APPLICABLE CODES AND STANDARDS
1. ALL LOCAL, STATE, AND FEDERAL AGENCIES HAVING
JURISDICTION OVER THIS PROJECT
a. CITY OF RENTON STRUCTURAL DESIGN CRITERIA
2. 2021 INTERNATIONAL BUILDING CODE (2021 IBC)
3. AMERICAN CONCRETE INSTITUTE (ACI):
a. ACI 318-19 BUILDING CODE REQUIREMENTS FOR
STRUCTURAL CONCRETE
4. AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC):
a. AISC 360-16 SPECIFICATION FOR STRUCTURAL STEEL
BUILDINGS
b. AISC 341-16 SEISMIC PROVISIONS FOR STRUCTURAL STEEL
BUILDINGS
c. 2014 RCSC SPECIFICATION FOR HIGH -STRENGTH BOLTS
5. AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE):
a. ASCE 7-16 MINIMUM DESIGN LOADS FOR BUILDINGS AND
OTHER STRUCTURES
6. ASTM INTERNATIONAL (ASTM):
a. ALL MATERIAL STANDARDS NOTED
7. AMERICAN WELDING SOCIETY (AWS):
a. AWS D1.1-2015 STRUCTURAL WELDING CODE - STEEL
b. AWS D1.3-2008 STRUCTURAL WELDING CODE - SHEET STEEL
c. AWS D1.4-2011 STRUCTURAL WELDING CODE - REINFORCING
STEEL
d. AWS D1.8-2016 STRUCTURAL WELDING CODE - SEISMIC
SUPPLEMENT
8. STEEL DECK INSTITUTE (SDI):
a. SDI CRD-2017 STANDARD FOR STEEL ROOF DECK
FOUNDATION DESIGN
1. THE FOUNDATION DESIGN IS BASED UPON THE "SUPPLEMENTAL
GEOTECHNICAL AND PAVEMENT RECOMMENDATIONS"
GEOTECHNICAL REPORT PREPARED BY THE GENERAL
ENGINEERING CONSULTANT. REPORT NUMBER D3458632 DATED
DECEMBER 2024.
2. ALLOWABLE NET BEARING CAPACITY: 2,000 PSF
3. ALLOWABLE NET POST -LIQUEFACTION
BEARING CAPACITY: 800 PSF
4. FROST DEPTH: 1'-0"
5. ALLOWABLE VERTICAL PILE CAPACITY: 80,000 LB
6. ALLOWABLE LATERAL PILE CAPACITY: 15,000 LB
MATERIALS OF CONSTRUCTION
1.
NORMAL WEIGHT CONCRETE
GENERAL STRUCTURAL CONCRETE
f'c = 4,500 psi
2.
REINFORCING STEEL
ASTM A615 GR 60
Fy = 60 ksi
3.
WELDABLE REINFORCING STEEL
ASTM A706 GR 60
Fy = 60 ksi
4.
WELDED WIRE REINFORCING
ASTM Al064
Fy = 70 ksi
5.
STRUCTURAL STEEL
WIDE FLANGE & TEE SHAPES
ASTM A992
Fy = 50 ksi
ANGLES AND CHANNELS
ASTM A36
Fy = 36 ksi
PLATES
ASTM A572
Fy = 50 ksi
HSS RECTANGULAR & SQUARE
ASTM A500 GR C
Fy = 50 ksi
HSS ROUND
ASTM A500 GR C
Fy = 45 ksi
BOLTS
ASTM A325
Fu = 120 ksi
ANCHOR RODS
ASTM F1554 GR 36
Fy = 36 ksi
ANCHOR RODS ASTM F1554 GR 55 WELDABLE
Fy = 55 ksi
HIGH STRENGTH ANCHOR ROD
ASSEMBLY:
ANCHOR RODS
ASTM F1554 GR 105
Fy = 105 ksi
NUTS
ASTM A563 GR D
HEADED STUDS
ASTM A108, TYPE B
Fu = 65 ksi
DEFORMED BAR ANCHORS
ASTM F1554 GR 55
Fy = 55 ksi
WELDING ELECTRODES
E70XX
STEEL ROOF DECKING (GALVANIZED)
ASTM A653 G60 (Z180) ZINC COATING
Fy = 50 ksi
WEATHERED STEEL PLATES
ASTM A242
Fy = 42 ksi
6.
NON -SHRINK AND NON-METALLIC GROUT AT BASE/BRG PLATES
AT 7 DAYS
f'c = 4,000 psi
AT 28 DAYS
f'c = 8,000 psi
1
06/13/2025
LPD
AJF
AE
ADDENDUM #1
0
12/10/2024
LPD
DJP
AE
ISSUED FOR BID
No.
DATE
DSN
CHK
APP
REVISION
DESIGN LOADS
i =11 0011111rill�i
1
GROUND SNOW LOAD, Pg: 20 PSF
SNOW EXPOSURE FACTOR, Ce: 1.0
SNOW LOAD IMPORTANCE FACTOR, Is: 1.0
THERMAL FACTOR, Ct : 1.2
RAIN ON SNOW: 5 PSF
MIN ROOF SNOW LOAD: 25 PSF
2. WIND DESIGN DATA
ULTIMATE DESIGN WIND SPEED, Vult: 110 MPH
RISK CATEGORY: II
WIND EXPOSURE CATEGORY: B
INTERNAL PRESSURE COEFFICIENT (ENCLOSED): ±0.18
3. EARTHQUAKE DESIGN DATA
RISK CATEGORY II
SEISMIC IMPORTANCE FACTOR, le 1.0
MAPPED SPECTRAL RESPONSE ACCELERATION PARAMETERS
Ss 1.530 g
S1 0.417 g
SITE CLASS E
DESIGN SPECTRAL RESPONSE ACCELERATION PARAMETERS
Sds 1.224 g
Sd 1 0.658 g
SEISMIC DESIGN CATEGORY D
3.1 SHELTER CANOPY
BASIC FORCE RESISTING SYSTEM:
STEEL SPECIAL CANTILEVER COLUMN
RESPONSE MODIFICATION COEFFICIENT, R: 2.50
OVERSTRENGTH FACTOR, Do: 1.25
DEFLECTION AMPLIFICATION FACTOR, Cd: 2.50
SEISMIC RESPONSE COEFFICIENT, Cs: 0.263
DESIGN BASE SHEAR PER COLUMN, V: 5 KIPS
ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE
3.2 CORE FACILITIES
BASIC FORCE RESISTING SYSTEM:
STEEL ORDINARY CONCENTRICALLY BRACED FRAMES '
STEEL ORDINARY MOMENT FRAMES 4
RESPONSE MODIFICATION COEFFICIENT, R: 3.25
OVERSTRENGTH FACTOR, Do: 3.00
DEFLECTION AMPLIFICATION FACTOR, Cd: 3.25
SEISMIC RESPONSE COEFFICIENT, Cs: 0.377
DESIGN BASE SHEAR, V: 104 KIPS
ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE
STORY DRIFT
1. THE PRIMARY STRUCTURE WILL EXPERIENCE LATERAL
MOVEMENTS BETWEEN ADJACENT FLOORS. THE STORY DRIFTS
PERPENDICULAR AND/OR PARALLEL TO THE PRIMARY STRUCTURE
ARE AS FOLLOWS:
SHELTER CANOPY SERVICE LEVEL DESIGN
STORY DRIFT STORY DRIFT
ROOF 3/4" 3 1/2"
CORE FACILITIES SERVICE LEVEL DESIGN
STORY DRIFT STORY DRIFT
ROOF
1
DESIGNED BY:
L. DOWELL
DRAWN BY:
R. MUNRO
CHECKED BY:
A.FORTNER
APPROVED BY:
A. ESPARZA
3/4"
2/June/2025
3"
STORY DRIFT (CONT'D) EARTHWORK AND FOUNDATIONS CONCRETE AND REINFORCING (CONT'D)
2. BUILDING COMPONENTS SUCH AS EXTERIOR CLADDING, STAIRS, 1. ALL EARTHWORK AND SITE PREPARATION SHALL BE PERFORMED 11. CONTINUOUS REINFORCEMENT IN WALLS AND FOOTINGS MAY BE
MISCELLANEOUS METALS, MEP SYSTEM SUPPORTS, INTERIOR IN STRICT ACCORDANCE WITH THE SPECIFICATIONS AND THE SPLICED AS REQUIRED, PROVIDED THAT BARS ARE OF THE
METAL STUD FRAMING, AND ANY OTHER ELEMENT REQUIRED BY GEOTECHNICAL REPORT. ALL FOUNDATION EXCAVATIONS SHALL LONGEST PRACTICAL LENGTH AND ALL SPLICES ARE SHOWN ON
THE BUILDING CODE SHALL BE DESIGNED TO ACCOMMODATE THE BE OBSERVED AND APPROVED BY THE GEOTECH. THE REINFORCING BAR SHOP DRAWINGS. SPLICES ARE TO BE
PRIMARY STRUCTURE STORY DRIFTS WITH ANY APPLICABLE STAGGERED WHEN POSSIBLE. PROVIDE LAP SPLICES AND
COMPONENT -SPECIFIC MODIFICATION PER CHAPTER 13 OF ASCE 7. 2. ANY EXISTING FILLS OR UNSUITABLE SOILS AS DETERMINED BY DEVELOPMENT LENGTHS IN ACCORDANCE WITH THE
THE GEOTECH SHALL BE EXCAVATED AND REPLACED WITH DEVELOPMENT LENGTH AND LAP SPLICE SCHEDULE. USE CLASS B
GENERAL CONSTRUCTION NOTES PROPERLY COMPACTED FILL LAP SPLICES UNLESS NOTED OTHERWISE
1. STRUCTURAL DRAWINGS SHALL NOT BE SCALED. PRINTED
DIMENSIONS HAVE PRECEDENCE OVER SCALED DRAWINGS AND
LARGE SCALE OVER SMALL.
2. ALL DRAWINGS AND SPECIFICATIONS ARE CONSIDERED TO BE A
PART OF THE CONTRACT DOCUMENTS. STRUCTURAL DRAWINGS
SHALL BE USED IN CONJUNCTION WITH THE CIVIL,
ARCHITECTURAL, MECHANICAL, ELECTRICAL AND PLUMBING
DRAWINGS FOR LOCATION AND SIZE OF OPENINGS, BLOCKOUTS,
FLOOR DEPRESSIONS, CURBS, DIMENSIONS, ETC. NOT INDICATED
ON THE STRUCTURAL DRAWINGS. THE LOCATION AND SIZE OF
MECHANICAL AND ELECTRICAL OPENINGS IN SLABS, WALLS AND
DECKS SHALL BE COORDINATED BY THE CONTRACTOR. PROVIDE
ALL ADDITIONAL FRAMING OR REINFORCING TO ACCOMMODATE
OPENINGS AS REQUIRED BY THE APPLICABLE STANDARD DETAILS
SHOWN ON THE STRUCTURAL DRAWINGS. NO HOLES, NOTCHES,
BLOCKOUTS, ETC. ARE ALLOWED IN STRUCTURAL MEMBERS
UNLESS DETAILED ON THE STRUCTURAL DRAWINGS OR
APPROVED BY THE STRUCTURAL ENGINEER.
3. WHERE DIMENSIONS ARE PROVIDED FOR OPENINGS,
BLOCKOUTS, FLOOR DEPRESSIONS, CURBS, ETC., BUT MAY BE
AFFECTED BY THE EQUIPMENT PURCHASED, THE CONTRACTOR
SHALL VERIFY THE INFORMATION PROVIDED PRIOR TO
CONSTRUCTION.
4. PROVIDE CONCRETE EQUIPMENT PADS AND INERTIAL BASES FOR
MECHANICAL AND ELECTRICAL INSTALLATIONS. CONSTRUCT
PADS AND BASES IN ACCORDANCE WITH THE TYPICAL DETAILS.
SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR LIMITS AND
LOCATIONS.
5. THE CONTRACTOR SHALL VISIT THE SITE AND GET FAMILIAR WITH
EXISTING CONDITIONS, CHECK AND VERIFY EXISTING DIMENSIONS
AND TAKE ADDITIONAL MEASUREMENTS AS NEEDED. NOTIFY THE
ARCHITECT OF ANY DISCREPANCY BETWEEN ACTUAL
CONDITIONS AND INDICATED CONDITIONS. MODIFICATION OF
DETAILS OF CONSTRUCTION SHALL NOT BE MADE WITHOUT
WRITTEN APPROVAL OF THE ARCHITECT OR STRUCTURAL
ENGINEER.
6. CONTRACTOR SHALL PROVIDE AND BE RESPONSIBLE FOR THE
PROTECTION AND REPAIR OF ADJACENT EXISTING SURFACES
AND AREAS WHICH MAY BE DAMAGED BY NEW WORK.
7. ALL COLUMNS AND FOUNDATIONS, UNLESS NOTED OTHERWISE,
SHALL BE CENTERED ON GRIDLINES IN EACH DIRECTION. BEAMS
SHALL BE EQUALLY SPACED BETWEEN COLUMN CENTERLINES
UNLESS NOTED OTHERWISE.
8. TYPICAL DETAILS SHALL APPLY IN GENERAL CONSTRUCTION
UNLESS SPECIFICALLY DETAILED. WHERE NO DETAILS ARE
GIVEN, CONSTRUCTION SHALL BE AS SHOWN FOR SIMILAR WORK.
9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ADEQUATE
DESIGN AND CONSTRUCTION OF ALL FORMS, SHORING AND
TEMPORARY BRACING. THE CONTRACTOR SHALL PROVIDE ALL
MEASURES NECESSARY TO PROTECT THE STRUCTURE AND
SAFETY OF WORKERS DURING CONSTRUCTION.
A. DO NOT PLACE CONSTRUCTION MATERIALS OR OTHER
CONSTRUCTION LOADS ON THE STRUCTURE SUCH THAT THE
LOADS PLACED EXCEED THE CAPACITY OF THE STRUCTURE.
B. TAKE INTO CONSIDERATION THAT FULL STRUCTURAL
CAPACITY OF MANY STRUCTURAL MEMBERS IS NOT REALIZED
UNTIL STRUCTURAL ASSEMBLY IS COMPLETE; THAT IS, UNTIL
SLABS, DECKS, DIAGONAL BRACING AND SHEAR WALLS ARE
INSTALLED.
C. PROVIDE TEMPORARY BRACING AND GUYING TO PROVIDE
STABILITY AND RESIST ALL LOADS TO WHICH THE PARTIALLY
COMPLETED STRUCTURE MAY BE SUBJECTED INCLUDING
ERECTION EQUIPMENT AND ITS OPERATION. ADEQUACY OF
TEMPORARY BRACING AND GUYING FOR THIS PURPOSE IS THE
SOLE RESPONSIBILITY OF THE CONTRACTOR.
D. DO NOT BACKFILL AGAINST BASEMENT WALLS UNTIL FRAMED
SLAB AND SLAB ON GRADE LOCATED TOP AND BOTTOM OF
BASEMENT WALL HAVE BEEN PLACED AND HAVE REACHED
THEIR 28-DAY DESIGN STRENGTH.
F)R 4STmRIDE
BRT General Engineering Consultant
SUBMITTED BY: DATE: REVIEWED BY:
R. PARGAS 12/10/2024 J. ALTCHECH
3.
EXTREME CARE SHALL BE EXERCISED WHEN EXCAVATING OR
12.
CORING OF SLABS, BEAMS, COLUMNS, OR WALLS IS NOT
GRADING ADJACENT TO EXISTING STRUCTURES OR
PERMITTED. PROVIDE SLEEVES FOR ALL PENETRATIONS PRIOR
IMPROVEMENTS SO AS NOT TO DAMAGE OR UNDERMINE
TO PLACING CONCRETE.
FOUNDATIONS, WALLS, SLABS, UTILITIES, ETC.
STEEL ROOF DECK
4.
DO NOT EXCAVATE BELOW THE BEARING ELEVATION OF ANY
COMPLETED FOOTING NOR ANY CLOSER TO THE FOOTING THAN A
1.
PROVIDE STEEL ROOF DECKS THAT CONFORM TO THE
SLOPE OF TWO HORIZONTAL (MEASURED FROM EDGE OF
REQUIREMENTS OF THE BUILDING CODE, SECTION 2210.
FOOTING TO NEAREST POINT IN EXCAVATION) TO ONE VERTICAL.
2.
CUTTING AND FRAMING OF OPENINGS FOR OTHER TRADES SHALL
5.
HORIZONTAL CONSTRUCTION JOINTS IN COLUMN FOOTINGS,
BE THE RESPONSIBILITY OF THE TRADES INVOLVED. HOLES THAT
SLABS ON GRADE AND MAT FOUNDATIONS ARE NOT PERMITTED.
ARE LOCATED AND DIMENSIONS ON THE DRAWINGS SHALL BE
THE RESPONSIBILITY OF THE DECK ERECTOR.
6.
PROVIDE DOWELS FOR ALL WALLS EMBEDDED INTO COLUMN
FOOTINGS, MAT FOUNDATIONS AND GRADE BEAMS. DOWELS
3.
ALL DECK SHALL HAVE A MINIMUM GAUGE OF 20, UNLESS
SHALL BE THE SAME SIZE AND SPACING AS VERTICAL WALL
INDICATED OTHERWISE ON THE STRUCTURAL DRAWINGS. STEEL
REINFORCEMENT.
DECK SHALL BE VERCO TYPE HSB-36, ASC TYPE B, OR APPROVED
EQUAL. ALL DECK SHALL BE GRADE 50 STEEL.
7.
BOTTOM OF ALL FOOTINGS SUBJECT TO FROST SHALL BE PLACED
AT OR BELOW FROST DEPTH.
4.
DECK SHALL BE PLACED IN A TWO OR THREE SPAN CONDITION IN
ALL LOCATIONS UNLESS NOT POSSIBLE DUE TO GEOMETRY.
CONCRETE AND REINFORCING
5.
DECKS SHALL HAVE MINIMUM 2" BEARING AT SUPPORTS.
1. LOCATION OF CONSTRUCTION JOINTS OR POUR JOINTS SHALL BE
AS INDICATED ON APPROVED SHOP DRAWINGS.
2. ALL CONCRETE SHALL BE VIBRATED DURING PLACEMENT.
3. PROVIDE 3/4" CHAMFER ON ALL EXPOSED CONCRETE CORNERS.
4. NO STAKES, STEEL OR WOOD, SHALL BE PERMITTED IN ANY
CONCRETE POUR. SUSPEND FORMS FROM ABOVE GRADE.
5. ANCHOR RODS, DOWELS, REINFORCING STEEL, INSERTS, ETC,
SHALL BE SECURELY TIED IN PLACE PRIOR TO POURING
CONCRETE. CONCRETE BLOCKS ONLY SHALL BE USED TO
SUPPORT REINFORCING OFF GRADE.
6. ALL REINFORCEMENT SHALL BE DETAILED, FABRICATED AND
PLACED IN ACCORDANCE WITH ACI 315.
7. PROVIDE MINIMUM CONCRETE COVERING FOR REINFORCEMENT
AS FOLLOWS:
A. CONCRETE DEPOSITED AGAINST EARTH: 3"
B. FORMED SURFACES EXPOSED TO
WEATHER OR IN CONTACT WITH EARTH:
REINFORCING #6 OR LARGER 2"
REINFORCING LESS THAN #6 1 1/2"
C. FORMED SURFACES IN BUILDING INTERIOR:
BEAMS, GIRDERS, AND COLUMNS 1 1/2"
D. SLABS, WALLS AND JOISTS:
REINFORCING #11 OR SMALLER 3/4"
REINFORCING #14 AND #18 1 1/2"
8. PROVIDE DOWELS OF SAME SIZE AND NUMBER FROM ADJACENT
POUR, BOTH VERTICALLY AND HORIZONTALLY, TO MATCH
TYPICAL REINFORCING SHOWN. LAPS TO BE IN ACCORDANCE
WITH THE DEVELOPMENT LENGTH AND LAP SPLICE SCHEDULE.
DOWELS SHALL BE CLEANED AFTER POUR.
9. FIELD WELDING OR BENDING OF REINFORCING IS NOT PERMITTED
EXCEPT AS INDICATED ON THE DRAWINGS OR AS APPROVED BY
THE STRUCTURAL ENGINEER. USE LOW HYDROGEN ELECTRODES
GRADE E70 OR E90 AS REQUIRED.
10. APPROVED ELECTRICAL CONDUIT MATERIAL CAST WITHIN
STRUCTURAL CONCRETE MEMBERS SHALL CONFORM TO ACI 318
UNLESS NOTED OTHERWISE AND TO THE FOLLOWING:
A. PERMITTED CONDUIT SHALL BE PLACED INSIDE THE
REINFORCING CAGE IN COLUMNS, WALLS, AND SLABS, AND
BELOW REINFORCING IN SLABS ON GRADE.
B. CONDUIT IN SLAB ON GRADE:
DIAMETER OF A SINGLE CONDUIT OR TWO OR MORE
VERTICALLY STACKED CONDUITS (INCLUDING CROSSOVERS)
SHALL NOT EXCEED 1/3 THE THICKNESS OF THE SLAB. THE
OUTSIDE DIMENSION OF TWO OR MORE ADJACENT CONDUITS
SHALL NOT EXCEED TWICE THE DEPTH OF THE SLAB AND THE
SEPARATION BETWEEN GROUPS OF CONDUITS SHALL NOT BE
LESS THAN THE THICKNESS OF THE SLAB.
C. DO NOT INSTALL CONDUIT IN PARKING GARAGE SLABS.
D. DO NOT INSTALL CONDUIT IN BEAMS.
SCALE:
Q w NTS
Q FILENAME: SO
W U)
w S 1-BT120-S-v2020
Z J
J � SOUNDTRANSIT CONTRACT No.:
RTA/OA 0206-19
DATE: SUBMITTAL DATE:
12/10/2024 12/10/2024
6. SEE ARCHITECTURAL AND LIFE -SAFETY DRAWINGS FOR THE
EXTENT OF FIREPROOFING. STEEL DECK TO BE SPRAY
FIREPROOFED SHALL BE GALVANIZED, CLEANED, AND
DEGREASED BEFORE SHIPPING.
7. CONTRACTOR SHALL DESIGN AND SUPPLY ALL ADDITIONAL
MISCELLANEOUS METALS AND SYSTEM SUPPORT COMPONENTS
THAT ARE REQUIRED TO SUPPORT ALL MECHANICAL,
ELECTRICAL, AND PLUMBING/FIRE-PROTECTION SYSTEMS. SUCH
SUPPORT COMPONENTS AND THEIR CONNECTIONS SHALL BE
PROVIDED TO DIRECTLY AND CONCENTRICALLY IMPOSE LOADS
ON THE PRIMARY STRUCTURE. A MAXIMUM LOAD OF 50 POUNDS
MAY HANG FROM STEEL ROOF DECK.
SPECIAL INSPECTIONS
1. STRUCTURAL STEEL, WELDING, HIGH STRENGTH BOLTS,
CONCRETE, ANCHORS CAST IN CONCRETE, ANCHORS POST -
INSTALLED IN HARDENED CONCRETE, AND REINFORCING STEEL
REQUIRE SPECIAL INSPECTIONS AND TESTING PER THE
INTERNATIONAL BUILDING CODE SECTION 1705.
2. THIS WORK SHALL BE PERFORMED BY A SPECIAL INSPECTOR
CERTIFIED BY THE AUTHORITY HAVING JURISDICTION TO
PERFORM THE TYPES OF INSPECTIONS AND TESTS SPECIFIED.
3. THE TIMING AND FREQUENCY OF THE INSPECTIONS AND TESTING
SHALL BE AS DESCRIBED IN THE CORRESPONDING TABLE OF THE
INTERNATIONAL BUILDING CODE FOR EACH ELEMENT.
ANCHOR RODS
1. ANCHOR RODS SHALL BE AS NOTED IN THE MATERIALS OF
CONSTRUCTION SECTION OF THE GENERAL NOTES, UNLESS
NOTED OTHERWISE. PROVIDE ANCHOR RODS PREFABRICATED
WITH CORRESPONDING DOUBLE HEAVY HEX NUTS ADDED AT
EMBEDDED IN CONCRETE END. INSTALL PLATE WASHERS AND
CORRESPONDING HEAVY HEX NUTS THAT SECURE THE BASE
PLATE ASSEMBLY TO THE ANCHOR RODS. RIGID STEEL
TEMPLATES SHALL BE USED TO LOCATE ANCHOR RODS WHILE
PLACING CONCRETE. AT LEAST ONE TEMPLATE SHALL BE
TOWARDS THE BOTTOM OF THE ANCHOR RODS.
2. LENGTH OF ANCHOR RODS SHALL BE ENOUGH TO PROVIDE THE
MINIMUM EMBEDMENT SHOWN ON THE DRAWINGS, WHICH IS
MEASURED FROM THE FACE OF CONCRETE TO THE NEAREST
FACE OF THE NOTED DOUBLE NUT. ADDITIONALLY, ADEQUATE
EXTENSION TO RECEIVE THE BASE PLATE WITH ADEQUATE
THREAD PROJECTION FOR FULL NUT ENGAGEMENT SHALL BE
PROVIDED. ANCHOR ROD INSTALLATION SHALL BE COORDINATED
WITH REINFORCING, FORMWORK, AND CONDUIT WHERE
APPLICABLE. LEVELING NUTS SHALL NOT BE USED EXCEPT AFTER
EVALUATION BY THE CONTRACTOR'S ERECTION ENGINEER.
3. ANCHOR ROD NUTS SHALL BE INSTALLED TO A SNUG -TIGHT
CONDITION. HEATING OR BENDING OF THE ANCHOR RODS OR
BASE PLATE IS NOT ALLOWED.
FDEVELOPIMENT ENGINEERING
R-4332267o 11 /25/2025
TRIDE BUS RAPID TRANSIT DRAWING NO.:
UTH RENTON TRANSIT CENTER BT120-SZN001
BT105 FACILITY ID:
STRUCTURAL BT120
SHEET No: REV:
GENERAL STRUCTURAL NOTES