HomeMy WebLinkAboutMFP26000225.pdfDEPARTMENT OF COMMUNITY
AND ECONOMIC DEVELOPMENT
Major Franchise Permit: MFP26000225
IVR Number: 26000225
Permit Information
Permit Name: Puget Sound Energy - Electric
101157296-ROL-13 TWFDR 116 4400FTAddress/Location:01/15/2026Application Date:2892600040Parcel Number: 11426 SE 169TH ST, OTHER
Permit Type:02/02/2026Issue Date:Franchise
Permit Work Class:02/02/2027Expiration Date:Major Utility
Job Number: 101157296Franchise Type:Electric
Description: Puget Sound Energy ElectricStart this project at pole with grid number 316744 166533 reconductor existing 336
ACSR to 336 ACSR tree wire. Reconductor this underbuilt distribution line. Contact the appropriate Transmission
engineer to coordinate efforts. Reconductor north to pole with grid number 316757 166569. Continue the reconductor
to the south along 116th Ave SE. At pole with grid number 316674 166567 (SK00387, ensure that this switch is fused
at 100T and is shown correctly on our maps. Continue this tree wire reconductor project south and west to poles with
grid numbers 316524 166540 and 316514 166563. East along SE Petrovitsky Rd, continue this tree wire
reconductor project. At pole with grid 316527 166665 relocate switch X3401 (65T)to this pole is possible. End this
reconductor east along SE Petrovitsky Rd at pole with grid number 316527 166678(X12295).This recloser is
operated (NO) Normally Open in a static environment.
Contacts
Name Address PhoneTypeBilling
Katie Zimmerman
Puget Sound Energy
1660 Park Lane
Burlington, WA 98233
B: (425) 620-6742
C: (425) 620-6742
ApplicantX
Permits Central 355 110th Ave NE
Bellevue, WA 98004
B: (425) 620-6742
H: (425) 620-6742
C: (425) 620-6742
Applicant
Vicki Henson
Potelco Inc
8001 212th St S
Kent, WA 98032
B: (253) 863-0484Contractor
Business License Number: 5109Electrical Contractor: POTELI*344O4
Construction Contractor: POTELI*227PL
Puget Sound Energy Inc 10885 NE 4th Street, PSE08-N08
Bellevue, WA 98009
B: (888) 225-5773Emergency
Contact
CITY OF RENTON ROW 1055 S Grady Way
Renton, WA 98057-3232
Owner
Katie Zimmerman
Puget Sound Energy
1660 Park Lane
Burlington, WA 98233
B: (425) 620-6742
C: (425) 620-6742
Specialized
Billing
General Conditions & Signature
Permission is hereby given for the work described on this permit according to the conditions hereon and according to the
approved plans and specifications pertaining thereto, subject to compliance with the Ordinance of the City of Renton.
Ÿ
This permit and plans must be posted at the job site at all times.Ÿ
I hereby certify that no work is to be done except as described above and in approved plans, and that work is to conform to
Renton Trench Restoration and Street Overlay Requirements.
Ÿ
Call 425.430.7203 or go to: https://permitting.rentonwa.gov one working day in advance to schedule an inspections and for ANY
work in the Right of Way.
Ÿ
Call 8 1 1 to locate underground utilities at least two full business days prior to any excavation.Ÿ
In accordance with RCW 19.122.033(4) the permit holder is required to contact (Williams Northwest Pipeline at 425.868.1010)
(Olympic Pipeline at 425.235.7736) (Puget Sound Energy at 425.375.3397) to request a consultation with the transmission
pipeline company prior to performing any construction or excavation activities. This requirement to consult with the
transmission pipeline company is in addition to the requirement to Call before You Dig as required in RCW 19.122.
Ÿ
Page 1 of 2THIS PERMIT AND PLANS MUST BE POSTED AT THE JOB SITE AT ALL TIMES
Note: The Applicant is responsible for compliance with all codes and regulations, whether or not described in this document.
PUBLIC WORKS DEPARTMENT
Page 1 of 6 | Published: 2/25/2025
Transportation Systems Division | 1055 South Grady Way, 5th Floor | Renton, WA 98057 | 425-430-7380
Website: rentonwa.gov
TRAFFIC CONTROL PLAN APPLICATION
Published: 2/25/2025
TRAFFIC CONTROL PLAN (TCP) MUST BE SUBMITTED TO PUBLIC WORKS TRANSPORTATION DIVISION
FOR REVIEW/APPROVAL AT LEAST FIVE (5) WORKING DAYS BEFORE THE DATE OF WORK AND FOR TRAFFIC SIGNAL
WORK WITHIN 150 FEET OF THE INTERSECTION AT LEAST FIFTEEN (15) WORKING DAYS BEFORE THE DATE OF WORK.
FOR PURPOSES OF THIS APPLICATION, WORKING DAYS ARE DEFINED AS MONDAY THRU FRIDAY, AND EXCLUDING
CITY HOLIDAYS.
The City of Renton requires any contractor, firm, corporation, or other public/private agency to prepare a Traffic
Control Plan (TCP) and obtain City's approval of that plan when construction, repair, or maintenance work is to be
conducted within the City's right-of-way.
1.Fill out the Traffic Control Plan (TCP) Application form and prepare required submittal documents.
2.All TCPs must conform to all attached requirements. Failure to do so may be subject to resubmittal.
3.Submit Application via email to TCP@rentonwa.gov with the subject line “TCP Application – [Project Name].”
4.Resubmittal may be required for TCPs that are incomplete and do not display proper requirements as
described in the guidelines. Additional review time may be needed.
By signing, I certify that the information on this application and within the submittal documents are accurate to the
best of my knowledge and I acknowledge and have read all the requirements and guidelines on this application.
Applicant’s Signature Date
Applicant’s Name (Print)
Project Name: Permit #:
Site Address:
Work Date: From _____________ To _____________ Work Time: Start ______________ End ______________
Construction Company:
Contact Name: Phone/Cell: _________________________
Business Address: City/State: Zip: ___________
Description of Work:
24 Hour Emergency
Contact Name & Phone:
Approval By: ______________________________________________ Date:____________________
PW/Transportation or CED/Development Engineering Division
Potelco, Inc
6905 S 228th St Kent, WA 98466
Please See Attached
Katie Zimmerman
1/15/2026
101157296-ROL-13 TWFDR 116 4400FT
11426 SE 169TH ST
AYLA SILER (425) 505-3330
MFP26000225
Monday Friday 8:00am 3:00pm
Scott Warlick CED 1/29/2026
Page 2 of 6 | Published: 2/25/2025
This Page Intentionally Left Blank
Page 3 of 6 | Published: 2/25/2025
APPLICANT AGREES TO ALL THE FOLLOWING REQUIREMENTS:
GENERAL
•Applicant is responsible for compliance with all traffic regulations of the City of Renton (City) and the State
of Washington, including codes and regulations not described in this application.
•Work Zone Traffic Control shall be in accordance with Manual on Uniform Traffic Control Devices (MUTCD)
and shown by a traffic control plan layout or reference to Washington State Department of Transportation
(WSDOT) traffic control plans.
•Any lane or street closures not in conformance with the approved Traffic Control Plan (TCP) and/or without
notification of emergency services may result in receiving a citation for violation of R.C.W. 47.36.200 Signs
or Flaggers at thoroughfare work sites and R.C.W. 9A.36.050 Reckless Endangerment, and other applicable
State and City codes.
•Indemnify and hold harmless the City from any and all claims, actions, and judgments, including all costs of
defense and attorney’s fees incurred in defending against same, arising from and related to
implementation of the approved TCPs including claims arising from towing of private vehicles and the acts
of Applicant’s agents and employees.
•Applicant must comply with all conditions of the application.
•The City shall be entitled, in its reasonable discretion, to settle claims prior to suit or judgment, and in such
event shall indemnify and hold harmless the City for any such claims paid, including the City’s reasonable
attorney’s fees and litigation costs incurred resulting from such claim.
•In the event any claim or suit is brought against City within the scope of this application, Applicant is
responsible to pay for legal counsel chosen by the City to defend against same.
•No more than one TCP shall be in use at any given time for a single project. If multiple TCPs are submitted
for review and approval at the same time, the TCPs shall be clearly labeled as separate plans and include
construction phasing and sequencing.
•Previously approved TCPs cannot be combined into a new TCP without review and approval by the City.
•Expired TCP is not valid and shall not be used. Applicant shall resubmit the expired TCP for approval with
the updated date and time and/or any changes to TCP.
•Applicant must have the approved TCP prior to commencing the work.
•Approved TCP must be at the work site during work hours.
•Signage shall be used to warn motorcyclists/bicyclists of the potential hazards on any uneven surfaced or
slippery road conditions during work and non-work hours.
•Any vehicle, equipment, barricade, or portable tow-away sign used within the work area must display a
company logo or any legally acceptable sign showing the company name, address, and telephone number
at a conspicuous place on the vehicle or equipment.
•At signalized intersections, vehicle detection shall always remain operational, unless approved in this TCP
and notified Transportation Signal Maintenance prior to commencing work. If damage occurs to existing
vehicle detection that is to remain, it is Applicant’s responsibility to replace with video vehicle detection
equipment that meets current City’s standards at Applicant’s expense.
•When not in use, temporary traffic control devices shall be removed or covered immediately. It is the
Applicant’s responsible to cover any temporary traffic control devices when not applicable for the
construction activities. Similarly, when work is suspended for short periods of time, traffic control devices
that are no longer necessary shall be removed or covered. If deemed abandoned, City crews will remove
and may store them at the City’s maintenance shop (3555 NE 2nd Street) for up to sixty (60) days. The City
is not responsible for any private property from City assets and identifying the property owner.
•Applicant is responsible to maintain existing pedestrian accessible routes during work and non-work hours.
At intersections, the work on pedestrian facilities shall be limited to one (1) corner at a time, with the least
possible inconvenience or delay to pedestrians. Pedestrian pushbuttons shall remain accessible at all times,
unless approved pedestrian accessible detour(s) are provided. Accessibility to existing or temporary
Page 4 of 6 | Published: 2/25/2025
pedestrian pushbuttons shall not be impaired. Deficiencies caused by Applicant’s operations shall be
repaired at Applicant’s expense.
•Applicant shall provide complete assistance and accommodation from a dedicated pedestrian escort to all
kinds of pedestrian traffic when sidewalk or walkway is impeded to safely redirect pedestrians around a
work zone.
•Driveway and alley access shall be maintained at all times, also see RMC Chapters 9 and 10 for Street
Closure and Street Excavation for details. Applicant is responsible for coordinating with the property
owners and/or residents prior to commencement of the work.
•Pavement excavation shall be limited to a maximum of one travel lane at a time unless otherwise
approved.
•Accessibility for emergency vehicles shall be maintained at all times.
PUBLIC OUTREACH
•Applicant must notify Transportation Signal Maintenance (425-430-7423) and City inspector (425-430-
7203) at least twenty-four (24) hours before commencing work (lane shift/closure or near a signal)
affecting the vehicle detection.
•Applicant shall notify emergency services (253-852-2121) twenty-four (24) hours before any street closures
or lane closures.
•Applicant shall call Renton School District (425-204-4455) or any public/private agency, including public
transit, to be affected by a temporary lane or road closure a minimum of five (5) working days (excluding
weekends and holidays) prior to starting any work.
•Applicant shall coordinate with King County Metro Transit Construction Information Center (206-477-1140
or construction.coord@kingcounty.gov) for any construction or installation activities affecting transit
operations or facilities. Notification information and guidelines can be found at:
https://kingcounty.gov/en/dept/metro/about/contractor-resources/transit-system-impacts.
WORKING DAYS AND TIMES
•Normal working days are Monday through Friday. Work on holidays, weekends or at night shall not occur
without City’s approval. For work times between 10:00 p.m. and 7:00 a.m., see Night Work section below
for details.
•Work time begins when any street or travel lane is fully or partially closed. This includes set up and removal
within the traveled way.
•If the City determines the closure hours adversely affect traffic during the work, the City may require to
adjust or reduce the working hours accordingly. Reduced work hours may be required by the City to
minimize traffic impacts for any work located near a school during pick-up and drop-off times or on an
arterial street. (See WSDOT Functional Classification Map:
https://www.wsdot.wa.gov/data/tools/geoportal/?config=FunctionalClass)
•Applicant may request the City for consideration of extended or modified working hours. Such request
must be approved by the City before changing hours of work.
CLOSURES
•All closure hours and days are subject to local permit and ordinance conditions (such as noise ordinances).
More information can be found on https://www.rentonwa.gov/City-Services/Permit-Center. Total street
closure lasting more than twenty-four (24) hours is subject to City Council authorization per Section 9-9 of
the Renton Municipal Code (RMC).
•Road closure notice – Applicant must install Portable Changeable Message Sign (PCMS) boards no less than
five (5) working days in advance of effective date and time, not including holidays, at location(s) as
identified in the TCP. Other methods of displaying the messages shall be approved by the City.
Page 5 of 6 | Published: 2/25/2025
•Road closure notice messages must include at least the following:
ROAD WILL BE CLOSED
MONTH/DAY – MONTH/DAY
_AM - _PM
•Road and/or sidewalk closure must be evaluated by the City with respect to both the necessity as well as
the impact of the closure to the public. Applicant shall submit detour plans for road closures to
accommodate both motorized and non-motorized users, including accessible pedestrian route(s). Road
closures shall require additional temporary traffic control including advance notification, approach and
detour signage.
•Applicant is responsible to temporarily remove the flags and install bags over the flag holders for any work
requiring the temporary closure of a crosswalk equipped with pedestrian flags. Applicant shall ensure the
bags remain intact and shall replace damaged bags as needed or determined necessary by the City of
Renton inspector. For any misplaced or lost flags, Applicant is responsible to replace at Applicant’s own
expense. Upon restoration of the crosswalk, Applicant shall remove the bags and return all flags to the
holders. Inventory of pedestrian flags must be submitted to the City inspector and reported to City of
Renton Transportation Signal Maintenance (425-430-7423) prior to removal.
UNIFORMED POLICE OFFICERS (UPO) / FLAGGERS
•Any construction activities within one hundred and fifty (150) feet of a signalized intersection shall require
Uniformed Police Officer(s) (UPO) at the traffic signal, unless otherwise approved in this TCP and evaluated
by City Transportation for the impacts of traffic signal operations and safety.
•Flagger and sign placement are subject to revision by the City Inspector on site, if needed to address traffic
or pedestrian safety or travel.
•For TCPs that require the presence of UPO to manage vehicular traffic and pedestrians at signalized
intersections, Applicant shall coordinate with Transportation Signal Maintenance (425-430-7423) at least
twenty-four (24) hours in advance for any signal that will be placed in red flashing mode. Applicant shall
notify Transportation Signal Maintenance when the intersection is back to the normal traffic signal
operations.
TEMPORARY TRAFFIC SIGNALS OR TRAFFIC SIGNAL MODIFICATION
•Temporary traffic signal programming or modification requires a minimum fifteen (15) working days for
each traffic signal controller to be programmed and tested by City Transportation staff before starting the
work. The Start Date on this TCP shall reflect the time for temporary traffic signal programming or
modification.
TEMPORARY NO-PARKING
•Applicant must post notice of date(s) and time(s) of Temporary No Parking Zone with signs at every
hundred (100) feet at least seventy-two (72) hours in advance of effective date and time.
•Applicant is responsible to show on the TCP the limits of Temporary No Parking Zone, identifying barricade
locations for vacate parking or curb lane usage. The cover sheet of this approved TCP form must be
attached to each Temporary No Parking Sign on the project site.
•Two travel lanes (one for each approach) must be open at all times on arterial streets unless approved in
this TCP.
NIGHT WORK
•Between the hours of 10 p.m. and 7 a.m., approved Noise Variance shall be required (See Section RMC 8-7-
8)for night work. Process may take up to twelve (12) weeks. More information can be found at
https://www.rentonwa.gov/City-Services/Permit-Center/Land-Use-Development/Noise-Variance.
•City may require night work for TCPs that have severe traffic impacts on arterial streets.
Page 6 of 6 | Published: 2/25/2025
•Night work shall always be required if two lanes of traffic (One for each approach) cannot be maintained
on an arterial street.
•Night work shall be required if an evaluation of existing traffic volumes and patterns finds that any TCP will
functionally reduce an arterial or high-volume collector street to only one lane of traffic.
•The following configurations may require night work:
Work at traffic signals that requires shifting one direction of traffic into a left turn pocket where a high
volume of left turns occur.
Work at traffic signals that requires shifting two directions of traffic into left turn pockets.
Work at traffic signals that requires shifting high-volume left-turn movement into a through lane on a
single approach to the intersection.
Work at signals that requires shifting left-turning traffic into a through lane on multiple approaches to
the intersection.
•If City’s initial TCP review finds that night work is required, a pre-construction meeting is mandatory to
confirm the extents of the work required, the duration of work, anticipated noise levels, and any potential
alternatives to mitigate the impact of night work to adjacent residents prior to review and approval of the
TCP.
TRAFFIC CONTROL PLAN (TCP) FORMAT
•TCP must be site and project specific. The TCP shall clearly indicate all existing transportation facilities
impacted by work including roads, bike lanes, sidewalks, transit stops, and driveways. Typical drawings,
taper tables and MUTCD illustrations, by themselves, are insufficient.
•Each construction phase shall be provided with appropriate work zone traffic control. The impacts of utility
relocation, traffic delays, detours and capacity restrictions must be considered and addressed. A suitable
sequence of construction activities must be discussed with City Staff prior to fully developing TCPs based on
the complexity of a project.
•TCPs shall be clearly labeled as separate plans to identify the construction sequencing during each phase
when more than one TCP layout is submitted.
•TCP must be submitted with an electronic copy of TCP layout(s), on 11” X 17” paper size PDF format, which
consist of:
Map(s) showing the location of the project and work area.
All fonts shall be legible and a minimum 10-point font size.
All symbols of viewing or printing shall be clear and contrasting.
All streets shall be labeled, and layout must include a north arrow and scale.
Must show channelizing devices, signing, flagger locations, barricades, PCMS boards, etc.
Show locations where the standard traffic control plans are applied.
SE 169TH ST
11
6
T
H
A
V
E
S
E
11
11
1
1
9
T
H
S
T
S
E
12
12
11 11 11
11
6
T
H
A
V
E
S
E
11 11 11
P01 P02
12
12
12 12
11
4
T
H
A
V
E
S
E
11426 SE 169th St
Renton
WA 98055
USA
11426 SE 169th St
Renton
WA 98055
USA
STOP
STOP
W20-1
RO
A
D
WO
R
K
AH
E
A
D
W20-4
ON
E
L
A
N
E
RO
A
D
AH
E
A
D
X'≥X'≥X'≥
W20-7A
W2
0
-
1
ROAD
WORKAHEAD
BEPREPARED
TO
STOP
W3
-
4
X'
≥
X'
≥
X'≥
W20-7A
W2
0
-
1
ROAD
WORKAHEAD
BE PREPARED
TO
STOP
W3
-
4
X'
≥
X'
≥
W2
0
-
1
ROAD
WORKAHEAD
BEPREPARED
TO
STOP
W3
-
4
X'
≥
X'
≥
RESIDENT(S) WILL BE INFORMED OF
TEMPORARY DRIVEWAY CLOSURE
FRO
M
TO
TO
W
A
W
A
Y
A
R
E
A
PHO
N
E
6
8
4
-
5
4
4
4
NAM
E
O
F
F
I
R
M
X
X
X
-
X
X
X
-
X
X
X
X
NO
P
A
R
K
I
N
G
PLACE SIGNS BOTH
SIDES OF WORK AREA
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Safaa Al Neema
(425) 398-6077
safaa.alneema@pse.com
1 OF 2411426 SE 169th St, Renton, WA 98055
0
11910045
09/04/2025
Puget Sound EnergyTraffic Control Supervisor:
Safaa Al Neema
Card No. IS 6 100072
Card Exp. 10/10/2028
Safaa.alneema@pse.com
(425)398-6077
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
WORK AREA
CHEVRON
ARROW BOARD
FLAGGER
UNIFORMED
POLICE OFFICERPOLICE
STOP
POLE
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated,
if indicated use ADA compliant channelization.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours as
per jurisdictional requirements. (Generally between 9
a.m. and 4 p.m. on non-arterials and from 9 a.m. to 3
p.m. on arterials. If night time work is approved,
signaling and flaggers shall conform to WAC
296-155-305. Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
MFP26000225
SE 169TH ST
11
6
T
H
A
V
E
S
E
11
11
P03
P04
1
1
9
T
H
S
T
S
E
12
12
11 11 11
11
6
T
H
A
V
E
S
E
11 11 11
P02
12
12
11426 SE 169th St
Renton
WA 98055
USA
11426 SE 169th St
Renton
WA 98055
USA
STOP
W20-1
RO
A
D
WO
R
K
AH
E
A
D
W20-4
ON
E
L
A
N
E
RO
A
D
AH
E
A
D
X'≥X'≥X'≥
W20-7A
STOP
STOP
RIGHT
KEEP
R4-7B
RIGHT
KEEP
R4-7B
W2
0
-
1
ROAD
WORK
AHEAD
CENTER LANE
CLOSEDAHEAD W9
-
3
X'
≥
X'
≥
X'≥
W2
0
-
7
A
W2
0
-
1
ROAD
WORK
AHEAD
CENTER LANE
CLOSED
AHEADW9
-
3
X'
≥
X'
≥
X'≥
W2
0
-
7
A
W
2
0
-
1
ROA
D
WOR
K
AHE
A
D
BE
PREP
A
R
E
D
TO
STO
P
W
3
-
4
X'
≥
X'
≥
RESIDENT(S) WILL BE INFORMED OF
TEMPORARY DRIVEWAY CLOSURE
FR
O
M
TO
TO
W
A
W
A
Y
A
R
E
A
PHO
N
E
6
8
4
-
5
4
4
4
NAM
E
O
F
F
I
R
M
X
X
X
-
X
X
X
-
X
X
X
X
NO
P
A
R
K
I
N
G
PLACE SIGNS BOTH
SIDES OF WORK AREA
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Safaa Al Neema
(425) 398-6077
safaa.alneema@pse.com
2 OF 2411426 SE 169th St, Renton, WA 98055
0
11910045
09/04/2025
Puget Sound EnergyTraffic Control Supervisor:
Safaa Al Neema
Card No. IS 6 100072
Card Exp. 10/10/2028
Safaa.alneema@pse.com
(425)398-6077
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
WORK AREA
CHEVRON
ARROW BOARD
FLAGGER
UNIFORMED
POLICE OFFICERPOLICE
STOP
POLE
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated,
if indicated use ADA compliant channelization.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours as
per jurisdictional requirements. (Generally between 9
a.m. and 4 p.m. on non-arterials and from 9 a.m. to 3
p.m. on arterials. If night time work is approved,
signaling and flaggers shall conform to WAC
296-155-305. Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
MFP26000225
SE 169TH ST
11
6
T
H
A
V
E
S
E
11525
11
11
P03
P04
11
9
T
H
S
T
S
E
12
12
11 11 11
SE 168TH ST
11
6
T
H
A
V
E
S
E
11 11 11
P05
11426 SE 169th St
Renton
WA 98055
USA
11426 SE 169th St
Renton
WA 98055
USA
STOP
W20-1
RO
A
D
WO
R
K
AH
E
A
D
W20-4
ON
E
L
A
N
E
RO
A
D
AH
E
A
D
X'≥X'≥X'≥
W20-7A
RIGHT
KEEP
R4-7B
RIGHT
KEEP
R4-7B
W1
-
9
STOP
STOP
CONETOPPER
W2
0
-
1
ROAD
WORK
AHEAD
CENTER LANE CLOSED
AHEADW9
-
3
X'
≥
X'
≥
X'≥
W2
0
-
7
A
BIKELANEENDSW9
-
1
B
BIKES MERGE WITH TRAFFICW4
-
1
B
X'
≥
X'≥
W
2
0
-
1
ROA
D
WOR
K
AHEA
D
BE
PREP
A
R
E
D
TO
STO
P
W
3
-
4
X'
≥
X'
≥
BEPREPARED
TOSTOP
W3
-
4
X'
≥
X'
≥
W2
0
-
7
A
BIKELANEENDS W9
-
1
B
BIKESMERGE WITHTRAFFICW4
-
1
B
X'
≥
X'
≥
W2
0
-
1
ROAD
WORKAHEAD
X'
≥
X'
≥
X'≥
RIGHT LANE
CLOSED
AHEAD
W2
0
-
5
R
W1
-
4
L
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Safaa Al Neema
(425) 398-6077
safaa.alneema@pse.com
3 OF 2411426 SE 169th St, Renton, WA 98055
0
11910045
09/04/2025
Puget Sound Energy
Traffic Control Supervisor:
Safaa Al NeemaCard No. IS 6 100072Card Exp. 10/10/2028Safaa.alneema@pse.com(425)398-6077
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
WORK AREA
CHEVRONARROW BOARD
FLAGGER
UNIFORMEDPOLICE OFFICERPOLICE
STOP
POLE
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated,
if indicated use ADA compliant channelization.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours as
per jurisdictional requirements. (Generally between 9
a.m. and 4 p.m. on non-arterials and from 9 a.m. to 3
p.m. on arterials. If night time work is approved,
signaling and flaggers shall conform to WAC
296-155-305. Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
MFP26000225
SE 169TH ST
11
6
T
H
A
V
E
S
E
11
11
P04
11
9
T
H
S
T
S
E
12
12
11 11 11
SE 168TH ST
11
6
T
H
A
V
E
S
E
11 11 11
P05
SE 168TH ST
13
12
13
11
11
11
11
11 12 11
11
6
T
H
A
V
E
S
E
RIGHT
KEEP
R4-7B
W1
-
9
CONETOPPER
BEPREPAREDTOSTOP
W3
-
4
X'
≥
X'
≥
W2
0
-
7
A
BIKELANEENDS W9
-
1
B
BIKESMERGE WITHTRAFFICW4
-
1
B
X'
≥
X'
≥
W2
0
-
1
ROAD
WORK
AHEAD
X'
≥
X'
≥
X'≥
RIGHT LANECLOSEDAHEAD
W2
0
-
5
R
W1
-
4
L
11 11 11
STOP
W20-1
RO
A
D
WO
R
K
AH
E
A
D
BE
PR
E
P
A
R
E
D
TO
ST
O
P
W3-4
X'≥X'≥X'≥
W20-7A
STOP
STOP
W
2
0
-
1
ROAD
WOR
K
AHE
A
D
W
2
0
-
4
ONE
L
A
N
E
ROAD
AHEA
D
X'
≥
X'
≥
X'≥
W
2
0
-
7
A
W2
0
-
1
ROADWORKAHEAD
CENTER LANE CLOSEDAHEADW9
-
3
X'
≥
X'
≥
X'≥
W2
0
-
7
A
W20-1
RO
A
D
WO
R
K
AH
E
A
D
BE
PR
E
P
A
R
E
D
TO
ST
O
P
W3-4
X'≥X'≥
W20-1
RO
A
D
WO
R
K
AH
E
A
D
BE
PR
E
P
A
R
E
D
TO
ST
O
P
W3-4
X'≥X'≥
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Safaa Al Neema
(425) 398-6077
safaa.alneema@pse.com
4 OF 2411426 SE 169th St, Renton, WA 98055
0
11910045
09/04/2025
Puget Sound Energy
Traffic Control Supervisor:
Safaa Al NeemaCard No. IS 6 100072Card Exp. 10/10/2028Safaa.alneema@pse.com(425)398-6077
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
WORK AREA
CHEVRONARROW BOARD
FLAGGER
UNIFORMED
POLICE OFFICERPOLICE
STOP
POLE
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated,
if indicated use ADA compliant channelization.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours as
per jurisdictional requirements. (Generally between 9
a.m. and 4 p.m. on non-arterials and from 9 a.m. to 3
p.m. on arterials. If night time work is approved,
signaling and flaggers shall conform to WAC
296-155-305. Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
MFP26000225
SE 171ST LN
SE 170TH CT
SE 169TH ST
11
6
T
H
A
V
E
S
E
11525
11
11
16
16
11
11
RO
A
D
WO
R
K
AH
E
A
D
W20-1
11
9
T
H
S
T
S
E
12
12
ROAD
WOR
K
AHEA
D
W
2
0
-
1
11 11 11
SE 168TH ST
11
6
T
H
A
V
E
S
E
11 11 11
W9
-
3
CENTER LANE CLOSED
AHEAD
ROAD
WORK
AHEADW2
0
-
1
RIGHT
KEEP
R4-7B
RIGHT
KEEP
R4-7B
RO
A
D
WO
R
K
AH
E
A
D
W20-1 RO
A
D
WO
R
K
AH
E
A
D
W20-1
M6
-
2
RIGHT LANE
CLOSED
AHEAD W2
0
-
5
R
W1
-
4
L
ROAD
WORKAHEAD W2
0
-
1
THE CREW SHALL CEASE
WORK FOR A FLAGGER/SPOTTER
TO ESCORT PEDESTRIANS
AROUND THE WORK AREA
CONETOPPER
CONETOPPER
P04
P06
RESIDENT(S) WILL BE INFORMED OF
TEMPORARY DRIVEWAY CLOSURE
X'
≥
X'
≥
X'
≥
X'≥
X'
≥
X'
≥
X'≥
BIKELANEENDS W9
-
1
B
BIKESMERGE WITHTRAFFICW4
-
1
B
X'
≥
X'
≥
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Safaa Al Neema
(425) 398-6077
safaa.alneema@pse.com
5 OF 2411426 SE 169th St, Renton, WA 98055
0
11910045
09/04/2025
Puget Sound Energy
Traffic Control Supervisor:
Safaa Al NeemaCard No. IS 6 100072Card Exp. 10/10/2028Safaa.alneema@pse.com(425)398-6077
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
WORK AREA
CHEVRON
ARROW BOARD
FLAGGER
UNIFORMED
POLICE OFFICERPOLICE
STOP
POLE MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated,
if indicated use ADA compliant channelization.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours as
per jurisdictional requirements. (Generally between 9
a.m. and 4 p.m. on non-arterials and from 9 a.m. to 3
p.m. on arterials. If night time work is approved,
signaling and flaggers shall conform to WAC
296-155-305. Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
MFP26000225
SE 172ND ST
SE 171ST LN
SE 170TH CT
SE 169TH ST
11
6
T
H
A
V
E
S
E
11525
11
11
16
16
11
11
15
15
11
9
T
H
S
T
S
E
12
12
ROAD
WOR
K
AHE
A
D
W
2
0
-
1
11 11 11
SE 168TH ST
11
6
T
H
A
V
E
S
E
11 11 11
W9
-
3
CENTER LANE
CLOSEDAHEAD
ROAD
WORK
AHEADW2
0
-
1
RIGHT
KEEP
R4-7B
RIGHT
KEEP
R4-7B
RO
A
D
WO
R
K
AH
E
A
D
W20-1
ON
L
Y
R3
-
5
R
ON
L
Y
R3
-
5
R
11 18
11 11 11
RIGHT LANE
CLOSED
AHEAD W2
0
-
5
R
W1
-
4
L
ROADWORKAHEAD W2
0
-
1
THE CREW SHALL CEASE
WORK FOR A FLAGGER/SPOTTER
TO ESCORT PEDESTRIANS
AROUND THE WORK AREA
M6
-
2
P06
P07
X'≥
X'
≥
X'
≥
X'≥
X'
≥
X'
≥
X'≥
BIKELANEENDS W9
-
1
B
BIKESMERGE WITHTRAFFICW4
-
1
B
X'
≥
X'≥
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Safaa Al Neema
(425) 398-6077
safaa.alneema@pse.com
6 OF 2411426 SE 169th St, Renton, WA 98055
0
11910045
09/04/2025
Puget Sound Energy
Traffic Control Supervisor:
Safaa Al NeemaCard No. IS 6 100072Card Exp. 10/10/2028Safaa.alneema@pse.com(425)398-6077
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
WORK AREA
CHEVRON
ARROW BOARD
FLAGGER
UNIFORMED
POLICE OFFICERPOLICE
STOP
POLE MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated,
if indicated use ADA compliant channelization.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours as
per jurisdictional requirements. (Generally between 9
a.m. and 4 p.m. on non-arterials and from 9 a.m. to 3
p.m. on arterials. If night time work is approved,
signaling and flaggers shall conform to WAC
296-155-305. Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
MFP26000225
SE 172ND ST
SE 171ST LN
SE 170TH CT
SE 169TH ST
11
6
T
H
A
V
E
S
E
11
11
16
16
11
11
15
15
11
6
T
H
A
V
E
S
E
11 11 11
RIGHT
KEEP
R4-7B
RO
A
D
WO
R
K
AH
E
A
D
W20-1
11 18
RO
A
D
WO
R
K
AH
E
A
D
W20-1
RIGHT LANECLOSED
AHEAD W2
0
-
5
R
W1
-
4
L
ROADWORKAHEAD W2
0
-
1
ST
R
E
E
T
CL
O
S
E
D
R1
1
-
2
W9
-
3
CENTER LANE CLOSEDAHEAD
ROAD
WORKAHEADW2
0
-
1
RO
A
D
CL
O
S
E
D
AH
E
A
D
W20-3
RO
A
D
WO
R
K
AH
E
A
D
W20-1
THE CREW SHALL CEASE
WORK FOR A FLAGGER/SPOTTER
TO ESCORT PEDESTRIANS
AROUND THE WORK AREA
RIGHT
KEEP
R4-7B
M6
-
2
CONETOPPER
CONETOPPER
P07
P08
RO
A
D
WO
R
K
AH
E
A
D
W20-1
X'≥
X'
≥
X'
≥
X'≥X'≥
X'
≥
X'≥
X'≥
BIKELANEENDS W9
-
1
B
BIKESMERGE WITHTRAFFICW4
-
1
B
X'
≥
X'≥
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Safaa Al Neema
(425) 398-6077
safaa.alneema@pse.com
7 OF 2411426 SE 169th St, Renton, WA 98055
0
11910045
09/04/2025
Puget Sound Energy
Traffic Control Supervisor:
Safaa Al NeemaCard No. IS 6 100072Card Exp. 10/10/2028Safaa.alneema@pse.com(425)398-6077
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
WORK AREA
CHEVRON
ARROW BOARD
FLAGGER
UNIFORMED
POLICE OFFICERPOLICE
STOP
POLE MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated,
if indicated use ADA compliant channelization.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours as
per jurisdictional requirements. (Generally between 9
a.m. and 4 p.m. on non-arterials and from 9 a.m. to 3
p.m. on arterials. If night time work is approved,
signaling and flaggers shall conform to WAC
296-155-305. Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
MFP26000225
SE 172ND ST
SE 171ST LN
SE 170TH CT
16
16
11
11
15
15
11
6
T
H
A
V
E
S
E
11 11 11
RO
A
D
WO
R
K
AH
E
A
D
W20-1
11 18
RO
A
D
WO
R
K
AH
E
A
D
W20-1
W9
-
3
CENTER LANE
CLOSEDAHEAD
ROAD
WORKAHEADW2
0
-
1
RIGHT
KEEP
R4-7B
CONETOPPER
THE CREW SHALL CEASE
WORK FOR A FLAGGER/SPOTTER
TO ESCORT PEDESTRIANS
AROUND THE WORK AREA
RO
A
D
WO
R
K
AH
E
A
D
W20-1
P08
P09
X'
≥
X'
≥
RIGHT LANE
CLOSED
AHEAD W2
0
-
5
R
W1
-
4
L
ROADWORK
AHEAD W2
0
-
1
X'
≥
X'
≥
X'≥
BIKELANE
ENDS W9
-
1
B
BIKESMERGE WITHTRAFFICW4
-
1
B
X'
≥
X'
≥
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Safaa Al Neema
(425) 398-6077
safaa.alneema@pse.com
8 OF 2411426 SE 169th St, Renton, WA 98055
0
11910045
09/04/2025
Puget Sound Energy
Traffic Control Supervisor:
Safaa Al NeemaCard No. IS 6 100072Card Exp. 10/10/2028Safaa.alneema@pse.com(425)398-6077
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
WORK AREA
CHEVRON
ARROW BOARD
FLAGGER
UNIFORMED
POLICE OFFICERPOLICE
STOP
POLE MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated,
if indicated use ADA compliant channelization.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours as
per jurisdictional requirements. (Generally between 9
a.m. and 4 p.m. on non-arterials and from 9 a.m. to 3
p.m. on arterials. If night time work is approved,
signaling and flaggers shall conform to WAC
296-155-305. Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
MFP26000225
SE 172ND ST
SE 170TH CT
16
16
11
11
11
6
T
H
A
V
E
S
E
11 11 11
11 11
STOP
FLAGGER
STOP
FLAGGER
W2
0
-
7
A
W2
0
-
4
ONE LANE ROADAHEAD
ROAD
WORK
AHEADW2
0
-
1
RO
A
D
WO
R
K
AH
E
A
D
W20-1 RO
A
D
WO
R
K
AH
E
A
D
W20-1
13
13
RO
A
D
CL
O
S
E
D
AH
E
A
D
W20-3
RO
A
D
WO
R
K
AH
E
A
D
W20-1
W2
0
-
7
A
W2
0
-
4
ONE LANEROADAHEAD
ROAD
WORKAHEAD W2
0
-
1
ST
R
E
E
T
CL
O
S
E
D
R1
1
-
2
SE 171ST LN
THE CREW SHALL CEASE
WORK FOR A FLAGGER/SPOTTER
TO ESCORT PEDESTRIANS
AROUND THE WORK AREA
11
6
T
H
A
V
E
S
E
P10
P09
X'
≥
X'
≥
X'
≥
X'
≥
X'≥
X'≥X'≥
X'
≥
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Safaa Al Neema
(425) 398-6077
safaa.alneema@pse.com
9 OF 2411426 SE 169th St, Renton, WA 98055
0
11910045
09/04/2025
Puget Sound Energy
Traffic Control Supervisor:
Safaa Al NeemaCard No. IS 6 100072Card Exp. 10/10/2028Safaa.alneema@pse.com(425)398-6077
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
WORK AREA
CHEVRON
ARROW BOARD
FLAGGER
UNIFORMED
POLICE OFFICERPOLICE
STOP
POLE MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated,
if indicated use ADA compliant channelization.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours as
per jurisdictional requirements. (Generally between 9
a.m. and 4 p.m. on non-arterials and from 9 a.m. to 3
p.m. on arterials. If night time work is approved,
signaling and flaggers shall conform to WAC
296-155-305. Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
MFP26000225
SE 173RD ST
SE 172ND ST
SE 170TH CT
16
16
11
11
11
6
T
H
A
V
E
S
E
11 11 11
11 18
STOP
FLAGGER
STOP
FLAGGER
13
13
SE 171ST LN
11 11
W20-7A
RO
A
D
WO
R
K
AH
E
A
D
W20-1
BE
PR
E
P
A
R
E
D
TO
ST
O
P
W3-4
100'100'100'
13
13
RESIDENT(S) WILL BE INFORMED OF
TEMPORARY DRIVEWAY CLOSURE
THE CREW SHALL CEASE
WORK FOR A FLAGGER/SPOTTER
TO ESCORT PEDESTRIANS
AROUND THE WORK AREA
11
6
T
H
A
V
E
S
E
P10
P11
W2
0
-
1
ROAD
WORK
AHEAD
W2
0
-
4
ONE LANEROADAHEADX'
≥
X'
≥
X'≥
W2
0
-
7
A
W20-1
RO
A
D
WO
R
K
AH
E
A
D
BE
PR
E
P
A
R
E
D
TO
ST
O
P
W3-4
X'≥X'≥X'≥
W20-7A
BIKELANEENDS W9
-
1
B
BIKESMERGE WITHTRAFFICW4
-
1
B
X'
≥
X'
≥
W2
0
-
1
ROADWORK
AHEAD
W2
0
-
4
ONE LANE ROADAHEAD X'
≥
X'
≥
X'≥
W2
0
-
7
A
STOP
FLAGGER
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Safaa Al Neema
(425) 398-6077
safaa.alneema@pse.com
10 OF 2411426 SE 169th St, Renton, WA 98055
0
11910045
09/04/2025
Puget Sound Energy
Traffic Control Supervisor:
Safaa Al NeemaCard No. IS 6 100072Card Exp. 10/10/2028Safaa.alneema@pse.com(425)398-6077
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
WORK AREA
CHEVRON
ARROW BOARD
FLAGGER
UNIFORMED
POLICE OFFICERPOLICE
STOP
POLE MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated,
if indicated use ADA compliant channelization.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours as
per jurisdictional requirements. (Generally between 9
a.m. and 4 p.m. on non-arterials and from 9 a.m. to 3
p.m. on arterials. If night time work is approved,
signaling and flaggers shall conform to WAC
296-155-305. Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
MFP26000225
SE 173RD ST
11
6
T
H
A
V
E
S
E
1111
1111
SE 172ND ST
P08
P09
11
6
T
H
A
V
E
S
E
11 18
13
13
11 11
13
13
STOP
FLAGGER
STOP
FLAGGER
RESIDENT(S) WILL BE INFORMED OF
TEMPORARY DRIVEWAY CLOSURE
THE CREW SHALL CEASE
WORK FOR A FLAGGER/SPOTTER
TO ESCORT PEDESTRIANS
AROUND THE WORK AREA
11
6
T
H
A
V
E
S
E
STOP
FLAGGER
W2
0
-
1
ROAD
WORK
AHEAD
W2
0
-
4
ONE LANEROADAHEADX'
≥
X'
≥
X'≥
W2
0
-
7
A
BIKELANEENDS W9
-
1
B
BIKESMERGE WITHTRAFFICW4
-
1
B
X'
≥
X'
≥
W20-1
RO
A
D
WO
R
K
AH
E
A
D
BE
PR
E
P
A
R
E
D
TO
ST
O
P
W3-4
X'≥X'≥X'≥
W20-7A
W2
0
-
1
ROAD
WORK
AHEAD
W2
0
-
4
ONE LANE ROADAHEAD X'
≥
X'
≥
X'≥
W2
0
-
7
A
W20-1
RO
A
D
WO
R
K
AH
E
A
D
X'≥
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Safaa Al Neema
(425) 398-6077
safaa.alneema@pse.com
11 OF 2411426 SE 169th St, Renton, WA 98055
0
11910045
09/04/2025
Puget Sound Energy
Traffic Control Supervisor:
Safaa Al NeemaCard No. IS 6 100072Card Exp. 10/10/2028Safaa.alneema@pse.com(425)398-6077
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
WORK AREA
CHEVRON
ARROW BOARD
FLAGGER
UNIFORMED
POLICE OFFICERPOLICE
STOP
POLE MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated,
if indicated use ADA compliant channelization.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours as
per jurisdictional requirements. (Generally between 9
a.m. and 4 p.m. on non-arterials and from 9 a.m. to 3
p.m. on arterials. If night time work is approved,
signaling and flaggers shall conform to WAC
296-155-305. Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
MFP26000225
SE 173RD ST
11
6
T
H
A
V
E
S
E
1111
SE 172ND ST1118
13
13
11 11
13
13
STOP
FLAGGER
STOP
FLAGGER
STOP
FLAGGER
RESIDENT(S) WILL BE INFORMED OF
TEMPORARY DRIVEWAY CLOSURE
THE CREW SHALL CEASE
WORK FOR A FLAGGER/SPOTTER
TO ESCORT PEDESTRIANS
AROUND THE WORK AREA
P12
P13
W2
0
-
1
ROAD
WORK
AHEAD
W2
0
-
4
ONE LANEROADAHEADX'
≥
X'
≥
X'≥
W2
0
-
7
A
BIKELANEENDS W9
-
1
B
BIKESMERGE WITHTRAFFICW4
-
1
B
X'
≥
X'
≥
W20-1
RO
A
D
WO
R
K
AH
E
A
D
BE
PR
E
P
A
R
E
D
TO
ST
O
P
W3-4
X'≥X'≥X'≥
W20-7A
W2
0
-
1
ROAD
WORK
AHEAD
W2
0
-
4
ONE LANE ROADAHEAD X'
≥
X'
≥
X'≥
W2
0
-
7
A
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Safaa Al Neema
(425) 398-6077
safaa.alneema@pse.com
12 OF 2411426 SE 169th St, Renton, WA 98055
0
11910045
09/04/2025
Puget Sound Energy
Traffic Control Supervisor:
Safaa Al NeemaCard No. IS 6 100072Card Exp. 10/10/2028Safaa.alneema@pse.com(425)398-6077
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
WORK AREA
CHEVRON
ARROW BOARD
FLAGGER
UNIFORMED
POLICE OFFICERPOLICE
STOP
POLE MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated,
if indicated use ADA compliant channelization.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours as
per jurisdictional requirements. (Generally between 9
a.m. and 4 p.m. on non-arterials and from 9 a.m. to 3
p.m. on arterials. If night time work is approved,
signaling and flaggers shall conform to WAC
296-155-305. Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
MFP26000225
SE 173RD ST
SE 175TH ST
11
6
T
H
A
V
E
S
E
1111
1111
13
13
STOP
FLAGGER
STOP
FLAGGER
RESIDENT(S) WILL BE INFORMED OF
TEMPORARY DRIVEWAY CLOSURE
THE CREW SHALL CEASE
WORK FOR A FLAGGER/SPOTTER
TO ESCORT PEDESTRIANS
AROUND THE WORK AREA
P13
P14
BIKELANEENDS W9
-
1
B
BIKESMERGE WITHTRAFFICW4
-
1
B
X'
≥
X'
≥
W2
0
-
1
ROAD
WORKAHEAD
W2
0
-
4
ONE LANEROADAHEADX'
≥
X'
≥
X'≥
W2
0
-
7
A
W20-1
RO
A
D
WO
R
K
AH
E
A
D
BE
PR
E
P
A
R
E
D
TO
ST
O
P
W3-4
X'≥X'≥
W2
0
-
1
ROAD
WORK
AHEAD
W2
0
-
4
ONE LANE ROADAHEAD X'
≥
X'
≥
X'≥
W2
0
-
7
A
STOP
FLAGGER
W20-1
RO
A
D
WO
R
K
AH
E
A
D
BE
PR
E
P
A
R
E
D
TO
ST
O
P
W3-4
X'≥X'≥X'≥
W20-7A
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Safaa Al Neema
(425) 398-6077
safaa.alneema@pse.com
13 OF 2411426 SE 169th St, Renton, WA 98055
0
11910045
09/04/2025
Puget Sound Energy
Traffic Control Supervisor:
Safaa Al NeemaCard No. IS 6 100072Card Exp. 10/10/2028Safaa.alneema@pse.com(425)398-6077
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
WORK AREA
CHEVRON
ARROW BOARD
FLAGGER
UNIFORMED
POLICE OFFICERPOLICE
STOP
POLE MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated,
if indicated use ADA compliant channelization.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours as
per jurisdictional requirements. (Generally between 9
a.m. and 4 p.m. on non-arterials and from 9 a.m. to 3
p.m. on arterials. If night time work is approved,
signaling and flaggers shall conform to WAC
296-155-305. Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
MFP26000225
SE 173RD ST
SE 175TH ST
11
6
T
H
A
V
E
S
E
1111
1111
11
6
T
H
A
V
E
S
E
13
13
STOP
FLAGGER
STOP
FLAGGER
RESIDENT(S) WILL BE INFORMED OF
TEMPORARY DRIVEWAY CLOSURE
THE CREW SHALL CEASE
WORK FOR A FLAGGER/SPOTTER
TO ESCORT PEDESTRIANS
AROUND THE WORK AREA
P14
P15
P16
W2
0
-
1
ROAD
WORKAHEAD
W2
0
-
4
ONE LANE ROADAHEAD X'
≥
X'
≥
X'≥
W2
0
-
7
A
W20-1
RO
A
D
WO
R
K
AH
E
A
D
W20-4
ON
E
L
A
N
E
RO
A
D
AH
E
A
D
X'≥X'≥X'≥
W20-7A
STOP
FLAGGER
W2
0
-
1
ROAD
WORKAHEAD
W2
0
-
4
ONE LANEROADAHEADX'
≥
X'
≥
X'≥
W2
0
-
7
A
BIKELANEENDS W9
-
1
B
BIKESMERGE WITHTRAFFICW4
-
1
B
X'
≥
X'
≥
W20-7A
SE PETROVITSKY RD
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Safaa Al Neema
(425) 398-6077
safaa.alneema@pse.com
14 OF 2411426 SE 169th St, Renton, WA 98055
0
11910045
09/04/2025
Puget Sound Energy
Traffic Control Supervisor:
Safaa Al NeemaCard No. IS 6 100072Card Exp. 10/10/2028Safaa.alneema@pse.com(425)398-6077
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
WORK AREA
CHEVRON
ARROW BOARD
FLAGGER
UNIFORMED
POLICE OFFICERPOLICE
STOP
POLE MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated,
if indicated use ADA compliant channelization.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours as
per jurisdictional requirements. (Generally between 9
a.m. and 4 p.m. on non-arterials and from 9 a.m. to 3
p.m. on arterials. If night time work is approved,
signaling and flaggers shall conform to WAC
296-155-305. Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
MFP26000225
SE 175TH ST
11
6
T
H
A
V
E
S
E
SE PETROVITSKY RD
1111
P13
P14
11
6
T
H
A
V
E
S
E
POLICEUPO
ONLYONLY
16 11 13
12
12
12
12
1414
12
12
12
12
ONLYONLY
111213
RESIDENT(S) WILL BE INFORMED OF
TEMPORARY DRIVEWAY CLOSURE
THE CREW SHALL CEASE
WORK FOR A FLAGGER/SPOTTER
TO ESCORT PEDESTRIANS
AROUND THE WORK AREA
X'
X'
PLACE W20-1 SIGNS ON ALL
ADJACENT STREETS WITHIN
FEET OF WORK AREA
ROAD
WORK
AHEAD W2
0
-
1
ROAD
WORKAHEADW2
0
-
1
1050
STOP
W2
0
-
1
ROAD
WORKAHEAD
W2
0
-
4
ONE LANE ROADAHEAD X'
≥
X'
≥
X'≥
W2
0
-
7
A
W20-7A
STOP
W2
0
-
1
ROAD
WORK
AHEAD
BEPREPARED
TOSTOP
W3
-
4
X'
≥
X'
≥
X'≥
W2
0
-
7
A
W20-1
RO
A
D
WO
R
K
AH
E
A
D
BE
PR
E
P
A
R
E
D
TO
ST
O
P
W3-4
X'≥X'≥X'≥
W20-7A
W20-1
RO
A
D
WO
R
K
AH
E
A
D
BE
PR
E
P
A
R
E
D
TO
ST
O
P
W3-4
X'≥X'≥X'≥
W20-7A
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Safaa Al Neema
(425) 398-6077
safaa.alneema@pse.com
15 OF 2411426 SE 169th St, Renton, WA 98055
0
11910045
09/04/2025
Puget Sound Energy
Traffic Control Supervisor:
Safaa Al NeemaCard No. IS 6 100072Card Exp. 10/10/2028Safaa.alneema@pse.com(425)398-6077
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
WORK AREA
CHEVRON
ARROW BOARD
FLAGGER
UNIFORMED
POLICE OFFICERPOLICE
STOP
POLE MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated,
if indicated use ADA compliant channelization.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours as
per jurisdictional requirements. (Generally between 9
a.m. and 4 p.m. on non-arterials and from 9 a.m. to 3
p.m. on arterials. If night time work is approved,
signaling and flaggers shall conform to WAC
296-155-305. Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
MFP26000225
SE 175TH ST
11
6
T
H
A
V
E
S
E
SE PETROVITSKY RD
1111
P17
11
6
T
H
A
V
E
S
E
POLICEUPO
ONLYONLY
16 11 13
12
12
12
12
1414
12
12
12
12
ONLYONLY
111213
P18
11
6
T
H
A
V
E
S
E
11
11
SE 177TH PL
10 10
11
6
T
H
A
V
E
S
E
SE PETROVITSKY RD
STOP
STOP
W20-1
RO
A
D
WO
R
K
AH
E
A
D
BE
PR
E
P
A
R
E
D
TO
ST
O
P
W3-4
X'≥X'≥X'≥
W20-7A
W20-1
RO
A
D
WO
R
K
AH
E
A
D
BE
PR
E
P
A
R
E
D
TO
ST
O
P
W3-4
X'≥X'≥X'≥
W20-7A
W2
0
-
1
ROAD
WORK
AHEAD
BE
PREPARED
TOSTOP
W3
-
4
X'
≥
X'
≥
X'≥
W2
0
-
7
A
W20-1
RO
A
D
WO
R
K
AH
E
A
D
BE
PR
E
P
A
R
E
D
TO
ST
O
P
W3-4
X'≥X'≥
W20-7A
W2
0
-
1
ROAD
WORK
AHEAD
W2
0
-
4
ONE LANE ROADAHEAD X'
≥
X'
≥
X'≥
W2
0
-
7
A
RESIDENT(S) WILL BE INFORMED OF
TEMPORARY DRIVEWAY CLOSURE
THE CREW SHALL CEASE
WORK FOR A FLAGGER/SPOTTER
TO ESCORT PEDESTRIANS
AROUND THE WORK AREA
THE CREW SHALL CEASE
WORK FOR A FLAGGER/SPOTTER
TO ESCORT PEDESTRIANS
AROUND THE WORK AREA
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Safaa Al Neema
(425) 398-6077
safaa.alneema@pse.com
16 OF 2411426 SE 169th St, Renton, WA 98055
0
11910045
09/04/2025
Puget Sound Energy
Traffic Control Supervisor:
Safaa Al NeemaCard No. IS 6 100072Card Exp. 10/10/2028Safaa.alneema@pse.com(425)398-6077
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
WORK AREA
CHEVRON
ARROW BOARD
FLAGGER
UNIFORMED
POLICE OFFICERPOLICE
STOP
POLE MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated,
if indicated use ADA compliant channelization.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours as
per jurisdictional requirements. (Generally between 9
a.m. and 4 p.m. on non-arterials and from 9 a.m. to 3
p.m. on arterials. If night time work is approved,
signaling and flaggers shall conform to WAC
296-155-305. Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
MFP26000225
SE PETROVITSKY RD
11
6
T
H
A
V
E
S
E
ONLYONLY
16 11 13
12
12
12
12
1414
12
12
12
12
ONLYONLY
111213
P19
P20
11
6
T
H
A
V
E
S
E
12
12
13
11
12
SE PETROVITSKY RD
ARRW-BRD
W20-1
RO
A
D
WO
R
K
AH
E
A
D
RIG
H
T
L
A
N
E
CL
O
S
E
D
AH
E
A
D
W20-5R W4-2R
X'≥X'≥X'≥
W2
0
-
1
ROADWORK
AHEAD
X'
≥
W2
0
-
1
ROAD
WORK
AHEAD
X'
≥
W20-1
RO
A
D
WO
R
K
AH
E
A
D
X'≥
THE CREW SHALL CEASE
WORK FOR A FLAGGER/SPOTTER
TO ESCORT PEDESTRIANS
AROUND THE WORK AREA
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Safaa Al Neema
(425) 398-6077
safaa.alneema@pse.com
17 OF 2411426 SE 169th St, Renton, WA 98055
0
11910045
09/04/2025
Puget Sound EnergyTraffic Control Supervisor:
Safaa Al Neema
Card No. IS 6 100072
Card Exp. 10/10/2028
Safaa.alneema@pse.com
(425)398-6077
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
WORK AREA
CHEVRON
ARROW BOARD
FLAGGER
UNIFORMED
POLICE OFFICERPOLICE
STOP
POLE
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated,
if indicated use ADA compliant channelization.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours as
per jurisdictional requirements. (Generally between 9
a.m. and 4 p.m. on non-arterials and from 9 a.m. to 3
p.m. on arterials. If night time work is approved,
signaling and flaggers shall conform to WAC
296-155-305. Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
MFP26000225
SE PETROVITSKY RD
11
6
T
H
A
V
E
S
E
POLICEUPO
ONLYONLY
16 11 13
12
12
12
12
1414
12
12
12
12
ONLYONLY
111213
1313
11
7
T
H
A
V
E
S
E
12
12
12
12
12
P21
P20
P22
11
6
T
H
A
V
E
S
E
10 10
11
6
T
H
A
V
E
S
E
12
12
13
11
12
SE PETROVITSKY RD
THE CREW SHALL CEASE
WORK FOR A FLAGGER/SPOTTER
TO ESCORT PEDESTRIANS
AROUND THE WORK AREA
THE CREW SHALL CEASE
WORK FOR A FLAGGER/SPOTTER
TO ESCORT PEDESTRIANS
AROUND THE WORK AREA
ARRW-BRD
W20-1
RO
A
D
WO
R
K
AH
E
A
D
RIG
H
T
L
A
N
E
CL
O
S
E
D
AH
E
A
D
W20-5R W4-2R
X'≥X'≥X'≥
BE
PR
E
P
A
R
E
D
TO
ST
O
P
W3-4
X'≥X'≥
W20-7A
W20-1
RO
A
D
WO
R
K
AH
E
A
D
BE
PR
E
P
A
R
E
D
TO
ST
O
P
W3-4
X'≥X'≥X'≥
W20-7A
W2
0
-
1
ROAD
WORK
AHEAD
BE PREPARED
TOSTOP
W3
-
4 X'
≥
X'
≥
X'≥
W2
0
-
7
A
STOP
W2
0
-
1
ROAD
WORK
AHEAD
BEPREPARED
TO
STOP
W3
-
4
X'
≥
X'
≥
X'≥
W2
0
-
7
A
ROAD
WORK
AHEADW2
0
-
1
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Safaa Al Neema
(425) 398-6077
safaa.alneema@pse.com
18 OF 2411426 SE 169th St, Renton, WA 98055
0
11910045
09/04/2025
Puget Sound EnergyTraffic Control Supervisor:
Safaa Al Neema
Card No. IS 6 100072
Card Exp. 10/10/2028
Safaa.alneema@pse.com
(425)398-6077
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
WORK AREA
CHEVRONARROW BOARD
FLAGGER
UNIFORMED
POLICE OFFICERPOLICE
STOP
POLE
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated,
if indicated use ADA compliant channelization.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours as
per jurisdictional requirements. (Generally between 9
a.m. and 4 p.m. on non-arterials and from 9 a.m. to 3
p.m. on arterials. If night time work is approved,
signaling and flaggers shall conform to WAC
296-155-305. Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
MFP26000225
SE PETROVITSKY RD
11
6
T
H
A
V
E
S
E
ONLYONLY
16 11 13
12
12
12
12
1414
12
12
12
12
ONLYONLY
111213
1313
11
7
T
H
A
V
E
S
E
12
12
12
12
12
SE PETROVITSKY RD
ROAD
WORK
AHEADW2
0
-
1
P21 P22
11
6
T
H
A
V
E
S
E
12
12
13
11
12
SE PETROVITSKY RD
ARRW-BRD
W20-1
RO
A
D
WO
R
K
AH
E
A
D
RIG
H
T
L
A
N
E
CL
O
S
E
D
AH
E
A
D
W20-5R W4-2R
X'≥X'≥X'≥
W2
0
-
1
ROAD
WORKAHEAD
X'
≥
W2
0
-
1
ROAD
WORKAHEAD
X'
≥
W20-1
RO
A
D
WO
R
K
AH
E
A
D
X'≥
THE CREW SHALL CEASE
WORK FOR A FLAGGER/SPOTTER
TO ESCORT PEDESTRIANS
AROUND THE WORK AREA
RESIDENT(S) WILL BE INFORMED OF
TEMPORARY DRIVEWAY CLOSURE
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Safaa Al Neema
(425) 398-6077
safaa.alneema@pse.com
19 OF 2411426 SE 169th St, Renton, WA 98055
0
11910045
09/04/2025
Puget Sound EnergyTraffic Control Supervisor:
Safaa Al Neema
Card No. IS 6 100072
Card Exp. 10/10/2028
Safaa.alneema@pse.com
(425)398-6077
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
WORK AREA
CHEVRONARROW BOARD
FLAGGER
UNIFORMED
POLICE OFFICERPOLICE
STOP
POLE
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated,
if indicated use ADA compliant channelization.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours as
per jurisdictional requirements. (Generally between 9
a.m. and 4 p.m. on non-arterials and from 9 a.m. to 3
p.m. on arterials. If night time work is approved,
signaling and flaggers shall conform to WAC
296-155-305. Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
MFP26000225
SE PETROVITSKY RD
11
6
T
H
A
V
E
S
E
ONLYONLY
16 11 13
12
12
12
12
1414
12
12
12
12
ONLYONLY
111213
1313
11
7
T
H
A
V
E
S
E
11
8
T
H
A
V
E
S
E
11
8
T
H
A
V
E
S
E
SE 176TH CT
12
12
1414
1414
12
12
12
12
12
SE PETROVITSKY RD
11 11 14
BUSSTOP
BUS
STOP
MOVE BUS STOP 250' EAST.
KING COUNTY METRO
WILL BE CONTACTED AT
206-477-1150 FIVE DAYS IN ADVANCE
OF SCHEDULED DATE.
P22
11
6
T
H
A
V
E
S
E
SE PETROVITSKY RD
STOP
KE
E
P
R4
-
7
B
RIG
H
T
KEEP
R4-7B
RIGHT
KE
E
P
R4
-
7
B
RI
G
H
T
STOP
STOP
STOP
BE
PR
E
P
A
R
E
D
TO
ST
O
P
W3-4
X'≥X'≥
W20-7A W20-1
RO
A
D
WO
R
K
AH
E
A
D
RIG
H
T
L
A
N
E
CL
O
S
E
D
AH
E
A
D
W20-5R
W4-2R
X'≥X'≥X'≥
W2
0
-
1
ROAD
WORKAHEAD
BE
PREPARED
TO
STOP
W3
-
4X'
≥
X'
≥
X'≥
W2
0
-
7
A
W20-1
RO
A
D
WO
R
K
AH
E
A
D
BE
PR
E
P
A
R
E
D
TO
ST
O
P
W3-4
X'≥X'≥
W2
0
-
1
ROAD
WORK
AHEAD
CENTER LAN
E
CLOSED
AHEADW9
-
3
X'≥
X'≥
X'≥
W2
0
-
7
A
BE
PR
E
P
A
R
E
D
TO
ST
O
P
W3-4
X'≥X'≥
W20-7AW20-1
RO
A
D
WO
R
K
AH
E
A
D
RIG
H
T
L
A
N
E
CL
O
S
E
D
AH
E
A
D
W20-5R W4-2R
X'≥X'≥X'≥
W2
0
-
1
ROAD
WORK
AHEAD
X'
≥
W2
0
-
1
ROAD
WORK
AHEAD
X'≥
W2
0
-
1
ROAD
WORK
AHEAD
BE PREPAREDTOSTOP
W3
-
4 X'≥
X'
≥
X'≥
W2
0
-
7
A
THE CREW SHALL CEASE
WORK FOR A FLAGGER/SPOTTER
TO ESCORT PEDESTRIANS
AROUND THE WORK AREA
P23
J02
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Safaa Al Neema
(425) 398-6077
safaa.alneema@pse.com
20 OF 2411426 SE 169th St, Renton, WA 98055
0
11910045
09/04/2025
Puget Sound EnergyTraffic Control Supervisor:
Safaa Al Neema
Card No. IS 6 100072
Card Exp. 10/10/2028
Safaa.alneema@pse.com
(425)398-6077
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
WORK AREA
CHEVRONARROW BOARD
FLAGGER
UNIFORMEDPOLICE OFFICERPOLICE
STOP
POLE
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated,
if indicated use ADA compliant channelization.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours as
per jurisdictional requirements. (Generally between 9
a.m. and 4 p.m. on non-arterials and from 9 a.m. to 3
p.m. on arterials. If night time work is approved,
signaling and flaggers shall conform to WAC
296-155-305. Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
MFP26000225
P23
P24
1313
11
7
T
H
A
V
E
S
E
11
8
T
H
A
V
E
S
E
11
8
T
H
A
V
E
S
E
1414
12
12
12
12
12
12
12
12
12
SE PETROVITSKY RD
SE PETROVITSKY RD
11 11 14
BUS
STOP
THE CREW SHALL CEASE
WORK FOR A FLAGGER/SPOTTER
TO ESCORT PEDESTRIANS
AROUND THE WORK AREA
BUSSTOP
MOVE BUS STOP 250' EAST.
KING COUNTY METRO
WILL BE CONTACTED AT
206-477-1150 FIVE DAYS IN ADVANCE
OF SCHEDULED DATE.
J02
ARRW-BRD
W20-1
RO
A
D
WO
R
K
AH
E
A
D
RIG
H
T
L
A
N
E
CL
O
S
E
D
AH
E
A
D
W20-5R
W4-2R
X'≥X'≥X'≥
W2
0
-
1
ROAD
WORK
AHEAD
X'≥
W2
0
-
1
ROAD
WORK
AHEAD
X'
≥
W2
0
-
1
ROAD
WORKAHEAD
X'
≥
W20-1
RO
A
D
WO
R
K
AH
E
A
D
X'≥
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Safaa Al Neema
(425) 398-6077
safaa.alneema@pse.com
21 OF 2411426 SE 169th St, Renton, WA 98055
0
11910045
09/04/2025
Puget Sound EnergyTraffic Control Supervisor:
Safaa Al Neema
Card No. IS 6 100072
Card Exp. 10/10/2028
Safaa.alneema@pse.com
(425)398-6077
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
WORK AREA
CHEVRONARROW BOARD
FLAGGER
UNIFORMEDPOLICE OFFICERPOLICE
STOP
POLE
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated,
if indicated use ADA compliant channelization.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours as
per jurisdictional requirements. (Generally between 9
a.m. and 4 p.m. on non-arterials and from 9 a.m. to 3
p.m. on arterials. If night time work is approved,
signaling and flaggers shall conform to WAC
296-155-305. Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
MFP26000225
P24
11
8
T
H
A
V
E
S
E
11
8
T
H
A
V
E
S
E
1414
12
12
12
12
12
12
12
12
12
SE PETROVITSKY RD
SE PETROVITSKY RD
11 11 14
BUSSTOP
THE CREW SHALL CEASE
WORK FOR A FLAGGER/SPOTTER
TO ESCORT PEDESTRIANS
AROUND THE WORK AREA
BUS
STOP
MOVE BUS STOP 250' EAST.
KING COUNTY METRO
WILL BE CONTACTED AT
206-477-1150 FIVE DAYS IN ADVANCE
OF SCHEDULED DATE.
P25
17 17
12
0
T
H
A
V
E
S
E
ARRW-BRD
W20-1
RO
A
D
WO
R
K
AH
E
A
D
RIG
H
T
L
A
N
E
CL
O
S
E
D
AH
E
A
D
W20-5R
W4-2R
X'≥X'≥X'≥
W2
0
-
1
ROAD
WORK
AHEAD
X'
≥
W2
0
-
1
ROAD
WORK
AHEAD
X'
≥
W20-1
RO
A
D
WO
R
K
AH
E
A
D
X'≥
W2
0
-
1
ROAD
WORK
AHEAD
X'
≥
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Safaa Al Neema
(425) 398-6077
safaa.alneema@pse.com
22 OF 2411426 SE 169th St, Renton, WA 98055
0
11910045
09/04/2025
Puget Sound EnergyTraffic Control Supervisor:
Safaa Al Neema
Card No. IS 6 100072
Card Exp. 10/10/2028
Safaa.alneema@pse.com
(425)398-6077
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
WORK AREA
CHEVRONARROW BOARD
FLAGGER
UNIFORMEDPOLICE OFFICERPOLICE
STOP
POLE
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated,
if indicated use ADA compliant channelization.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours as
per jurisdictional requirements. (Generally between 9
a.m. and 4 p.m. on non-arterials and from 9 a.m. to 3
p.m. on arterials. If night time work is approved,
signaling and flaggers shall conform to WAC
296-155-305. Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
MFP26000225
11
8
T
H
A
V
E
S
E
11
8
T
H
A
V
E
S
E
1414
12
12
12
12
12
12
12
12
12
SE PETROVITSKY RD
SE PETROVITSKY RD
11 11 14
BUSSTOP
THE CREW SHALL CEASE
WORK FOR A FLAGGER/SPOTTER
TO ESCORT PEDESTRIANS
AROUND THE WORK AREA
BUS
STOP
P25 P27
P26
17 17
12
0
T
H
A
V
E
S
E
ARRW-BRD
W20-1
RO
A
D
WO
R
K
AH
E
A
D
X'≥
W2
0
-
1
ROAD
WORKAHEAD
X'
≥
W2
0
-
1
ROAD
WORK
AHEAD
X'
≥
RI
G
H
T
L
A
N
E
CL
O
S
E
D
AH
E
A
D
W20-5R
W4-2R
X'≥X'≥
W20-1
RO
A
D
WO
R
K
AH
E
A
D
X'≥
W2
0
-
1
ROAD
WORK
AHEAD
X'
≥
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Safaa Al Neema
(425) 398-6077
safaa.alneema@pse.com
23 OF 2411426 SE 169th St, Renton, WA 98055
0
11910045
09/04/2025
Puget Sound EnergyTraffic Control Supervisor:
Safaa Al Neema
Card No. IS 6 100072
Card Exp. 10/10/2028
Safaa.alneema@pse.com
(425)398-6077
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
WORK AREA
CHEVRONARROW BOARD
FLAGGER
UNIFORMEDPOLICE OFFICERPOLICE
STOP
POLE
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated,
if indicated use ADA compliant channelization.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours as
per jurisdictional requirements. (Generally between 9
a.m. and 4 p.m. on non-arterials and from 9 a.m. to 3
p.m. on arterials. If night time work is approved,
signaling and flaggers shall conform to WAC
296-155-305. Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
MFP26000225
11
8
T
H
A
V
E
S
E
11
8
T
H
A
V
E
S
E
1414
12
12
12
12
12
12
12
12
12
SE PETROVITSKY RD
SE PETROVITSKY RD
11 11 14
BUS
STOP
THE CREW SHALL CEASE
WORK FOR A FLAGGER/SPOTTER
TO ESCORT PEDESTRIANS
AROUND THE WORK AREA
BUSSTOP
P26
17 17
12
0
T
H
A
V
E
S
E
W20-1
RO
A
D
WO
R
K
AH
E
A
D
RIG
H
T
L
A
N
E
CL
O
S
E
D
AH
E
A
D
W20-5R
W4-2R
X'≥X'≥X'≥
W2
0
-
1
ROADWORK
AHEAD
X'
≥
W20-1
RO
A
D
WO
R
K
AH
E
A
D
X'≥
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Safaa Al Neema
(425) 398-6077
safaa.alneema@pse.com
24 OF 2411426 SE 169th St, Renton, WA 98055
0
11910045
09/04/2025
Puget Sound EnergyTraffic Control Supervisor:
Safaa Al Neema
Card No. IS 6 100072
Card Exp. 10/10/2028
Safaa.alneema@pse.com
(425)398-6077
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
WORK AREA
CHEVRONARROW BOARD
FLAGGER
UNIFORMEDPOLICE OFFICERPOLICE
STOP
POLE
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated,
if indicated use ADA compliant channelization.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours as
per jurisdictional requirements. (Generally between 9
a.m. and 4 p.m. on non-arterials and from 9 a.m. to 3
p.m. on arterials. If night time work is approved,
signaling and flaggers shall conform to WAC
296-155-305. Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
MFP26000225
N
Vicinity Map
Thomas Guide Page 316744-166533
10
1
1
5
7
2
9
6
ARE TO BE INSTALLED, CROSS SECTION DETAILS OF THE TYPICAL EROSION
STRUCTURES, & SPECIAL REQUIREMENTS FOR WORK IN SENSITIVE AREAS.)
EROSION & SEDIMENT CONTROL REQUIREMENTS
NOTES DETAILING WHERE EROSION OR SEDIMENT CONTROL STRUCTURES
(LOCAL JURISDICTIONS MAY HAVE ADDITIONAL REQUIREMENTS INCLUDING
0150.3200 TECHNIQUES FOR TEMPORARY EROSION & SEDIMENT CONTROL
EROSION & SEDIMENT CONTROL SHALL BE PER PSE STANDARD PRACTICE
& ANY ADDITIONAL LOCAL JURISDICTION REQUIREMENTS.
FOREMAN (CHECK BOX WHEN COMPLETED)
PSE Equipment LOCKED/SECURED & Work Area left in CLEAN/SAFE Condition.
Grid, Cable, and Switch numbers INSTALLED & VERIFIED.
Field Changes RED-LINED on As-built.
Indicate correct FUSE SIZE on As-built & VERIFY proper PHASE.
Foreman's Signature _______________________________________________
Print Name ___________________________________ Date ______________
Material VERIFIED and CHANGES noted on Paperwork.
Total PRIMARY Cable noted on As-built.
Company ID#'s RECORDED in correct location on As-built.
Deviations noted on the As-built and their reason.
I certify that the work performed meets PSE's standards and procedures
and that all quality requirements are met.
No
No
No
Yes
Yes
Yes
"Flagging Required"
"Outages Required"
"Locates Required"
ROL-13 TWFDR 116 440O FT
336 TW RECONDUCTOR
GENERAL SPECIFICATIONS
Project Summary:
This project reconductors the feeder from the substation to recloser X12295. This will
eliminate/reduce vegetation outages and will prevent line slap.
Design Detail:
Start this project at pole with grid number 316744-166533 reconductor existing 336
ACSR to 336 ACSR tree wire. Reconductor this underbuilt distribution line. Contact
the appropriate Transmission engineer to coordinate efforts. Reconductor north to pole
with grid number 316757-166569. Continue the reconductor to the south along 116th
Ave SE.
At pole with grid number 316674-166567 (SK00387, ensure that this switch is fused at
100T and is shown correctly on our maps.
Continue this tree wire reconductor project south and west to poles with grid numbers
316524-166540 and 316514-166563. East along SE Petrovitsky Rd, continue this tree
wire reconductor project.
At pole with grid 316527-166665 relocate switch X3401 (65T)to this pole is possible.
End this reconductor east along SE Petrovitsky Rd at pole with grid number
316527-166678(X12295).This recloser is operated (NO) Normally Open in a static
environment.
Planning Budget Type: RRM
IDOT Score: 7.83
5 year average non-storm customer minute interruptions saved: 124,606
5 year average non-storm customer interruptions saved: 1,671
5 year average non -storm outages saved: 1
Infrastructure Impacts:
List units added by this project
Conductor: 336 ACSR tree wire
Circuit Ft: 4,400
Recloser: None
Switch: None
General
-All work is to be completed per PSE Standards & Practices. Copies of all PSE
Standards are available upon request.
-Work sites shall be kept clear of debris and all construction materials; equipment
and packing shall be removed daily.
-Return all unused and removed poles, transformers and hardware to PSE,
storeroom. All copper shall be coiled and returned the day it is removed from the
poles. Remove all unused pins and insulators.
-Return all streetlights, area lights and floodlights to Sumner yard.
Preconstruction
- Notify appropriate city, County or DOT authorities 48 to 72 hours, or as required by
permitting agency, in advance of starting work in Right-of-way involving a Permit.
- All system switching shall be approved by System Operations (425-882-4652) a
minimum of 48 hours in advance.
- Notify customers of all outages 48 hours in advance.
Work Drawings & Documents
- Field design changes shall be approved by PSE Project Manager or Engineer.
- Mark all field changes, equipment ID numbers and Underground cable information in
red on Foreman's copy of worksketch.
- Return one Foreman's copy of worksketch to Project Manager at completion of job.
- When permits are required, a copy shall be available on work site at all times.
Safety
- Refer to PSE standards 6275.3000 and 6275.6000 for system ground requirements.
- Refer to PSE standards 6275.9050 for personal protective grounding requirements.
- Refer to PSE standards 6275.9150 for vehicle grounding and barricading
requirements.
- Proper line clearances shall be taken at the beginning, and released at the end, of
each work day, or as otherwise instructed by the System Operator.
- Provide signs, barricades, and traffic control in conformance with permit regulations.
- Utilize flagging and other vehicle traffic control as necessary and in conformance with
local traffic regulations.
- Maintain traffic flow as required by permitting agency.
Erosion & Sediment Control
-Refer to PSE standards 0150.3200 for minimum requirements.
-Comply with all requirements of permitting agency.
-Installed erosion & sediment devices shall be maintained until vegetation has been
re-established or disturbed soil has been otherwise permanently stabilized.
Joint Facilities
-Coordinate with Communication Companies for transfers.
OVERHEAD CONSTRUCTION
Poles & Structures
-Poles are to be installed or relocated as staked. Unless otherwise noted, all pole
location measurements are from the center of the pole.
-All new poles set shall be the class indicated on the sketch, or better. Do not set a
lower class pole than specified.
-Install ground plate assembly on all new poles. Install Switch Ground Assembly per
standard specification 6014.1000 at new gang operated switch locations.
-Install grid numbers on all new and existing poles as shown on sketch.
-Straighten existing poles as indicated or as necessary.
-Treat all field-drilled poles with copper napthenate wood preservative.
-Remove old poles after communication companies have transferred off and return to
PSE storeroom. Fill and crown pole holes and restore area similar to adjacent
landscaping.
Conductors & Equipment
- Transfer all overhead and underground primary, secondary and service conductors
and guys to new poles set, unless otherwise indicated on this sketch.
- Transfer existing transformers to new poles unless otherwise indicated on this sketch.
- Use stirrups to connect all overhead and underground primary taps, and all
transformers. Install at all sites being worked within the scope of the project where
they are currently missing.
- Use 397 AAC and Ampact connectors for all bare conductor feeder jumpers and 600
amp switch jumpers. Install tree wire conductor for jumpers on all poles that are
double deadended with tree wire.
- Apply grit inhibitor on all Ampact, stirrup, and dead-end connections.
- Connect primary taps and transformers to same phase as existing unless otherwise
shown on the drawing.
- All neutral connections to be made with solid compression connectors. Connect all
pole grounds to common neutral.
- Use Load-interrupter cutouts (with arc shields) on all primary overhead and
underground taps with fused protection above 40T.
- Install Wildlife Protectors on all transformers.
Owner / Developer Contact Info
officeATTN:
N/A
N/A
N/A
N/A N/APHONE
CABLE TV
11910045 101157296
583078997
108162039
PROJECT PHASE
PWR
NOTIF#ORDER#
Superior
UG Expense
Removal
OH Expense 593262366
594163784
UG Expense
OH Expense
E-Mail:
Cell Phone:
Project Manager Contact Information:
Manager:AYLA SILER
425.456.2757
ayla.siler@pse.com
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
AYLA SILER 425.456.2757 N/A
A. CRAWFORD 425.424.7982 N/A
N/A N/A N/A
CDB/APM 928.848.7369 06-24-24
RW-132063 RENTON
ROL-13 TWFDR 116 4400FT
Rel-Upgr - Tree Wire
11426 SE 169TH ST, RENTON, WA 98055
DESIGNED BY ACTALENT SERVICES
N/A N/A
N/A N/A
AS NOTED 1/7
N/A N/A N/A N/A
NW 33-23-05 N/A 214-084
2305E130 2305E136 2305E130 ROL-13
CENTURYLINK
N/A
N/A
COMCAST
N/A
N/A
RENTON SCHOOL
N/A
N/A
PSE FIBER
N/A
N/A
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL 811 TWO BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
LEGEND
CONDUIT RISER
OVERHEAD TRANSFORMER
JUNCTION VAULT/JUNCTION BOX
NEW CONDUCTOR AND OR TRENCH LINE
DISCONNECT - FUSED
PULL VAULT OR SPLICE VAULT
EXISTING POLE
DOWN GUY
DISCONNECT - UNFUSED
NEW POLE
PADMOUNT TRANSFORMER
SECONDARY HANDHOLE
EXISTING CONDUCTOR TO BE REMOVED
OR ABANDONED
STREET LIGHT
TOTAL UNDERGROUND TRANSFORMER
ENERGY CUSTOMER DEMAND POINT
OR
OR
OR
OVERHEAD JUMPER CONNECTION
ARE TO BE INSTALLED, CROSS SECTION DETAILS OF THE TYPICAL EROSION
STRUCTURES, & SPECIAL REQUIREMENTS FOR WORK IN SENSITIVE AREAS.)
EROSION & SEDIMENT CONTROL REQUIREMENTS
NOTES DETAILING WHERE EROSION OR SEDIMENT CONTROL STRUCTURES
(LOCAL JURISDICTIONS MAY HAVE ADDITIONAL REQUIREMENTS INCLUDING
0150.3200 TECHNIQUES FOR TEMPORARY EROSION & SEDIMENT CONTROL
EROSION & SEDIMENT CONTROL SHALL BE PER PSE STANDARD PRACTICE
& ANY ADDITIONAL LOCAL JURISDICTION REQUIREMENTS.
UTILITY POLE EROSION CONTROL DETAIL
TOP VIEW
DRY DRAINAGE DITCH or DRY VEGETATED SITE
SLOPE
Place gravel bags for
Sediment Trap
Place straw mulch
on disturbed areaExcavated or
Augered Hole
Pole
SLOPE
Not to scale Drainage ditches or Dry vegetated sites
INSTALL VISE GRIP INSULATORS w/ NYLON JAW
INSERTS WITH THE PROJECT AREA
6/13/2025425.559.5712
MFP26000225
RESTORATION PER CITY OF RENTON STANDARDS
This permit is for Major construction work in the ROW and will be billed at an additional
$158/HR for inspections. After hours and weekend work will be billed at $175/HR
10
1
1
5
7
2
9
6
SCALE: 1" = 50'
OVERHEAD CIRCUIT MAP (AFTER)OVERHEAD CIRCUIT MAP (BEFORE)
SCALE: 6" = 1 MILE
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
AYLA SILER 425.456.2757 N/A
A. CRAWFORD 425.424.7982 N/A
N/A N/A N/A
CDB/APM 928.848.7369 06-24-24
RW-132063 RENTON
ROL-13 TWFDR 116 4400FT
Rel-Upgr - Tree Wire
11426 SE 169TH ST, RENTON, WA 98055
DESIGNED BY ACTALENT SERVICES
N/A N/A
N/A N/A
AS NOTED 2/7
N/A N/A N/A N/A
NW 33-23-05 N/A 214-084
2305E130 2305E136 2305E130 ROL-13
CENTURYLINK
N/A
N/A
COMCAST
N/A
N/A
RENTON SCHOOL
N/A
N/A
PSE FIBER
N/A
N/A
25T
X92693
SB
X92692
25T
T92694
100T
X92695
100T
T92696
40T
X92698
40T
T92699
100T
T92700
100T
T85499
40T
X92703
6/13/2025425.559.5712
MFP26000225
11
6
t
h
A
V
E
.
S
E
SE 169th ST.
316744-166533
25kVA 120/240V
316744-166545
T85159
100' 336.4 TW
316744-166555
50kVA 120/240
155' 336.4 TW
316743-166569
T1/18
SK00596 100T
X92692 100T
316757-166569
2x37.5kVA
1x50kVA 120/240V
WYE/DELTA
T76945 25T
22
3
'
3
3
6
.
4
T
W
20
9
'
3
3
6
.
4
T
W
20
1
'
3
3
6
.
4
T
W
316721-166568
100kVA 120/240A
316706-166568
SK00553 25T
SK00352 100T
T84857 25T
X92695 100T
316685-166567
20
0
'
3
3
6
.
4
T
W
11
4
'
3
3
6
.
4
T
W
ROL
13
RO
L
13
RO
L
13
RO
L
13
ABCN
CB
A
CB
A
CBAN
CBAN
316720-166588
2 x 75kVA
167kVA 120/240V
WYE/DELTA
#
2
A
C
S
R
CBA
316694-166571
UNKNOWN 100T
X92697 100T
BØADD558
CBAN
CBAN
10
1
1
5
7
2
9
6
MATCHLINE SEE SHEET 4
AA
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
AYLA SILER 425.456.2757 N/A
A. CRAWFORD 425.424.7982 N/A
N/A N/A N/A
CDB/APM 928.848.7369 06-24-24
RW-132063 RENTON
ROL-13 TWFDR 116 4400FT
Rel-Upgr - Tree Wire
11426 SE 169TH ST, RENTON, WA 98055
DESIGNED BY ACTALENT SERVICES
N/A N/A
N/A N/A
AS NOTED 3/7
N/A N/A N/A N/A
NW 33-23-05 N/A 214-084
2305E130 2305E136 2305E130 ROL-13
CENTURYLINK
N/A
N/A
COMCAST
N/A
N/A
RENTON SCHOOL
N/A
N/A
PSE FIBER
N/A
N/A
SITE PLAN
SCALE: 1" = 50'
WIRE STRINGING PRIMARY & SECONDARY
Location
Pri Sec
Wire Size & Type
Quantity
Length
(Per conductor)Total UnitsFromTo
P02 P04 X 336 TW 3 255 765 2-75x765'
P05 P18 X 336 TW 3 2526 7578 2-75x7578'
P19 P27 X 336 TW 3 1400 4200 2-75x4200'
WIRE REMOVAL TABLE
Location
Wire Size & Type Quantity
Length
(per
conductor)RemarksFromTo
P02 P04 336.4 ACSR 3 255
P05 P18 336.4 ACSR 3 2526
P19 P27 336.4 ACSR 3 1400
336.4 ACSR = 12,543' Removed
POLE RETIREMENT TABLE TEMP TRANSFERS ST. LIGHT TRANSFERS
SITE
#
POLE DATA POLE
TEL TV FIBER TRAN RMVD ID NUMBER
GRID #HEIGHT CLASS YEAR TOPPED RMVD
P06 316721-166568 45 2 1969
P08 316685-166567 45 3 1986
POLE TABLE (NEW)
Site
#
Pole Data
Grid #Height Class Year Remarks / Location Ref.
P06 316721-166568 45 H2
P08 316685-166567 45 H2
SITE SPECIFIC NOTES:
THREE PHASE BEGINS AT P02, RECONDUCTORING TO BEGIN THERE AS WELL.
P01 316744-166533 (1974, 80' CL-1, ∠0⁰, AVG SPAN 110')
-EXIST POLE TO REMAIN
-EXIST TRANSMISSION WITH DIST. UNDERBUILD
-TREE TRIMMING REQUIRED
P02 316744-166545 (1967, 45' CL-1, ∠0⁰, AVG SPAN 105')
-EXIST POLE TO REMAIN
-EXIST SOLID BLADES TO REMAIN
-TREE TRIMMING REQUIRED
-REPLACE (2) BELL DE WITH NEW DE (6016.100,DEDA71A)2-21X2
P03 316744-166555 (2013, 80' CL-1, ∠0⁰, AVG SPAN 128')
-EXIST POLE TO REMAIN
-EXIST TRANSMISSION WITH DIST. UNDERBUILD
-EXIST CROSSARM TO REMAIN
-REMOVE EXISTING C-NECK INSULATORS (3)
-INSTALL NEW VISE-GRIP INSULATORS (3)(6015.1000, INDCSA)2-21X3
P04 316743-166569 (1974, 80' CL-1, ∠0⁰, AVG SPAN 216')
-EXIST POLE 6.6' FROM FOG
-EXIST POLE VIOLATES CZ
-EXIST POLE TO REMAIN
-EXIST TRANSMISSION WITH DIST. UNDERBUILD
-EXIST CROSSARM TO REMAIN
-REMOVE EXISTING C-NECK INSULATORS (3)
-INSTALL NEW VISE-GRIP INSULATORS (3)(6015.1000, INDCSA)2-21X3
-RETIRE SW#SK00596
-INSTALL X92692
P05 316757-166569 (2020, 50' CL-H2, ∠0⁰, AVG SPAN 223')
-INSTALL 24" PLATE DISTRIBUTION ANCHOR 5' NORTH
FROM EXISTING DISTRIBUTION ANCHOR.(6012.100,ANDP24)2-10A
-INSTALL DOUBLE 7/16" DISTRIBUTION DOWN GUY TO (6013.1000,GYDD7SA
NEW ANCHOR.
-EXIST POLE 12.3' FROM FOG
-EXIST POLE TO REMAIN
-EXIST FUSE(S) TO REMAIN
-EXIST SW# T76045
-REMOVE DISTRIBUTION GUYING
P06 316721-166568 (1969, 45' CL-2, ∠0⁰, AVG SPAN 205')
-EXIST POLE 6.5' FROM FOG
-EXIST POLE VIOLATES CZ
-REPLACE EXIST POLE WITH 45' CLH2 (6010.1000, PD45H2)2-69
SET POLE 4' (E) OF EXISTING, AT LEAST 10' FROM FOG
WRAP POLE (9999220)
TAPE (9999235)
-INSTALL NEW 3Ø SINGLE WINGARM (6033.4012, TASW313)
INSTALL 11' CROSSARM
INSTALL (3) VISE-GRIP INSULATORS (6015.1000, INDCSA)
INSTALL PORC INS FOR PRIMARY NEUT (6015.1000, INDASA)
-TRANSFER EXIST 100kVA 7-120/240V XFMR 2-71X0
INSTALL LB C/O; TAP CØ (6022.1000, DLS115L)
INSTALL 40T FUSE (3412500)
-INSTALL 10” SINGLE HELIX ANCHOR (LL=10') (NE)(6012.1000, ANDH1)
INSTALL 3/8” SEC DOWN GUY (6013.0100, GYD3SAN)
-TRANSFER OH SVC, ____TPLX (WSW) SERVING ADDRESS 16917, ACTUAL____'
-TRANSFER OH SVC, ____(2)TPLX (SW) SERVING ADDRESS 16935, ACTUAL____'
-TOP POLE 1' ABOVE COMMS, REMOVE AFTER COMMS TRANSFER 2-129
P07 316706-166568 (2013, 95' CLH1, ∠0⁰, AVG SPAN 201')
-EXIST POLE 6.3' FROM FOG
-EXIST POLE VIOLATES CZ
-EXIST POLE TO REMAIN
-EXIST TRANSMISSION WITH DIST. UNDERBUILD
-EXIST CROSSARM TO REMAIN
-REMOVE EXISTING C-NECK INSULATORS (3)
-INSTALL NEW VISE-GRIP INSULATORS (3)(6015.1000, INDCSA)2-21X3
-EXIST FUSES TO REMAIN INSTALL PRIMARY NUET
-RETIRE SW#SK50053
-RETIRE SW#SK00352
-ADD SW# X92694
-ADD SW# X92695
New pole at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER TRANSFER
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
P06
316721-166568
100
P08 316685-166567 [FIELD 316685-166576] (1986, 45' CL3, ∠0⁰, AVG SPAN 157')
-EXIST POLE 6.4' FROM FOG
-EXIST POLE VIOLATES CZ
-REPLACE EXIST POLE WITH 45' CLH2 (6010.1000, PD45H2)2-69
SET POLE 4' (E) OF EXISTING, AT LEAST 10' FROM FOG
WRAP POLE (9999220)
TAPE (9999235)
-INSTALL NEW 3Ø SINGLE WINGARM (6033.4012, TASW313)
INSTALL 11' CROSSARM
INSTALL (3) VISE-GRIP INSULATORS (6015.1000, INDCSA)
INSTALL PORC INS FOR PRIMARY NEUT (6015.1000, INDASA)
-INSTALL SPAN GUY (NNE) TO 316694-166571
INSTALL 3/8" PRI SPAN GUY (6013.0170, GYD3OW)
-INSTALL 24" PLATE ANCHOR (LL=15') (S), BACKFILL____(6012.1000, ANDP24)2-10A
INSTALL 7/16" PRI DOWN GUY (6013.0100, GYD7SA)
-INSTALL GRID NUMBER 316685-166567
-TOP POLE 1' ABOVE COMMS, REMOVE AFTER COMMS TRANSFER 2-129
6/13/2025425.559.5712
MFP26000225
11
6
t
h
A
V
E
.
S
E
316674-166567
SK00387 100T
X92696 100T
14
3
'
3
3
6
.
4
T
W
316660-166567
50kVA 120/240V
UNKOWN 40T
X92698 40T
316634-166566
SK00598 40T
X92699 40T
316620-166566
UNKNOWN 100T
X92700 100T
22
1
'
3
3
6
.
4
T
W
15
2
'
3
3
6
.
4
T
W
15
2
'
3
3
6
.
4
T
W
316607-166565
37.5kVA 120/240V
316584-16565
15kVA 120/240V
15
2
'
3
3
6
.
4
T
W
RO
L
13
RO
L
13
RO
L
13
AØ33673
BØ33674
CØ33675
316657-166560
BØ
#4ACSR
AØ32904
BØ32905
CØ32906
AØ26822
BØ26823
CØ26824
CBAN
CBAN
CBAN
CBAN
CBAN
CBAN
CBAN
J01
316674-166568
CONST VAULT
316674-166568
CONDUIT DIAGRAM (PROPOSED)
SCALE: N.T.S.
316674-166567
X92696
NEW 1-4"
CONST VAULT
316674-166568
316674-166567
X92696
EKB975
EKB976
EKB977
1/0 JKT
CABLE DIAGRAM (PROPOSED)
SCALE: N.T.S.
10
1
1
5
7
2
9
6
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
AYLA SILER 425.456.2757 N/A
A. CRAWFORD 425.424.7982 N/A
N/A N/A N/A
CDB/APM 928.848.7369 06-24-24
RW-132063 RENTON
ROL-13 TWFDR 116 4400FT
Rel-Upgr - Tree Wire
11426 SE 169TH ST, RENTON, WA 98055
DESIGNED BY ACTALENT SERVICES
N/A N/A
N/A N/A
AS NOTED 4/7
N/A N/A N/A N/A
NW 33-23-05 N/A 214-084
2305E130 2305E136 2305E130 ROL-13
CENTURYLINK
N/A
N/A
COMCAST
N/A
N/A
RENTON SCHOOL
N/A
N/A
PSE FIBER
N/A
N/A
SITE PLAN
SCALE: 1" = 50'
POLE RETIREMENT TABLE TEMP TRANSFERS ST. LIGHT TRANSFERS
SITE
#
POLE DATA POLE
TEL TV FIBER TRAN RMVD ID NUMBER
GRID #HEIGHT CLASS YEAR TOPPED RMVD
P12 316620-166566 40 5 1967
P13 316607-166565 40 1 1967
POLE TABLE (NEW)
Site
#
Pole Data
Grid #Height Class Year Remarks / Location Ref.
P12 316620-166566 45 1
P13 316607-166565 45 1
New pole at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER TRANSFER
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
P13
316607-166565
37.5
MATCHLINE A SEE SHEET 3
AA
MATCHLINE B SEE UPPER RIGHT
BB
P09 316674-166567 (2013, 80' CL1, ∠0⁰, AVG SPAN 129')
-EXIST POLE 6.5' FROM FOG
-EXIST POLE VIOLATES CZ
-EXIST POLE TO REMAIN
-EXIST TRANSMISSION WITH DIST. UNDERBUILD
-EXIST CROSSARM TO REMAIN
-REMOVE EXISTING C-NECK INSULATORS (3)
-INSTALL NEW VISE-GRIP INSULATORS (3)(6015.1000, INDCSA)2-21X3
-INSTALL NEUTRAL IN COMMON POSITION
-REMOVE EXISTING 200A TERMINATION
-INSTALL 3Ø 200A TERM, OH TO UG (6043.1000, TSU3C1F)2-71N,2-57X3
INSTALL LB C/O'S & 40T FUSES (93412500)
INSTALL (3) LB C/O COVERS (9999530)
INSTALL (3) LA COVERS (9998115)
-ACTUAL 3Ø____UG PRI ADDED L=____BATCH YEAR____2-55X___2-55X___
-ACTUAL TRENCH L=_____2-45X___2-36X___
-REMOVE SWITCH NUMBER SK00387
P10 316660-166567 (2000, 45' CL1, ∠0⁰, AVG SPAN 182')
-EXIST POLE 10.9' FROM CURB FACE (NO FOG)
-EXIST POLE TO REMAIN
-EXIST CROSSARM TO REMAIN
-REMOVE EXISTING C-NECK INSULATORS (3)
-INSTALL NEW VISE-GRIP INSULATORS (3)(6015.1000, INDCSA)2-21X3
-EXIST FUSE TO REMAIN
-INSTALL PORC INST FOR PRIMARY NUET
-INSTALL NEW SW# X92698
-TREE TRIMMING REQUIRED
P11 316634-166566 (1975, 75' CL1, ∠0⁰, AVG SPAN 187')
-EXIST POLE 14.1' FROM FOG
-EXIST POLE TO REMAIN
-EXIST TRANSMISSION WITH DIST. UNDERBUILD
-EXIST CROSSARM TO REMAIN
-REMOVE EXISTING C-NECK INSULATORS (3)
-INSTALL NEW VISE-GRIP INSULATORS (3)(6015.1000, INDCSA)2-21X3
-INSTALL PORC INS FOR PRIMARY NEUT
-INSTALL NEW SW# X92699
Primary Cable & Conduit Table (Foreman to Complete)
LOCATION CONDUIT PRIMARY CABLE
QTY OF LUBE (gal.)AS BUILT INFORMATION
From To Size
(in)
Qty
Design
Length
(ft)
Actual
Length
(ft)
TYPE BENDS PULL
(lbs)
PULL
Rev
(lbs)
Cable
Size
Design
Length
(ft)
Actual
Length
(ft)
CABLE NUMBERS MANUFACTURING INFORMATION FOR FEEDER CABLE ONLY
Check applicable box
DB120 HDPE SCH 80 90°45°22°11°A B C Manufacturer Compound Year Tape CN #4/0 NEU Design As Built Actual Amount Installed
(Conduit & Cable)
P09 J01 4"1 45 X X 310 343 750 1/0 JKT 105'-0"EKB975 EKB976 EKB977
P12 316620-166566 (1967, 40' CL5, ∠0⁰, AVG SPAN 152')
-EXIST POLE 15.5' FROM FOG
-REPLACE EXIST POLE (S) 2' WITH 45' CL1 (6010.1000, PD451)2-69
-INSTALL NEW 3Ø PRIMARY NEUTRAL SINGLE ARM (6033.3012, TAP313)
INSTALL 11' CROSSARM
-INSTALL (3) VICE-GRIP INSULATORS (6015.1000, INDCSA)
-INSTALL PORC INS PRIMARY NEUT (6015.1000, INDASA)
-INSTALL 3Ø 200A TERM (6043.1000, TSU3L1F)2-71N,2-57X3
INSTALL (3) L.I. C/O
FUSE AT 100T
SW# T92697
-TRANSFER 3Ø 1/0 UG PRI; EXTEND AS REQ'D
-ACTUAL 1/0 UG PRI ADDED L=______ BATCH YEAR______2-55X____2-55X____
-ACTUAL TRENCH L=______2-36X____2-45_____
-TRANSFER OH SEC,____TPLX (N), ATTACHED TO P11 (SPAN=152') ACTUAL____'
-TRANSFER OH SEC,____TPLX (S), ATTACHED TO P13 (SPAN=152') ACTUAL____'
-TRANSFER OH SVC, ____TPLX (NE) SERVING ADDRESS 17236, ACTUAL____'
-TRANSFER OH SVC, ____TPLX (SE) SERVING ADDRESS 17240, ACTUAL____'
-TOP POLE 1' ABOVE COMMS, REMOVE AFTER COMMS TRANSFER 2-129
P13 316607-166565 (1967, 40' CL1, ∠0⁰, AVG SPAN 152')
-EXIST POLE 15.9' FROM FOG 2-69
-REPLACE EXIST POLE (S) 2' WITH 45' CL1 (6010.1000, PD451)
-INSTALL NEW 3Ø PRIMARY NEUTRAL SINGLE ARM (6033.3012, TAP313)
INSTALL 11' CROSSARM
-INSTALL (3) VISE-GRIP INSULATORS (6015.1000,INDCSA)
-INSTALL PORC INS PRIMARY NEUT (6015.1000,INDASA)
-TRANSFER EXIST 37.5kVA 7-120/240V XFMR 2-71XO
REPL LB C/O, 15T FUSE, & STIRRUP; TAP BØ
-TRANSFER OH SEC,____TPLX (N), ATTACHED TO P12 (SPAN=152') ACTUAL____'
-TRANSFER OH SEC,____TPLX (S), ATTACHED TO P14 (SPAN=152') ACTUAL____'
-TRANSFER UG SVC, ____TPLX (E) SERVING ADDRESS 17248 2-54AX____
ACTUAL____', TRENCH____'2-36X____2-45X____
-TRANSFER UG SVC, ____TPLX (E) SERVING ADDRESS 17314 2-54AX____
ACTUAL____', TRENCH____'2-36X____2-45X____
-TOP POLE 1' ABOVE COMMS, REMOVE AFTER COMMS TRANSFER 2-129
P14 316584-166565 (2013, 95' CLH3, ∠0⁰, AVG SPAN 189')
-EXIST POLE 16.4' FROM FOG
-EXIST POLE TO REMAIN
-EXIST TRANSMISSION WITH DIST. UNDERBUILD
-EXIST CROSSARM TO REMAIN
-REMOVE EXISTING PRIMARY DEADENDS (6)2-21X3
-REMOVE EXISTING C-NECK INSULATORS (6)2-21X3
-INSTALL NEW VISE-GRIP INSULATORS (6)(6015.1000, INDCSA)
TRENCH DETAIL
2-57X3
6/13/2025425.559.5712
MFP26000225
11
6
t
h
A
V
E
.
S
E
11
6
t
h
A
V
E
.
S
E
316569-166565
T85499 100T
316559-166564
25kVA 120/240V
22
6
'
3
3
6
.
4
T
W
71
'
3
3
6
.
4
T
W
316528-166563
25kVA 120/240V
316514-166563
X372
NO
28
1
'
3
3
6
.
4
T
W
18
1
'
3
3
6
.
4
T
W
316524-166540
X440
NO
316522-166558
174' 336.4 TW
316525-166581
X542
205' 336.4 TW
FLYING TAPS
161' 336.4 TW
316501-166562
25kVA 120/240V
RO
L
13
RO
L
13
RO
L
13
ROL
13
AØ32901
BØ32902
CØ32903
AB
C
Ø
CØ
#2
A
C
S
R
316528-166562
25kVA 120/240V
CBAN
CBAN
CBA
CBA
SE PETROVITSKY RD.
CB
A
CB
A
ROL
13
316541-166558
T92697 100T
10
1
1
5
7
2
9
6
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
AYLA SILER 425.456.2757 N/A
A. CRAWFORD 425.424.7982 N/A
N/A N/A N/A
CDB/APM 928.848.7369 06-24-24
RW-132063 RENTON
ROL-13 TWFDR 116 4400FT
Rel-Upgr - Tree Wire
11426 SE 169TH ST, RENTON, WA 98055
DESIGNED BY ACTALENT SERVICES
N/A N/A
N/A N/A
AS NOTED 5/7
N/A N/A N/A N/A
NW 33-23-05 N/A 214-084
2305E130 2305E136 2305E130 ROL-13
CENTURYLINK
N/A
N/A
COMCAST
N/A
N/A
RENTON SCHOOL
N/A
N/A
PSE FIBER
N/A
N/A
SITE PLAN
SCALE: 1" = 50'
MATCHLINE B SEE LOWER LEFT
BB
MA
T
C
H
L
I
N
E
C
SE
E
U
P
P
E
R
R
I
G
H
T
C
C
P15 316569-166565 (1967, 45' CL1, ∠0⁰, AVG SPAN 149')
-EXIST POLE 24.7' FROM FOG
-REPLACE EXIST POLE (S) 2' WITH 55' CL1 (6010.1000, PD551)2-69
-INSTALL NEW 3Ø PRIMARY NEUTRAL SINGLE ARM (6033.3012, TAP313)
INSTALL 11' CROSSARM
INSTALL (3) VICE-GRIP INSULATOR (6015.1000, INDCSA)
INSTALL PORC INS FOR PRIMARY NEUT (6015.1000, INDASA)
-INSTALL 3Ø 200A TERM (6043.1000, TSU3L1F)2-71N,2-57X3
INSTALL (3) L.I. C/O
FUSE AT 100T
SW# T85499
-TRANSFER 3Ø 1/0 UG PRI; EXTEND AS REQ'D
-ACTUAL 1/0 UG PRI ADDED L=______ BATCH YEAR______2-55X___2-55X___
-ACTUAL TRENCH L=______2-45X___2-36X___
-TRANSFER OH SEC,____TPLX (S), ATTACHED TO P16 (SPAN=71') ACTUAL____'
-TOP POLE 1' ABOVE COMMS, REMOVE AFTER COMMS TRANSFER 2-129
P16 316559-166564 (1985, 85' CLH1, ∠0⁰, AVG SPAN 176')
-EXIST POLE 25.8' FROM FOG
-EXIST POLE TO REMAIN
-EXIST TRANSMISSION WITH DIST. UNDERBUILD
-EXIST CROSSARM TO REMAIN
-REMOVE EXISTING C-NECK INSULATORS (3)
-INSTALL NEW VISE-GRIP INSULATORS (3)(6015.1000, INDCSA)2-21X3
P17 316528-166563 (1979, 80' CL1, ∠0⁰, AVG SPAN 231')
-EXIST POLE 11.2' FROM FOG
-EXIST POLE TO REMAIN
-EXIST TRANSMISSION WITH DIST. UNDERBUILD
-EXIST CROSSARM TO REMAIN
-INSTALL UNDERBUILD DBL DE
-REMOVE EXISTING PRIMARY DEADENDS (6)
-REMOVE EXISTING C-NECK INSULATORS (6)
-INSTALL NEW VISE-GRIP INSULATORS (6)(6015.1000, INDCSA)2-21X3
-INSTALL NEW PRIMARY DEADENDS (6)(6016.1000, DEDA71A)2-21X3
FLYING TAPS
INSTALL NEW “Y” FLYING TAPS ON SPAN BETWEEN P17 AND P18 OVER`2-21X3
SPAN BETWEEN P20 AND P21 (6099.9999, 2368300, [18]); (6099.9999, 2368200, [6])
P18 316514-166563 (1978, 65' CL1, ∠0⁰, AVG SPAN 160')
-EXIST POLE 16.4' FROM FOG
-EXIST POLE TO REMAIN
-REMOVE EXISTING PRIMARY DEADENDS (6)
-INSTALL NEW PRIMARY DEADENDS (6)(6016.1000, DEDA71A)2-21X3
P19 316524-166540 [FIELD 316514-166557] (1985, 45' CL1, ∠0⁰, AVG SPAN 165')
-EXIST POLE 8.7' FROM CURB FACE (NO FOG)
-EXIST POLE VIOLATES CZ
-EXIST POLE TO REMAIN
-REMOVE EXISTING GRID NUMBER
-INSTALL NEW GRID NUMBER 316524-166540
-INSTALL NEW PRIMARY DEADENDS (6)(6016.1000, DEDA71A)2-21X3
P20 316522-166558 [MISSING] (1984, 50' CL1, ∠0⁰, AVG SPAN 190')
-EXIST POLE 6.0' FROM FOG
-EXIST POLE VIOLATES CZ
-EXIST POLE TO REMAIN
-REMOVE EXISTING C-NECK INSULATORS (6)
-INSTALL NEW VISE-GRIP INSULATORS (6)(6015.1000, INDCSA)2-21X3
-INSTALL NEW GRID NUMBER 316522-166558
P21 316525-166581 (1982, 50' CL2, ∠0⁰, AVG SPAN 183')
-EXIST POLE 7.2' FROM CURB FACE (NO FOG)
-EXIST POLE VIOLATES CZ
-REPLACE EXIST POLE WITH 50' CLH2 (6010.1000, PD50H2)2-69
SET POLE IN SAME HOLE
POLE WILL REQUIRE VARIANCE APPLICATION (RENTON)
WRAP POLE (9999222)
TAPE (9999235)
-INSTALL 3Ø TAN PTP (6033.1012, TAN313)
INSTALL STANDARD 9' ARM
INSTALL (2) NEUT DEADENDS (6016.1000, DEDR4PS)
-INSTALL NEW VICE-GRIP INSULATORS (3)(6015.1000, INDCSA)
-INSTALL 1Ø ARM-MOUNTED TAP (CØ) NO C/O (6031.5060, FR13RDE)2-71N
USE 12KV INSULATOR (9389100)
-INSTALL (3) INLINE DEADENDS (6016.1000, DEDA7L1)
-TRANSFER 600A 3Ø UNITIZED GOPT (6022.2000 FIG 3, DLSG15)2-72O
-TRANSFER OH SEC,____TPLX (N), ATTACHED TO 316528-166562 (80') ACTUAL____'
-TRANSFER OH SEC,____TPLX (E), ATTACHED TO P22 (SPAN=161') ACTUAL____'
-TRANSFER OH SVC, ____TPLX (SE) SERVING ADDRESS 11615, ACTUAL____'
-TRANSFER STREETLIGHT 2-302
-TOP POLE 1' ABOVE COMMS, REMOVE AFTER COMMS TRANSFER 2-129
New pole at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER TRANSFER
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
P15
316569-166565
15
POLE RETIREMENT TABLE TEMP TRANSFERS ST. LIGHT TRANSFERS
SITE
#
POLE DATA POLE
TEL TV FIBER TRAN RMVD ID NUMBER
GRID #HEIGHT CLASS YEAR TOPPED RMVD
P15 316569-166565 45 1 1967
P21 316525-166581 50 2 1982
POLE TABLE (NEW)
Site
#
Pole Data
Grid #Height Class Year Remarks / Location Ref.
P15 316569-166565 45 1
P21 316525-166581 50 H2
6/13/2025425.559.5712
MFP26000225
SE PETROVITSKY RD.
11
8
t
h
A
V
E
.
S
E
12
0
t
h
A
V
E
.
S
E
SE 176th ST.
11
7
t
h
A
V
E
.
S
E
316524-166596
UNKNOWN 40T
X92702 40T
161' 336.4 TW
316526-166629
T81079 100T379' 336.4 TW
210' 336.4 TW
150' 336.4 TW
316526-166650
15kVA 120/240
316527-166665
X92704 100T
316533-166665
T95142 65T
78
'
#
2
A
C
S
R
316527-166678
X12295121' 336.4 TW
316528-166691
ROL
13
ROL
13
BØ
#2
A
C
S
R
AØ33806
BØ33807
CØ33808
CB
A
CB
A
CB
A
CB
A
J02
ABC
CONST VAULT
316674-166568
CONDUIT DIAGRAM (PROPOSED)
SCALE: N.T.S.
316526-166629
T81079 100T
NEW 1-4"
EKB978
EKB979
EKB980
1/0 JKT
CABLE DIAGRAM (PROPOSED)
SCALE: N.T.S.
CONST VAULT
316674-166568
316526-166629
T81079 100T
10
1
1
5
7
2
9
6
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
AYLA SILER 425.456.2757 N/A
A. CRAWFORD 425.424.7982 N/A
N/A N/A N/A
CDB/APM 928.848.7369 06-24-24
RW-132063 RENTON
ROL-13 TWFDR 116 4400FT
Rel-Upgr - Tree Wire
11426 SE 169TH ST, RENTON, WA 98055
DESIGNED BY ACTALENT SERVICES
N/A N/A
N/A N/A
AS NOTED 6/7
N/A N/A N/A N/A
NW 33-23-05 N/A 214-084
2305E130 2305E136 2305E130 ROL-13
CENTURYLINK
N/A
N/A
COMCAST
N/A
N/A
RENTON SCHOOL
N/A
N/A
PSE FIBER
N/A
N/A
MA
T
C
H
L
I
N
E
C
SE
E
L
O
W
E
R
L
E
F
T
C
C
P25 316527-166665 (1985, 45' CL1, ∠0⁰, AVG SPAN 136')
-EXIST POLE 9.9' FROM CURB FACE (NO FOG)
-EXIST POLE VIOLATES CZ
-EXIST POLE TO REMAIN
-EXISTING ARM TO REMAIN
-REMOVE EXISTING C-NECK INSULATORS (3)
-INSTALL NEW VISE-GRIP INSULATORS (2)(6015.1000, INDCSA)
-INSTALL NEW VISE-GRIP INSULATOR (1)(6015.1000, INDCPT1)2-21X3
-INSTALL NEW L.I. CUTOUTS (6022.1000, DLS315F)2-71N
FUSE AT 100T
SW# X92704
P26 316533-166665 (1972, 40' CL1, ∠0⁰, AVG SPAN 78')
-EXIST POLE 14.1' FROM CURB FACE (NO FOG)
-EXIST POLE TO REMAIN
RETIRE SW#X3401
INSTALL SW#T95142
P27 316527-166678 (2012, 45' CL1, ∠0⁰, AVG SPAN 128')
-EXIST POLE 12.1' FROM CURB FACE (NO FOG)
-REMOVE EXISTING INLINE DEADENDS (3)
-REMOVE EXISTING TANGENT FRAMING
-INSTALL 3Ø DBL DE (6033.1046, DDE3315)2-21X3
INSTALL 9' DOUBLE CROSSARMS
-TIE INTO EXISTING 600 SB FOR RECLOSER
SITE PLAN
SCALE: 1" = 50'
POLE RETIREMENT TABLE TEMP TRANSFERS ST. LIGHT TRANSFERS
SITE
#
POLE DATA POLE
TEL TV FIBER TRAN RMVD ID NUMBER
GRID #HEIGHT CLASS YEAR TOPPED RMVD
P22 316526-166629 40 UNK 1985
P23 316524-166596 55 3 1967
POLE TABLE (NEW)
Site
#
Pole Data
Grid #Height Class Year Remarks / Location Ref.
P23 316524-166596 55 H3
P23 316526-166629 45 H3
P22 316524-166596 (1967, 55' CL3, ∠0⁰, AVG SPAN 270')
-EXIST POLE 4.9' FROM CURB FACE (NO FOG)
-EXIST POLE VIOLATES CZ
-REPLACE EXIST POLE WITH 55' CLH3 (6010.1000, PD55H3)2-69
SET POLE IN SAME HOLE
POLE WILL REQUIRE VARIANCE APPLICATION (RENTON)
WRAP POLE (9999222)
TAPE (9999235)
-INSTALL 3Ø TAN PTP (6033.1012, TAN313)
INSTALL STANDARD 9' ARM
-INSTALL NEW VISE-GRIP INSULATORS (3) 6015.1000, INDCSA)
-RETIRE UNKNOWN 40T CUTOUT
-INSTALL 1Ø TAP 2-71N
INSTALL 1Ø PRIMARY NEUT DE (6031.3011, DE2115A)
INSTALL LB C/O (6022.1000, DLS115L)
FUSE AT 40T (3412500)
TAP BØ
INSTALL NEW SW# X92702
-TRANSFER OH SEC,____TPLX (W), ATTACHED TO P21 (SPAN=161') ACTUAL____'
-TRANSFER OH SVC, ____TPLX (SW) SERVING ADDRESS 11625, ACTUAL____'
-TRANSFER STREETLIGHT 2-302
-TOP POLE 1' ABOVE COMMS, REMOVE AFTER COMMS TRANSFER 2-129
P23 316526-166629 (1985, 40' UNK, ∠0⁰, AVG SPAN 295')
-EXIST POLE 6.3' FROM CURB FACE (NO FOG)
-EXIST POLE VIOLATES CZ
-REPLACE EXIST POLE WITH 45' CLH3 (6010.1000, PD45H3)2-69
SET POLE 4' (S) OF EXISTING
-INSTALL NEW 3Ø SINGLE WINGARM (6033.4012, TASW313)
INSTALL 11' CROSSARM
-INSTALL NEW WINGARM 3Ø 200A TERM, OH TO UG (6044.1000, TSUWGL)2-71N,2-57X3
-INSTALL LI C/O'S & 100T FUSES (93412500)
INSTALL (3) LI C/O COVERS (99947626)
INSTALL (3) LA COVERS (9998115)
ACTUAL 3Ø_____ UG PRI ADDED L=___BATCH YEAR____2-55X___2-55____
ACTUAL TRENCH L=_____2-36X___2-45X___
INSTALL SW BD #T81079
EXISTING SW# T81079
-TRANSFER 3Ø 1/0 UG PRI; EXTEND AS REQ'D
-ACTUAL 1/0 UG PRI ADDED L=______ BATCH YEAR______
-ACTUAL TRENCH L=______
-TOP POLE 1' ABOVE COMMS, REMOVE AFTER COMMS TRANSFER 2-129
P24 316526-166650 (1985, 45' CL2, ∠0⁰, AVG SPAN180')
-EXIST POLE 8.4' FROM CURB FACE (NO FOG)
-EXIST POLE VIOLATES CZ
-EXIST POLE TO REMAIN
-REMOVE FIBERGLASS STANDOFFS TO REMAIN
-INSTALL 3Ø TAN PTP (6033.1012, TAN313) 2-21X3
INSTALL STANDARD 9' ARM
INSTALL VISE GRIPS
-TREE TRIMMING REQUIRED
Primary Cable & Conduit Table (Foreman to Complete)
LOCATION CONDUIT PRIMARY CABLE
QTY OF LUBE (gal.)AS BUILT INFORMATION
From To Size
(in)
Qty
Design
Length
(ft)
Actual
Length
(ft)
TYPE BENDS PULL
(lbs)
PULL
Rev
(lbs)
Cable
Size
Design
Length
(ft)
Actual
Length
(ft)
CABLE NUMBERS MANUFACTURING INFORMATION FOR FEEDER CABLE ONLY
Check applicable box
DB120 HDPE SCH 80 90°45°22°11°A B C Manufacturer Compound Year Tape CN #4/0 NEU Design As Built Actual Amount Installed
(Conduit & Cable)
P23 J02 4"1 20 X 209 209 1/0 JKT 80 EKB978 EKB979 EKB980
TRENCH DETAILS
2-57X3
6/13/2025425.559.5712
MFP26000225
LS=2345
RS=202.5
LS=1400
RS=249.15
LS=255
RS=136.11
FROM P05 TO P17
FROM P02 TO P04
FROM P19 TO P27
LS=181
RS=181
FROM P17 TO P18
10
1
1
5
7
2
9
6
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
AYLA SILER 425.456.2757 N/A
A. CRAWFORD 425.424.7982 N/A
N/A N/A N/A
CDB/APM 928.848.7369 06-24-24
RW-132063 RENTON
ROL-13 TWFDR 116 4400FT
Rel-Upgr - Tree Wire
11426 SE 169TH ST, RENTON, WA 98055
DESIGNED BY ACTALENT SERVICES
N/A N/A
N/A N/A
AS NOTED 7/7
N/A N/A N/A N/A
NW 33-23-05 N/A 214-084
2305E130 2305E136 2305E130 ROL-13
CENTURYLINK
N/A
N/A
COMCAST
N/A
N/A
RENTON SCHOOL
N/A
N/A
PSE FIBER
N/A
N/A
DEADEND DIAGRAM
SCALE: NOT TO SCALE
6/13/2025425.559.5712
MFP26000225
DEPARTMENT OF COMMUNITY
AND ECONOMIC DEVELOPMENT
Major Franchise Permit: MFP26000225
(Date)(Signature)
Page 2 of 2THIS PERMIT AND PLANS MUST BE POSTED AT THE JOB SITE AT ALL TIMES