHVVDEOH ¿UH DODUP FRQWURO SDQHOV 7KH 3$'6,0 LV DQ LQWHUIDFH PRGXOH XVHG WR PRQLWRU GU\ FRQWDFW GHYLFHV VXFK DV VSULQNOHU ZDWHUÀRZ YDOYH WDPSHU VZLWFKHV RU FRQYHQWLRQDO SXOO VWDWLRQV 7KH module is capable of monitoring one Class B circuit. Setting the Address (DFK DGGUHVVDEOH 6/& GHYLFH PXVW EH DVVLJQHG DQ DGGUHVV 7KH DGGUHVV is set using the DIp switch located on the paD100-SIM. %HIRUH FRQQHFWLQJ D GHYLFH WR WKH 6/& ORRS WDNH WKH IROORZLQJ SUHFDXWLRQV WR SUHYHQW SRWHQWLDO GDPDJH WR WKH SDQHO RU GHYLFH 1. 3RZHU WR WKH GHYLFH LV UHPRYHG 2. Field wiring is correctly installed. 3. Field wiring has no open or short circuits. Technical Specifications Operating Voltage 24.0V Max SLC Standby Current ȝ$ Max SLC alarm Current ȝ$ Max Wiring Resistance of IDC  ȍ Max Wiring Capacitance of IDC ȝ) eOL Resistor . ȍ Operating Temperature Range 32 to 120ºF (0 to 49ºC) Operating Humidity Range 0 to 93% (non-condensing) Max no. of Module per Loop 127 units Dimensions 4.17” (106mm)L × 4.17” (106mm)W × 1.14” (29mm)D Mounting Options Standard 4” Square or Double gang Box Shipping Weight 0.6 lbs Features • One (1) Class B monitoring input • SLC Class a, Class X & Class B • Mounts in a standard 4” or double gang box • Wiring terminals accessible when mounted in box • all wiring terminals accept 22 to 12 aWg • product includes a 5 year warranty • 88./ /LVWHG IRU 6PRNH &RQWURO NOTE: 7KLV DGGUHVVDEOH PRGXOH GRHV QRW VXSSRUW ZLUH VPRNH detectors. 8830083 - REV D • 12/18 page 2 OF 2 potter electric Signal Company, LLC • St. Louis, MO • phone: 800-325-3936 • www.pottersignal.com PAD100-SIM Single Input Module Installation Using Compatible Electrical Box Wiring Diagram PAD100-SIM With Class B Circuit Fig 1 Model Description Stock No. paD100-SIM Single Input Module 3992704 Ordering Information Fig 2 FROM FACP OR PREVIOUS MODULE TO NEXT MODULE END-OF-LINE RESISTOR 5.1K OHM Part #3005013 12 W 801 Valley Avenue N.W. Suite D, Puyallup, WA 98371 Phone: (253) 840-9900 | Fax: (800) 591-4382 REDHAHF901QP Tab 7- NOTIFICATION DEVICES Agency Listings 7125-1653:0504 7135-1653:0503 S5512 S4011 FM approved except for ALERT models 3057383, 3057072 AVDS865-05 • 2/22/2018 • Page 1 Features • Updated Modern Aesthetics • Small profile devices for Horns and Horn Strobes • Plug-in design with minimal intrusion into the back box • Tamper-resistant construction • Automatic selection of 12- or 24-volt operation at 15 and 30 candela • Field-selectable candela settings on wall units: 15, 30, 75, 95, 110, 135, and 185 • Horn rated at 88+ dBA at 16 volts • Rotary switch for horn tone and two volume selections • Mounting plate for all standard and all compact wall units • Mounting plate shorting spring checks wiring continuity before device installation • Electrically compatible with legacy SpectrAlert and SpectrAlert Advance devices • Compatible with MDL3 sync module • Strobes and Horn Strobes listed for wall mounting only • Horns listed for wall or ceiling use The System Sensor L-Series offers the most versatile and easy-to-use line of horns, strobes, and horn strobes in the industry with lower current draws and modern aesthetics. With white and red plastic housings, standard and compact devices, and plain, FIRE, and FUEGO-printed devices, System Sensor L-Series can meet virtually any application requirement. The L-Series line of wall-mount horns, strobes, and horn strobes include a variety of features that increase their application versatility while simplifying installation. All devices feature plug-in designs with minimal intrusion into the back box, making installations fast and foolproof while virtually eliminating costly and time-consuming ground faults. To further simplify installation and protect devices from construction damage, the L-Series utilizes a universal mounting plate for all models with an onboard shorting spring, so installers can test wiring continuity before the device is installed. Installers can also easily adapt devices to a suit a wide range of application requirements using field-selectable candela settings, automatic selection of 12- or 24-volt operation, and a rotary switch for horn tones with two volume selections. Indoor Selectable- Output Horns, Strobes, and Horn Strobes for Wall Applications System Sensor L-Series audible visible notification products are rich with features guaranteed to cut installation times and maximize profits with lower current draw and modern aesthetics. AVDS865-05 • 2/22/2018 • Page 2 L-Series Specifications Architect/Engineer Specifications General L-Series standard horns, strobes, and horn strobes shall mount to a standard 2 x 4 x 17/8-inch back box, 4 × 4 × 1½-inch back box, 4-inch octagon back box, or double-gang back box. L-Series compact products shall mount to a single-gang 2 × 4 × 17⁄8-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products for all standard models and a separate universal mounting plate shall be used for mounting wall compact models. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L-Series products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 30, 75, 95, 110, 135, and 185. Strobe The strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize Strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 411/16 × 411/16 × 21/8-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC or regulated 24 DC/FWR1 Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage Range MDL3 Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions (including lens)5.6˝ L × 4.7˝ W × 1.91˝ D (143 mm L × 119 mm W × 49 mm D) Compact Wall-Mount Dimensions (including lens)5.26” L x 3.46” W x 1.91” D (133 mm L x 88 mm W x 49 mm D) Horn Dimensions 5.6˝ L × 4.7˝ W × 1.25˝ D (143 mm L × 119 mm W × 32 mm D) Compact Horn Dimensions 5.25” L x 3.45” W x 1.25” D (133 mm L x 88 mm W x 32 mm D) 1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. 2. Strobe products will operate at 12 V nominal only for 15 cd and 30 cd. AVDS865-05 • 2/22/2018 • Page 3 Horn and Horn Strobe Output (dBA) Switch Position Sound Pattern dB 8–17.5 Volts 16–33 Volts DC DC FWR 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non-Temporal High 85 90 90 4 Non-Temporal Low 76 84 84 5 3.1 KHz Temporal High 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non-Temporal High 84 89 89 8 3.1 KHz Non-Temporal Low 77 83 83 9*Coded High 85 90 90 10*3.1 KHz Coded High 84 89 89 * Settings 9 and 10 are not available on 2-wire horn strobes. Temporal coding must be provided by the NAC. If the NAC voltage is held constant, the horn output remains constantly on. UL Max. Strobe Current Draw (mA RMS) Candela 8–17.5 Volts 16–33 Volts DC DC FWR Candela Range 15 88 43 60 30 143 63 83 75 N/A 107 136 95 N/A 121 155 110 N/A 148 179 135 N/A 172 209 185 N/A 222 257 UL Max. Current Draw (mA RMS), Wall Horn Strobe, Candela Range (15–185 cd) DC Input 8–17.5 Volts 16–33 Volts 15cd 30cd 15cd 30cd 75cd 95cd 110cd 135cd 185cd Temporal High 98 158 54 74 121 142 162 196 245 Temporal Low 93 154 44 65 111 133 157 184 235 Non-Temporal High 106 166 73 94 139 160 182 211 262 Non-Temportal Low 93 156 51 71 119 139 162 190 239 3.1K Temporal High 93 156 53 73 119 140 164 190 242 3.1K Temporal Low 91 154 45 66 112 133 160 185 235 3.1K Non-Temporal High 99 162 69 90 135 157 175 208 261 3.1K Non-Temporal Low 93 156 52 72 119 138 162 192 242 FWR Input 16–33 Volts 15cd 30cd 75cd 95cd 110cd 135cd 185cd Temporal High 83 107 156 177 198 234 287 Temporal Low 68 91 145 165 185 223 271 Non-Temporal High 111 135 185 207 230 264 316 Non-Temportal Low 79 104 157 175 197 235 283 3.1K Temporal High 81 105 155 177 196 234 284 3.1K Temporal Low 68 90 145 166 186 222 276 3.1K Non-Temporal High 104 131 177 204 230 264 326 3.1K Non-Temporal Low 77 102 156 177 199 234 291 UL Max. Horn Current Draw (mA RMS) Sound Pattern dB 8–17.5 Volts 16–33 Volts DC DC FWR Temporal High 39 44 54 Temporal Low 28 32 54 Non-Temporal High 43 47 54 Non-Temporal Low 29 32 54 3.1 KHz Temporal High 39 41 54 3.1 KHz Temporal Low 29 32 54 3.1 KHz Non-Temporal High 42 43 54 3.1 KHz Non-Temporal Low 28 29 54 Coded High 43 47 54 3.1 KHz Coded High 42 43 54 UL Current Draw Data Horn Tones and Sound Output Data 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 www.systemsensor.com ©2018 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. AVDS865-05 • 2/22/2018 L-Series Dimensions Model Description Wall Horn Strobes P2RL 2-Wire, Horn Strobe, Red P2WL 2-Wire, Horn Strobe, White P2GRL 2-Wire, Compact Horn Strobe, Red P2GWL 2-Wire, Comp 2 fils act Horn Strobe, White P2RL-P 2-Wire, Horn Strobe, Red, Plain P2WL-P 2-Wire, Horn Strobe, White, Plain P2RL-SP 2-Wire, Horn Strobe, Red, FUEGO P2WL-SP 2-Wire, Horn Strobe, White, FUEGO P4RL 4-Wire, Horn Strobe, Red P4WL 4-Wire, Horn Strobe, White Wall Strobes SRL Strobe, Red SWL Strobe, White SGRL Compact Strobe, Red SGWL Compact Strobe, White SRL-P Strobe, Red, Plain SWL-P Strobe, White, Plain SRL-SP Strobe, Red, FUEGO SWL-CLR-ALERT Strobe, White, ALERT L-Series Ordering Information Notes: All -P models have a plain housing (no “FIRE” marking on cover). All -SP models have “FUEGO” marking on cover. All -ALERT models have “ALERT” marking on cover. *Horn-only models are listed for wall or ceiling use. Model Description Horns* HRL*Horn, Red HWL*Horn, White HGRL*Compact Horn, Red HGWL*Compact Horn, White Accessories TR-2 Universal Wall Trim Ring Red TR-2W Universal Wall Trim Ring White SBBRL Wall Surface Mount Back Box, Red SBBWL Wall Surface Mount Back Box, White SBBGRL Compact Wall Surface Mount Back Box, Red SBBGWL Compact Wall Surface Mount Back Box, White 4.70" (11.94 cm)1.91" (4.85 cm) 1.25" (3.18 mm) 5.67" (14.4 cm) A0549-00A0550-00 Compact Strobe, Horn Strobe Compact Horn Strobe, Horn Strobe Horn A0548-00 A0547-00 4.7"119 mm 5.67" 144 mm 1.25" 32 mm 3.46"88 mm 1.91"48.5 mm 1.25"32 mm 5.27"133.9 mm 3.46"88 mm 1.25"32 mm 5.27"133.9 mm Wall Surface Mount Back Box SBBRL/SBBWL A0554-01 4.82" (12.24 cm)1.85" (4.69 cm) 5.78" (14.68 cm) A0557-00 1.55" (3.9 cm)3.57" (9.1 cm) 5.38" (13.7 cm) Compact Wall Surface Mount Back Box SBBGRL, SBBGWL Agency Listings AVDS115-02 • 12/3/2019 • Page 1 MEA452-05-E3023572 7300-1653:187 (outdoor strobes) 7125-1653:188 (horn strobes, chime strobes) 7135-1653:189 (horns, chimes) S4011 (chimes, horn strobes, horns) S3593 (outdoor and alert strobes) Features • Weatherproof per NEMA 4X, IP56 • Listed to UL 1638 (strobe) and UL 464 (horn) • Compatible with System Sensor synchronization protocol and legacy SpectrAlert products • Field-selectable candela settings: 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185 • Automatic selection of 12- or 24-volt operation at 15 and 15/75 candela • Rotary switch for horn tone and three volume selections • Horn rated at 88+ dBA at 16 volts • Rated from –40°F to 151°F • Universal mounting plate with an onboard shorting spring that tests wiring continuity before devices are installed • Plug-in design with minimal intrusion into the back box • Tamper-resistant construction • Listed for ceiling or wall mounting SpectrAlert Advance offers the broadest line of outdoor horns, strobes, and horn strobes in the industry. With white or red plastic housings, wall or ceiling mounting options, and plain or FIRE-printed devices, SpectrAlert Advance can meet virtually any application requirement, including indoor, outdoor, wet, and dry applications in temperatures from −40°F to 151°F. Like the entire SpectrAlert Advance line, outdoor horns, strobes, and horn strobes for wall applications include a variety of features that increase application flexibility and simplify installation. First, field-selectable settings, including candela, automatic selection of 12- or 24-volt operation, horn tones, and three volume options enable installers to easily adapt devices to meet requirements. Next, SpectrAlert Advance devices use a universal mounting plate for both wall and ceiling applications. This mounting plate includes an onboard shorting spring that ensures wiring continuity before devices are installed, so installers can verify proper wiring without mounting the devices and exposing them to potential construction damage. Once the plates are mounted, all SpectrAlert Advance devices utilize a plug-in design with a single captured screw to speed installation and virtually eliminate costly ground faults. Outdoor devices ship with weatherproof plastic back boxes (metal back boxes are available separately) that accommodate in-and- out wiring for daisy chaining devices. Plastic back boxes feature removable side flanges and improved resistance to saltwater corrosion. Knock-outs located on the back eliminate the need to drill holes for screw-in mounting. Plastic and metal weatherproof back boxes come with ¾-inch top and bottom conduit entries and ¾-inch knock-outs at the back. A screw-in NPT plug with an O-ring gasket for a watertight seal is included with each back box. Outdoor Selectable- Output Horns, Strobes, and Horn Strobes for Wall Applications SpectrAlert® Advance outdoor audible visible products are rich with features that cut installation times and maximize profits. AVDS115-02 • 12/3/2019 • Page 2 SpectrAlert Advance Outdoor Horn, Strobe, and Horn StrobeSpecifications Architect/Engineer Specifications General SpectrAlert Advance outdoor horns, strobes, and horn strobes shall mount to a weatherproof back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Outdoor SpectrAlert Advance products shall operate between −40 and 151 degrees Fahrenheit from a regulated DC or full- wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The strobe shall be suitable for use in wet environments. Horn Strobe Combination The horn strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options shall be set by a multiple position switch. On four-wire products, the strobe shall be powered independently of the sounder. The horn or horn strobe models shall operate on a coded or non-coded power supply. The horn strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The horn strobe shall be suitable for use in wet environments. Physical/Electrical Specifications Operating Temperature –40°F to 151°F (–40°C to 66°C) Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR1 Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage with MLD3 Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions (including lens)5.6˝ L × 4.7˝ W × 2.5˝ D (142 mm L × 119 mm W × 64 mm D) Horn Dimensions 5.6˝ L × 4.7˝ W × 1.3˝ D (142 mm L × 119 mm W × 33 mm D) Wall-Mount Weatherproof Back Box Dimensions (SA-WBB)5.7˝ L × 5.1˝ W × 2.0˝ D (145 mm L × 130 mm W × 51 mm D) Notes: 1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. 2. 2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd. UL Max. Strobe Current Draw (mA RMS) Candela 8–17.5 Volts 16–33 Volts DC FWR DC FWR Standard Candela Range 15 123 128 66 71 15/75 142 148 77 81 30 NA NA 94 96 75 NA NA 158 153 95 NA NA 181 176 110 NA NA 202 195 115 NA NA 210 205 High Candela Range 135 NA NA 228 207 150 NA NA 246 220 177 NA NA 281 251 185 NA NA 286 258 UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, Standard Candela Range (15–115 cd) DC Input 8–17.5 Volts 16–33 Volts 15 15/75 15 15/75 30 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-Temporal High 141 152 91 100 116 176 201 221 229 Non-Temporal Medium 133 145 75 85 102 163 187 207 216 Non-Temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non-Temporal High 142 161 103 112 126 181 203 221 229 Non-Temporal Medium 134 155 85 95 110 166 189 208 216 Non-Temporal Low 132 154 80 90 105 161 184 202 211 UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, High Candela Range (135–185 cd) DC Input 16–33 Volts FWR Input 16–33 Volts 135 150 177 185 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281 Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267 Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262 UL Max. Horn Current Draw (mA RMS) Sound Pattern dB 8–17.5 Volts 16–33 Volts DC FWR DC FWR Temporal High 57 55 69 75 Temporal Medium 44 49 58 69 Temporal Low 38 44 44 48 Non-Temporal High 57 56 69 75 Non-Temporal Medium 42 50 60 69 Non-Temporal Low 41 44 50 50 Coded High 57 55 69 75 Coded Medium 44 51 56 69 Coded Low 40 46 52 50 UL Current Draw Data Horn Tones and Sound Output DataCandela Derating For K series products used at low temperatures, listed candela ratings must be reduced in accordance with this table. Strobe Output (cd) Listed Candela Candela rating at –40°F 15 Do not use below 32°F15/75 30 75 44 95 70 110 110 115 115 135 135 150 150 177 177 185 185 Horn and Horn Strobe Output (dBA) Switch Position Sound Pattern dB 8–17.5 Volts 16–33 Volts 24-Volt Nominal Reverberant Anechoic DC FWR DC FWR DC FWR DC FWR 1 Temporal High 78 78 84 84 88 88 99 98 2 Temporal Medium 74 74 80 80 86 86 96 96 3 Temporal Low 71 73 76 76 83 80 94 89 4 Non- Temporal High 82 82 88 88 93 92 100 100 5 Non- Temporal Medium 78 78 85 85 90 90 98 98 6 Non- Temporal Low 75 75 81 81 88 84 96 92 7†Coded High 82 82 88 88 93 92 101 101 8†Coded Medium 78 78 85 85 90 90 97 98 9†Coded Low 75 75 81 81 88 85 96 92 †Settings 7, 8, and 9 are not available on 2-wire horn strobe. 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 www.systemsensor.com ©2019 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. AVDS115-02 • 12/3/2019 SpectrAlert Advance Diagrams Model Description Red White Wall Horn Strobes P2RK P2WK 2-Wire Horn Strobe, Standard cd, Outdoor (includes plastic weatherproof back box) P2RK-P P2WK-P 2-Wire Horn Strobe, Standard cd, Outdoor, Plain (includes plastic weatherproof back box) P2RK-R P2WK-R 2-Wire Horn Strobe, Standard cd, Outdoor (does not include plastic weatherproof back box) P2RHK P2WHK 2-Wire Horn Strobe, High cd, Outdoor (includes plastic weatherproof back box) P2RHK-P P2WHK-P 2-Wire Horn Strobe, High cd, Outdoor, Plain (includes plastic weatherproof back box) P2RHK-R P2WHK-R 2-Wire Horn Strobe, High cd, Outdoor (does not include plastic weatherproof back box) P4RK P4WK 4-Wire Horn Strobe, Standard cd, Outdoor (includes plastic weatherproof back box) P4RK-R —4-Wire Horn Strobe, Standard cd, Outdoor (does not include plastic weatherproof back box) P2RHK-120 —2-Wire Horn Strobe, High cd, Outdoor, 120 V (includes plastic weatherproof back box) Wall Strobes SRK SWK Strobe, Standard cd, Outdoor (includes plastic weatherproof back box) SRK-P SWK-P Strobe, Standard cd, Outdoor, Plain (includes plastic weatherproof back box) SRK-R SWK-R Strobe, Standard cd, Outdoor (does not include plastic weatherproof back box) SRHK SWHK Strobe, High cd, Outdoor (includes plastic weatherproof back box) SRHK-P SWHK-P Strobe, High cd, Outdoor, Plain (includes plastic weatherproof back box) SRHK-R SWHK-R Strobe, High cd, Outdoor (does not include plastic weatherproof back box) Horns HRK —Horn, Red, Outdoor (includes plastic weatherproof back box) HRK-R —Horn, Red, Outdoor (does not include plastic weatherproof back box) Accessories SA-WBB SA-WBBW Metal Weatherproof Back Box WTP WTPW Metal Weatherproof Outdoor Flush-mounting Plate SpectrAlert Advance Ordering Information Notes: All -P models have a plain housing (no “FIRE” marking on cover). All -R models require metal weatherproof outdoor flush mounting plate or a metal weatherproof outdoor back box (order separately). “Standard cd” refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. “High cd” refers to strobes that include 135, 150, 177, and 185 candela settings. When replacing standard outdoor units both the device and back box must be replaced. 4.7˝ 5.6˝ 6.8˝Dia. 2.5˝ 2.5˝64mm119mm 142mm Wall-Mount Horn Strobes Wall Plastic Weatherproof Back Box Wall-Mount Horn Strobe with Plastic Weatherproof Back Box 801 Valley Avenue N.W. Suite D, Puyallup, WA 98371 Phone: (253) 840-9900 | Fax: (800) 591-4382 REDHAHF901QP Tab 8- BATTERIES PS S E R I E S TERMINALS: (mm) DIMENSIONS: inch (mm)PERFORMANCE SPECIFICATIONS Nominal Voltage 12 volts (6 cells) Nominal Capacity 20-hr. (350mA to 10.50 volts) 10-hr. (650mA to 10.50 volts) 5-hr. (1.2A to 10.20 volts) 1-hr. (4.5A to 9.00 volts) 7.00 AH 6.50 AH 6.00 AH4.50 AH Approximate Weight 4.80 lbs. (2.18 kg) Internal Resistance (approx.) 23.0 milliohms Max Short-Duration Discharge Current (10 Sec.)70.0 amperes Shelf Life (% of nominal capacity at 68°F (20°C)1 Month 3 Month 6 Month 97% 91% 83% Operating Temperature Range Charge Discharge 5°F (-15°C) to 122°F (50°C) -4°F (-20°C) to 140°F (60°C) Case ABS Plastic Power Sonic Chargers PSC-12800A-C PSC-121000-PC www.power-sonic.com To ensure safe and efficient operation always refer to the latest edition of our Technical Manual, as published on our website. © 2018. Power-Sonic Corporation. All rights reserved. All trademarks are the property of their respective owners.All data subject to change without notice. E&O.E CORPORATE HEADQUARTERS (USA AND INTERNATIONAL EXCLUDING EMEA) Power-Sonic Corporation 7550 Panasonic Way, San Diego, California 92154 T: +1 (619) 661 2020 F: +1 (619) 661 3650 E: customer-service@power-sonic.com POWER-SONIC EUROPE LIMITED (EMEA – EUROPE, MIDDLE EAST AND AFRICA) 3 Buckingham Square, Hurricane Way, Wickford, Essex SS11 8YQ T: +44 (0)1268 560686 F: +44 (0)1268 560902 E: salesEMEA@power-sonic.com General Purpose Fire & SecurityEmergency Lighting MODEL PS-1270 F1 12 Volt 7.0 Amp. Hr. Warning: Risk of fire, explosion, or burns.Do not disassemble, heat above 60 C, or incinerate. Rechargeable Sealed Lead-Acid BatteryDC power, constant voltage chargeCycle use: 14.4 - 15.0V(20 C)Standby use: 13.5 - 13.8V(20 C)Initial current: 2.1A MAX 8 0 13340 01000 Sealed RechargeableBattery 120070260211 L HT H W Tolerances are +/- 0.04 in. (+/- 1mm) and +/- 0.08 in. (+/- 2mm) for height dimensions. All data subject to change without notice. L: 5.95 (151) W: 2.56 (65) H: 3.70 (94) HT: 3.86 (98) L: 5.95 (151) W: 2.56 (65) H: 3.70 (94) HT: 3.86 (98) Tolerances are +/- 0.04 in. (+/- 1mm) and +/- 0.08 in. (+/- 2mm) for height dimensions. All data subject to change without notice. FEATURES •Absorbent Glass Mat (AGM) technology for superior performance •Valve regulated, maintenance free spill proof construction •Power/volume ratio yielding excellent energy density •Rugged vibration and impact resistant ABS case and cover •Gas recombination technology •5 year design life APPROVALS •Approved for transport by air. D.O.T., I.A.T.A., F.A.A. and C.A.B. certifi ed •U.L. recognized •ISO9001:2015 – Quality management systems Medical Re v 1 : 1 1 / 1 8 PS-1270 12V 7.0 AH @ 20-hr.12V 6.5 AH @ 10-hr. Rechargeable Sealed Lead Acid Battery PS – General Purpose Series OR Torque – Not Applicable 4.7 5 1.5 6.35 3.2 2.5 0.8 F1: Quick disconnect tabs, 0.187" x 0.032" – Mate with AMP. INC. FASTON “187” series Torque – Not Applicable 6.3 5 1.5 7.95 3.4 2.5 0.8 F2: Quick disconnect tabs, 0.250" x 0.032" – Mate with AMP. INC FASTON “250” series PS S E R I E S www.power-sonic.com To ensure safe and efficient operation always refer to the latest edition of our Technical Manual, as published on our website. © 2018. Power-Sonic Corporation. All rights reserved. All trademarks are the property of their respective owners.All data subject to change without notice. E&O.E CORPORATE HEADQUARTERS (USA AND INTERNATIONAL EXCLUDING EMEA) Power-Sonic Corporation 7550 Panasonic Way, San Diego, California 92154 T: +1 (619) 661 2020 F: +1 (619) 661 3650 E: customer-service@power-sonic.com POWER-SONIC EUROPE LIMITED (EMEA – EUROPE, MIDDLE EAST AND AFRICA) 3 Buckingham Square, Hurricane Way, Wickford, Essex SS11 8YQ T: +44 (0)1268 560686 F: +44 (0)1268 560902 E: salesEMEA@power-sonic.com SHELF LIFE & STORAGE LIFE CHARACTERISTICS IN STAND-BY USE Cap a c i t y R e t e n t i o n R a t i o ( % ) Standing Period (Months) 100 80 60 40 00 2 4 6 8 10 12 14 16 18 20 40oC(104oF) 30oC(86oF)20oC(68oF) 5oC (41oF) Charging is not necessary unless 100% of capacity is required. Charging beforeuse is necessaryto help recoverfull capacity. 100 80 60 40 20 0 012345 Ambient Temperature 20˚C (68˚F) Float Charging Voltage2.25 - 2.30 V/Cell Ret e n t i o n C a p a c i t y ( % ) Years SHELF LIFE & STORAGE LIFE CHARACTERISTICS IN STAND-BY USE Cap a c i t y R e t e n t i o n R a t i o ( % ) Standing Period (Months) 100 80 60 40 00 2 4 6 8 10 12 14 16 18 20 40oC(104oF) 30oC (86oF)20oC (68oF) 5oC(41oF) Charging is not necessary unless 100% of capacity is required. Charging beforeuse is necessaryto help recoverfull capacity. 100 80 60 40 20 0 012345 Ambient Temperature 20˚C (68˚F) Float Charging Voltage 2.25 - 2.30 V/Cell Ret e n t i o n C a p a c i t y ( % ) Years SHELF LIFE & STORAGE LIFE CHARACTERISTICS IN STAND-BY USE CHARGING Cycle Applications: Apply constant voltage charge at 2.35v/c – 2.45v/c (14.1 – 14.7v for 12v Monobloc) at 20°C. Initial charging current should be set at less than 0.25C Amps. Switch to fl oat charge to avoid overcharging. “Float” or “Stand-By” Service: Apply constant voltage charge of 2.25v/c – 2.30v/c (13.5 to 13.8 volts for 12v Monobloc at 20°C. When held at this voltage, the battery will seek its own current level and maintain itself in a fully charged condition. Temperature Compensation: Charging Voltage for both Cyclic and Standby applications should be regulated in relation to ambient temperature. As temperature rises charging voltage should be reduced to prevent overcharge and increased as temperature falls to avoid undercharge. For further charging information including temperature compensation factors, see Power Sonic Technical Manual/ Power Sonic Charger specifi cations. CHARGERS Power Sonic offers a wide range of chargers suitable for batteries with a variety of capacities. Please refer to our website for more information on our switch mode and transformer type chargers. Please contact our technical department for advice if you have diffi culty in locating a suitable charger. FURTHER INFORMATION Please refer to our website www.power-sonic.com for a complete range of useful downloads, such as product catalogs, material safety data sheets (MSDS), ISO certifi cation, etc. APPLICATIONS •General purpose •Emergency lighting •Medical •Fire and security PS-1270 12V 7.0 AH @ 20-hr.12V 6.5 AH @ 10-hr. Rechargeable Sealed Lead Acid BatteryPS – General Purpose Series Re v 1 : 1 1 / 1 8 801 Valley Avenue N.W. Suite D, Puyallup, WA 98371 Phone: (253) 840-9900 | Fax: (800) 591-4382 REDHAHF901QP Tab 9- BATTERY CALCULATIONS Project Name: Standby Hours: 24 Alarm Mins: 5 Installed By: Efficiency Factor: 20% Designed By: SLC Type: Class B Date: 1/16/2026 NAC Source Voltage: 20.4 Model #: AFC-50 Max Panel Current (amps): 5 Panel ID: Location: Qty Part #Description Each Total Each Total 1 AFC-50 Analog Addressable FACP 0.130 0.130 0.220 0.220 Panel Standby: 0.130 Panel Alarm: 0.220 1 UD-2000 / UD-1000 0.016 0.016 0.023 0.023 RA-6075/R 0.020 0.025 RA-6500 (R/F)0.020 0.050 LED-16 (F) Flush Mount LED Annunciator 0.025 0.025 LED-16 (F)* LED Annunciator LED Power* 0.015 0.210 CA-6075 0.012 0.044 PSN-1000(E)0.015 0.015 PAD100-SLCE-127 SLC Expander 0.060 0.060 NOHMI-SLCE-127** SLC Expander 0.060 0.060 IDC-6 Initating Zone Expander 0.020 0.020 IDC-6 Initating Zone Expander Power* 0.030 0.270 RLY-5 Relay Expander 0.025 0.035 RLY-5 Relay Expander Power* 0.010 0.135 DRV-50 LED Driver Module 0.025 0.025 DRV-50 LED Driver Module LED Power* 0.010 0.215 FCB-1000 Fire Communications Bridge 0.025 0.025 FIB-1000 Fiber Interface Board 0.030 0.030 MC-1000 0.010 0.010 SPG-1000 Serial Parallel Gateway 0.040 0.040 NCE-1000 Network Card Ethernet 0.050 0.050 NCF-1000 Network Card Fiber 0.095 0.095 PSK-1000 Programmable Soft Key module 0.018 0.019 (Maximum current draw on P-Link limited to 1 Amp)P-LINK Standby: 0.016 P-LINK Alarm: 0.023 *Only enter quantity if PLINK power is being used to power devices PAD-PD Analog Photo Smoke 0.000300 0.000300 PAD-PHD Analog Photo Smoke/Heat 0.000300 0.000300 PAD-HD Analog Fixed Temp Heat 0.000300 0.000300 PAD-CD Analog Carbon Monoxide Detector 0.000300 0.000300 PAD-PCD Analog Smoke/Carbon Monoxide Detector 0.000300 0.000300 PAD-PHCD Analog Smoke/Heat/Carbon Detector 0.000300 0.000300 PAD100-DRTS Duct Remote Test Switch 0.010000 0.015000 PAD-DUCT Addressable Duct Detector 0.000300 0.000300 PAD-DUCTR* Addressable Duct Detector w/Relay 0.000500 0.000500 2 PAD100-PSSA/PSDA Addressable Pull Station Single/Dual Action 0.000200 0.000400 0.000200 0.000400 PAD100-MIM Micro Input Module 0.000200 0.000200 4 PAD100-SIM Single Input Module 0.000240 0.000960 0.000240 0.000960 PAD100-DIM Dual Input Module 0.000240 0.000240 PAD100-RM Relay Module 0.000240 0.000240 PAD100-OROI One Relay One Input Module 0.000240 0.000240 PAD100-TRTI Two Relay Two Input Module 0.000240 0.000240 PAD100-ZM* Conventional Zone Module 0.000240 0.000240 PAD100-NAC* Notification Appliance Circuit 0.000200 0.000200 PAD100-SM Speaker Module 0.000200 0.000200 PAD100-IM Isolator Module 0.000150 0.000150 PAD100-LED LED Module 0.000240 0.000240 PAD100-LEDK Addressable LED w/ Key Switch 0.000200 0.000200 PAD100-SB*** Addressable Sounder Base 0.000200 0.000200 PAD100-LFSB*** Addressable Low Frequency Sounder Base 0.000200 0.000200 PAD100-RB* Addressable Relay Base 0.000200 0.000200 PAD100-IB Addressable Isolator Base 0.000150 0.000150 KENWORTH RED HAWK FIRE PROTECTION RED HAWK FIRE PROTECTION Flush Mount LCD Annunciator AFC-50 Battery & Voltage Drop Calculations Alarm (amps) Alarm ELECTRICAL ROOM LCD Annunciator DACT Card P-LINK (RS-485) Standby (amps)Addressable Fire Panel User assumes all responsibility to ensure the quantities and current draw values in this worksheet are accurate prior to submittal. Standby Class A Module Power Expander SLC Devices Standby Alarm ** REQUIRED IF USING NOHMI PROTOCOL SLC DEVICES Multi-Connect Expander AFC / ARC / IPA Series - PAD100/200 Potter Electric Signal (C)2022 1 of 3 AFC-50 Battery and Voltage Drop Calculation 1 PAD300-PD Analog Photo Smoke 0.000300 0.000300 0.000300 0.000300 PAD300-PD-I Analog Photo Smoke W/ Isolator 0.000300 0.000300 PAD300-PHD Analog Photo Smoke/Heat 0.000300 0.000300 PAD300-PHD-I Analog Photo Smoke/Heat/Isolater 0.000300 0.000300 PAD300-HD Analog Fixed Temp Heat 0.000300 0.000300 PAD300-HD-I Analog Fixed Temp Heat W/ Isolator 0.000300 0.000300 PAD300-CD Analog CO Detector 0.000300 0.000300 PAD300-CD-I Analog CO Detector W/Isolater 0.000300 0.000300 PAD300-PCD Analog Smoke/CO Detector 0.000300 0.000300 PAD300-PCD-I Analog Smoke/CO Detector W/Isolater 0.000300 0.000300 PAD300-PHCD Analog Smoke/Heat/CO Detector 0.000300 0.000300 PAD300-PHCD-I Analog Smoke/Heat/CO Detector W/ Isolater 0.000300 0.000300 PAD300-DD Addressable Duct Detector 0.000300 0.000300 PAD300-SB*** Addressable Sounder Base 0.000200 0.000200 PAD300-LFSB*** Addressable Low Frequency Sounder Base 0.000200 0.000200 PAD300-RB* Addressable Relay Base 0.000200 0.000200 PAD300-IB Addressable Isolator Base 0.000150 0.000150 PSA Analog Photo Smoke 0.000325 0.000325 PSHA Analog Photo Smoke/Heat 0.000325 0.000325 RHA Analog Rate of Rise Heat 0.000325 0.000325 FHA Analog Fixed Temp Heat 0.000325 0.000325 DDA Addressable Duct Detector 0.000325 0.000325 APS-SA/APS-DA Addressable Pull Station Single/Dual Action 0.000325 0.000325 MCM Mini Contact Input Module 0.000325 0.000325 SCM-4 Single Contact Input Module 0.000325 0.001000 DCM-4 Dual Contact Input Module 0.000325 0.001000 TRM-4 Twin Relay Output Module 0.000325 0.001000 CIZM-4 * Conventional Zone Input Mod 0.000325 0.001000 MOM-4 * Monitored Output Module 0.000325 0.001000 ARB * Detector Base w/Relay 0.000325 0.000325 ASB * Detector Base w/Sounder 0.000325 0.000325 SCI ** Short Circuit Isolator (Class A) 0.000325 0.002340 AIB ** Detector Base w/Isolator (Class A) 0.000325 0.002340 IM/IB/SCI/AIB Class B ** 1 0.000000 0.000000 0.036000 0.036000 * Requires Aux Power (Configure Below)SLC Standby: 0.001660 SLC Alarm: 0.037660 ** *** Standby (amps) Ckt Use Description Total 1 Notification 0.00000 0.30600 2 Notification 0.00000 0.15300 NAC Standby:0.00000 NAC Alarm:0.45900 I/O Circuits (See I/O Configuration below)Standby (amps) Ckt Use Description Total 1 0.00000 0.00000 2 0.00000 0.00000 I/O Standby: 0.00000 I/O Alarm: 0.00000 Battery Calculation Summary Standby (amps) Panel Current: 0.13000 0.22000 P-Link Current: 0.01600 0.02300 SLC Device Current: 0.00166 0.03766 NAC Circuit Current: 0.00000 0.45900 I/O Circuit Current: 0.00000 0.00000 SLC Loop Type: Class B Total Standby: 0.147660 Total Alarm: 0.73966 Device Addresses Used:7 Standby Hours: 24 Alarm Mins: 5 Device Addresses Available:50 AH Required:3.55 AH Required:0.07 Total Combined Standby & Alarm AmpHours Required: 3.62 5 Efficiency Factor: 20% Required Battery AmpHours: 4.34 Battery AmpHours Provided: 8 NAC Circuits (See NAC Configuration below)Alarm (amps) Total Alarm (amps) Total Alarm (amps) NAC CKT 1 NAC CKT 1 Note: The cabinet will house two 8 AH or 18 AH batteries. The charging circuit is rated for up to two 55 AH batteries. Requires Aux Sounder Base Power (Configure Below) SLC Loop Alarm LED Current See the installation manual for special considerations when installing IM, IB, AIB, SCI devices on Class B loops. Current Draw from Install Manual AFC / ARC / IPA Series - PAD300 PFC-6000 / P Series Potter Electric Signal (C)2022 2 of 3 AFC-50 Battery and Voltage Drop Calculation NAC Circuit Configuration & Voltage Drop 1/16/2026 NAC 1 MAX Circuit Current (amps): 3 Source Voltage Used (VDC): 20.4 Usage:Description: Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd #14 Stranded 3.26 0.000 0.306 20.40 16 Qty Lookup Type Each Total Each Total 2 P2RLED 0.000000 0.000000 0.153000 0.306000 Total Standby:0.00000 Total Alarm: 0.30600 NAC 2 MAX Circuit Current (amps): 3 Source Voltage Used (VDC): 20.4 Usage:Description: Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd #12 Solid 2.01 0.000 0.153 20.40 16 Qty Lookup Type Each Total Each Total 1 PG2RKLED 0.000000 0.000000 0.153000 0.153000 Total Standby:0.00000 Total Alarm: 0.15300 I/O Circuit Configuration & Voltage Drop 1/16/2026 I/O 1 MAX Circuit Current (amps): 1 Source Voltage Used (VDC): 20.4 Usage:Description: Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd #12 Solid 2.01 0.000 0.000 20.40 16 Qty Lookup Type Each Total Each Total Total Standby:0.00000 Total Alarm: 0.00000 I/O 2 MAX Circuit Current (amps): 1 Source Voltage Used (VDC): 20.4 Usage:Description: Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd #12 Solid 2.01 0.000 0.000 20.40 16 Qty Lookup Type Each Total Each Total Total Standby:0.00000 Total Alarm: 0.00000 Standby (amps) NAC CKT 1 Standby (amps)Alarm (amps) KENWORTH Circuit Devices Standby (amps) Alarm (amps) User can add devices on the fly Circuit Devices (No lookup function) User can add devices on the fly to these bottom rows Notification Circuit Devices Descrption Description Description Alarm (amps) to these bottom rows (No lookup function) HORN/STROBE 75CD WEATHERPROOF HORN/STROBE Notification Description KENWORTH NAC CKT 1 Standby (amps)Alarm (amps)Circuit Devices Potter Electric Signal (C)2022 3 of 3 AFC-50 Battery and Voltage Drop Calculation 801 Valley Avenue N.W. Suite D, Puyallup, WA 98371 Phone: (253) 840-9900 | Fax: (800) 591-4382 REDHAHF901QP Tab 10- CERTIFICATIONS Jonathon J Dworsack Fire Alarm Systems Level III 149662 2024-04-30 2028-03-01 Jeffrey Marshall Gordon Fire Alarm Systems Level II 145454 2026-08-01