HomeMy WebLinkAboutR-4332371N co co O W O N (D N Q O N H !b U) 0 w CD I H (n Z Q ry H I 0 n ry I (n D m of 0 co 00 LO M a 0 N >Q M 0 0 LO CY) m BUILDING THERMAL ENVELOPE AIR LEAKAGE TEST 2.A 22 2.0 2.D 2.E 1. BUILDING AIR LEAKAGE TESTING SHALL BE PERFORMED PER ASTM C779 2. THE TARGET LEAKAGE RATE IS 0.25 CFM/FT2 (1.5 L/S*M2) AT 0.3 IN. WG (75 PA) 3. TESTED PORTIONS OF THE BUILDING SHALL INCLUDE ALL SPACES DIRECTLY UNDER THE ROOF, ALL SPACES THAT HAVE A BUILDING ENTRANCE, EXPOSED FLOOR, LOADING DOCK OR ARE BELOW GRADE PLANE, AND REPRESENTATIVE ABOVE - GRADE AREAS THAT TOTAL >: 25% OF THE BUILDING TOTAL ABOVE -GRADE WALL AREA; 4. THE WEIGHTED AVERAGE AIR LEAKAGE RATE OF THE BUILDING THERMAL CONTINUOUS AIR BARRIER ENVELOPE SHALL NOT EXCEED 0.25 CFM/FT2 (1.27 L/S*M2) WHEN MEASURED AT A GRAPHIC REPRESENATION — — — — — — — — — — — — — — — — PRESSURE DIFFERENTIAL OF 0.3 IN. WG (75 PA). FOR BUILDING ENVELOPE, SEE WALL SECTION FOR DETAIL I TRANVERSE SECTION - @ OPERATOR RESTROOM ( A SCALE: 3/4" = V-0" BT120-ARP221 DESIGNED BY: C. CHEANG DRAWN BY: 9849 REGISTERED J. CHAN ARC 45 — F)R TmRIDE CHECKED BY: N N BRT General Engineering Consultant D. HOGAN STATE OF WASHINGT 0 12/10/2024 J.C. D.H. C.C. ISSUED FOR BID APPROVED BY: SUBMITTED BY: DATE: REVIEWED BY: No. DATE I DSN I CHK APP REVISION C. CHEANG I R. PARGAS 112/10/2024 J. ALTCHECH SCALE: Q w mrr As indicated _j Q FILENAME: � w U) S 1-BT120-A-v2020 Z J J U_ SOUNDTRANSIT N R T0. CONTRACT /CN 02 05-24 DATE: SUBMITTAL DATE: 12/10/2024 12/10/2024 8 4 0 8 EDEVESLiOPIMENT ENGINEERING SCALE IN FEET I o 11 /25/2025 R-4332371 STRIDE BUS RAPID TRANSIT DRAWING NO.: SOUTH RENTON TRANSIT CENTER BT120-AIX722 BT105 FACILITY ID: ARCHITECTURE BT120 SHEET No: REV: BUILDING SECTIONS II CORE FACILITY 449 0