DRAWING NOTES:
LEGEND REFER TO GEN-GZN006 & GEN-GZN007
FOR ADDITIONAL SYMBOLS AND LEGEND
GENERAL NOTES
PIPING SYMBOLS
VALVE SYMBOLS
A.
REFER TO GEN-GZN006 AND GEN-GZN007 FOR ADDITIONAL SYMBOLS AND
KEY NOTES:
LEGEND.
(1) 1/2" TP FROM ABOVE -DETAIL 4/MPD001.
O P-TRAP
GATE VALVE
B.
REFER TO SPECIFICATIONS FOR MATERIALS AND METHODS
O1" DCW FROM ABOVE.
FOR CONSTRUCTION.
O1" NPW FROM ABOVE.
0 CLEANOUT
BALL VALVE
C.
COORDINATE THE EXACT LOCATION OF FLOOR DRAINS WITH THE
40 2" DCW UP THROUGH FLOOR.
ARCHITECTURAL DRAWINGS AND MECHANICAL EQUIPMENT LOCATIONS PRIOR
TO INSTALLATION OF DRAINS.
HOSE BIBB, WALL HYDRANT
CHECK VALVE (NON SLAM)
05 3" WASTE FROM LAVATORIES.
PRESSURE REDUCING VALVE
D.
COORDINATE ACCESS DOORS FOR INSTALLATION IN WALLS AND CEILINGS
3" WASTE FROM SINK.
O
o FLOOR DRAIN
(PRV)
WHERE ACCESS IS REQUIRED TO CONCEALED PLUMBING EQUIPMENT,
VALVES, CONTROLS, AND OTHER DEVICES.
07 3" WASTE FROM MOP SINK.
LINE/WALL CLEANOUT
STRAINER
E.
PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS, REVISIONS,
T 4" WASTE FROM URINALS.
AMENDMENTS OR SUPPLEMENTS OF APPLICABLE STATUTES, ORDINANCES,
WATER HAMMER ARRESTER
CODES, OR REGULATIONS OF FEDERAL, STATE AND LOCAL AUTHORITIES
ABBREVIATIONS
99 4" SANITARY SEWER FROM WATER CLOSETS.
HAVING JURISDICTION IN EFFECT ON THE DATE BIDS ARE RECEIVED. AS OF
PRESSURE GAUGE WITH COCK
JAN 2023, WAC VERSIONS OF: 2018 IBC, 2018 UPC.
10 4" WASTE FROM FLOOR DRAIN.
BCO
BUILDING CLEANOUT
F.
COORDINATE WORK WITH ARCHITECTURAL FEATURES AND COORDINATE
11 2" WASTE FROM HUB DRAIN. SEE DETAIL 3/MPS001.
UNION
BOD
BASIS OF DESIGN
WORK SUCH THAT INTERFERENCES BETWEEN PIPING, DUCTWORK,
EQUIPMENT, PLUMBING WORK, ELECTRICAL WORK, BUILDING STRUCTURE
12 4" WASTE FROM HUB DRAIN.
� PITCH DOWN IN DIRECTION OF ARROW
FS
FLOOR SINK
WILL BE AVOIDED.
13 4" UP TO CLEANOUT - DETAIL 2/MPD001.
HC
HANDICAPPED
G.
PROVIDE THE ENTIRE SYSTEM AND ITS COMPONENT ITEMS OF EQUIPMENT IN
14 DROP 4" SANITARY SEWER DOWN TO LOWER
® WALL HUNG WATER CLOSET
HD
HUB DRAIN
OPERATING CONDITION WITHOUT OBJECTIONABLE VIBRATION OR NOISE.
PROVIDE WATER HAMMER ARRESTERS AT RESTROOM PLUMBING CHASES.
ELEVATION.
15 2" VENT UP THROUGH FLOOR.
WALL HUNG URINAL
MS
MOP SINK
H.
PROVIDE ALL WIRING AND ELECTRICAL CONTROLS IN ACCORDANCE WITH
NFPA 70 (NEC).
NPW
NON -POTABLE WATER
16 4" UP THROUGH FLOOR TO CLEANOUT.
O
WALL HUNG LAVATORY
PCO
PLUG CLEANOUT
I.
VERIFY AND DOCUMENT EXISTING CONDITIONS AND DIMENSIONS ON THE JOB
17 3" HUB DRAIN (3" X 2" REDUCER).a
DROP -IN SINK
PG
PRESSURE GAUGE
SITE PRIOR TO STARTING ANY WORK.
18 4" HUB DRAIN (8" X 4" REDUCER). ROUTE DRAIN FROM
RPBA REDUCED PRESSURE BACKFLOW
J.
DO NOT SCALE THESE DRAWINGS FOR CONSTRUCTION PURPOSES.
BACKFLOW PREVENTER TO HUB DRAIN.
ASSEMBLY
INSTALL PIPING TO PROVIDE THE MAXIMUM POSSIBLE CLEAR HEIGHT
19 3" VENT THROUGH ROOF.
S
SINK
UNDERNEATH WHILE COORDINATING WITH OTHER TRADES. MAINTAIN A
20 4" DOUBLE TWO-WAY CLEANOUT - DETAIL 2/MPD001.
URN
URINAL
MINIMUM OF 6" ABOVE FINISHED CEILING TO PROVIDE CLEARANCE FOR
LIGHTING FIXTURES.
21 PROVIDE TAILPIECE TYPE TRAP PRIMER - DETAIL
VE
SANITARY VENT
K.
PROVIDE FINAL CONNECTIONS TO EQUIPMENT.
4/MPD001.
WHA
WATER HAMMER ARRESTER
22 SEE DOMESTIC WATER DIAGRAM 1/MPS001.
L.
LOCATE VENT TERMINALS A MINIMUM OF 10' HORIZONTALLY FROM ANY DOOR,
OPERABLE WINDOW, OR OTHER AIR INTAKE OF THE BUILDING OR ADJACENT
23 SEE SANITARY SEWER RISER DIAGRAM 1/MPS002.
BUILDING UNLESS THE VENT TERMINAL IS AT LEAST 2' ABOVE THE TOP OF
SUCH OPENING.
24 3" UP TO CLEANOUT -DETAIL 1/MPD001.
M.
EXTEND ALL VENT LINES VERTICALLY (45 DEGREE ANGLE OR GREATER FROM
25 2" WASTE FROM SINK.
HORIZONTAL) TO MINIMUM OF 6" ABOVE THE HIGHEST FLOOR LEVEL RIM OF
THE HIGHEST FIXTURE SERVED BY VENT.
26 1" DCW FROM BELOW FLOOR.
27 1" DCW UP THROUGH FLOOR.
N.
ALL SANITARY SEWER BRANCH LINES SHALL DROP TO THE SAME ELEVATION
AS THE SANITARY SEWER MAIN LINES UTILIZING A MAXIMUM SLOPE OF 45
28 NOT USED.
DEGREES.
29 NOT USED.
O.
ALL SANITARY SEWER PIPING SHALL BE SLOPED AT 1/4" PER FOOT MINIMUM.
P.
SEE ARCHITECTURAL, MECHANICAL, CIVIL, ELECTRICAL AND ROOM FINISH
30 NOT USED.
DRAWINGS FOR LOCATION OF EQUIPMENT AND FIXTURES.
31 NOT USED.
Q.
HANDLE, STORE, AND INSTALL EQUIPMENT ACCORDING TO MANUFACTURER'S
32 NOT USED.
INSTRUCTIONS.
33 NOT USED.
34 NOT USED.
WASHINGTON STATE ENERGY CODE NOTES FOR PLUMBING
35 NOT USED.
APPLICABLE CODES TO PLUMBING
WASHINGTON STATE PLUMBING CODE 2021 (UPC 2021
�6:) FLUSH VALVES SCHEDULED AIR TOUCHLESS, HANDLE
A.
PER C404.3.1 THE MAXIMUM LENGTH OF PIPING OF DOMESTIC HOT WATER
FLUSH VALVES ARE SHOWN IN CASE THE OWNER
AMMENDED)
FROM SOURCE OF HEATED WATER IS 3 FEET FOR 3/8" PIPE SIZE.
CHANGES DIRECTION. TYPICAL WC-1 AND UR-1 UNITS.
37 2" VENT THROUGH ROOF.
WASHINGTON STATE COMMERCIAL ENERGY CODE 2021
(IECC 2021 AMMENDED)
B.
PER C404.10.3 INSULATE DOMESTIC HOT WATER PIPING TO TABLE 403.10.3.
PIPE SIZE <1", INSULATION THICKNESS 1". INSULATE DOMESTIC COLD WATER
38 3/4" CONDENSATE TRAP CONNECTOR. LINE FROM ACU
PIPING WITH 1/2" THICK INSULATION IF <1.5", OTHERWISE 1" THICK INSULATION.
EQUIPMENT SYMBOLS
IN THIS ROOM.
C.
PIPE INSULATION SHALL BE CONTINUOUS TP PREVENT THERMAL BRIDGING.
C39"\) BACKFLOW PREVENTER IS POWERED FLOOD CONTROL
TYPE. IT CLOSES OFF WATER UPON DETECTION OF
D.
PER C408.1.4 PRIOR TO FINAL PLUMBING INSPECTIONS OR OBTAINING
BACKFLOW ACTIVATION. NO BMS.
CERTIFICATE OF OCCUPANCY, THE CERTIFIED COMMISSIONING
40 MAINTAIN 24" VERTICAL LIMIT AT FLOOR DRAINS.
EQUIPMENT CLEARANCE
L
PERFESSIONAL SHALL PROVIDE EVIDENCE OF BUILDING COMMISSIONING.
R-4332420
FDEVELOPIMENT ENGINEERING
o 11 /25/2025
DESIGNED D S LVABY
�� Y �I ,
rat%F WA. Icfr
/mow . _ �� �
`� z�
'� -i'
0676
v' Al°���ISTERF�.��
pS,ON `
7
�aCO S�
BRT General Engineering Consultant
F
Q
w
z
w
Q
U
J
SOUNDTRANSIT
NTSE
STRIDE BUS RAPID TRANSIT
SOUTH RENTON TRANSIT CENTER
BT105
MECHANICAL -PLUMBING
GENERAL NOTES AND LEGEND
DRAWING NO.:
BT120-MPN001
DRAWN BY:
D. SILVAN
FILENAME:
S1-BT120-MP-v2020
FACILITY ID:
BT120
CHECKED BY:
M. PHILLIPS
CONTRACT No.:
RTA/CN 0205-24
SHEET No: REV:
0
12/10/2024
DOS
MP
JHS
ISSUED FOR BID
APPROVED BY:
SUBMITTED BY:
DATE:
REVIEWED BY:
DATE:
SUBMITTAL DATE:
CORE FACILITY
498 0
No.
DATE
DSN
CHK
APP
REVISION
J. SACKINGER
Signed: 12-10-2024
R. PARGAS
12/10/2024
J. ALTCHECH
12/10/2024
12/10/2024