INLETS AND OUTLETS CALLOUT
FREE FLOW AREA RECTANGULAR DUCT SIZE
AIRFLOW TYPE
T1 DIAMETER NECK SIZE
DIFFUSER TYPE, SEE
10" OA- SCHEDULE FOR MODULE SIZE
�10" SD-1
(500 OA)
AIRFLOW IN UNITS OF CUBIC
FEET PER MINUTE, CFM, TO BE
BALANCED TO
FREE FLOW AREA RECTANGULAR DUCT SIZE
AIRFLOW TYPE
DIAMETER NECK SIZE
GRILLE TYPE, SEE SCHEDULE
FOR MODULE SIZE
12"x12" EA
16"x8" EG-1
17� (500 EA)
AIRFLOW IN UNITS OF CUBIC
FEET PER MINUTE, CFM, TO BE
BALANCED TO
fir► (200) PULLED AIRFLOW, CFM (INCLUDING INFILTRATION)
► (200) PUSHED AIRFLOW, CFM
AIRFLOW TYPES:
SA - SUPPLY AIR
RA - RETURN AIR
OA - OUTSIDE AIR
EA - EXHAUST AIR
0 12/10/2024 DW MP JHS ISSUED FOR BID
No. DATE DSN CHK APP REVISION
AHRI
EER
HSPF
MOCP
SCCR
ABBREVIATIONS
AIR-CONDITION, HEATING, AND REFRIGERATION INSTITUTION
ENERGY EFFICIENCY RATIO
HEATING SEASONAL PERFORMANCE FACTOR
MAXIMUN OVER CURRENT PROTECTION
SHORT CIRCUIT CURRENT RATING
SYMBOLS AND LEGEND
WALL REGISTER OR
GRILLE (SUPPLY)
CEILING DIFFUSER OR
REGISTER (SUPPLY)
CEILING REGISTER OR
GRILLE (RETURN AND
EXHAUST)
WALL REGISTER OR
GRILLE (RETURN AND
EXHAUST)
TURNING VANES
45 DEGREES ENTRY
CONICAL TEE
FD
FIRE DAMPER
MANUAL OPPOSED -BLADE
DAMPER
MANUAL BUTTERFLY
DAMPER
MOTORIZED DAMPER
M
FLEXIBLE CONNECTION
FLEXIBLE DUCTWORK
2021 WASHINGTON STATE ENERGY CODE (WSEC) NOTES
COMMERCIAL BUILDING, NEW CONSTRUCTION 2018 WSEC.
FOR COMPLIANCE WITH THE WSEC FOR OTHER DISCIPLINES SUCH AS ARCHITECTURAL,
ELECTRICAL AND PLUMBING SEE THOSE SHEETS.
FOR WSEC COMPLIANCE FOR MECHANICAL - HVAC THE PROJECT MUST MEET THE FOLLOWING:
C403 MECHANICAL SYSTEMS AS NOTED BELOW.
C403.1.1 HVAC TOTAL SYSTEM PERFORMANCE RATIO (TSPR)
THIS PROJECT HAS BUILDINGS IS LESS THAN 5000 SF THEREFORE CLAIMS EXCEPTION 1.
THIS PROJECT COMPLIES WITH C403.2.2 VENTILATION AND EXHAUST AND CHAPTER 4 IMC.
ASHRAE 62.1 SCHEDULE IS SHOWN IN THIS SET.
THIS PROJECT SELECTED EQUIPMENT TO MEET THE MINIMUM EFFICIENCY REQUIREMENTS OF
TABLES C403.3.2 (1 THROUGH 12).
C403.3.2 (1) AIR COOLED SPLIT SYSTEM AIR CONDITIONER MINIMUM 13.0 SEER: ELECTRICAL
ROOM.
C403.3.2 (2) AIR COOLED SPLIT SYSTEM HEAT PUMP MIN. 14.0 SEER, 8.2 HSPF: SECURITY, CORE
FAC.
C403.3.2 (3) SINGLE PACKAGE VERTICAL HEAT PUMPS, ROOM AIR CONDITIONERS: STORAGE,
TELECOM.
THIS PROJECT HAS AN AIR-TO-AIR ENERGY RECOVERY VENTILATION UNIT, COMPLIANT WITH
C403.3.5.
THIS PROJECT DOES NOT HAVE A REQUIREMENT FOR DIRECT DIGITAL CONTROLS PER
C403.4.11. ALL CONTROLS ARE LOCAL WIRED THERMOSTATS.
THIS PROJECT TAKES THE ECONOMIZERS EXCEPTION TABLE C403.5 FOR UNITS OF CLIMATE
ZONE 4C EFFICIENCY IMPROVEMENT OF 64%. ON SPLIT SYSTEM SERVING THE ELECTRICAL
SUPPLY DUCT (SECTION) ROOM.
C403.6 DOES NOT APPLY. VAV SYSTEMS SERVING MULTIPLE ZONES ARE NOT ON THIS PROJECT.
INTAKE, RETURN, OR
EXHAUST DUCT SECTION
BELLMOUTH OT ROOM TEMPERTURE SENSOR
OP ROOM PRESSURE SENSOR
** REFER TO GEN-GZN006 & GEN-GZN007 FOR ADDITIONAL SYMBOLS AND LEGEND.
CODES APPLICABLE TO HVAC
WASHINGTON STATE MECHANICAL CODE 2021 (IMC 2021 AMMENDED)
AMERICAN SOCIETY OF HEATING, REFRIGERATION, AND AIR CONDITIONING
ENGINEERS (ASHRAE):
• ASHRAE 62.1, VENTILATION AND ACCEPTABLE INDOOR AIR QUALITY
• ASHRAE 55, THERMAL ENVIRONMENTAL CONDITIONS FOR HUMAN OCCUPANCY
WASHINGTON STATE COMMERICAL ENERGY CODE 2021 (IECC 2021 AMMENDED)
SMACNA HVAC DUCT CONSTRUCTION STANDARDS
DESIGNED BY:
D. WONG
DRAWN BY:
L. GOUDEAU
CHECKED BY:
M. PHILLIPS
APPROVED BY:
J. SACKINGER
�2 t
30676
' ISTEgFO- Fv
ESS'ON
Signed: 12-10-2024
C403.7 THIS PROJECT COMPLIES WITH VENTILATION AND EXHAUST SYSTEMS. IN PARTICULAR
THIS PROJECT USES AN OCCUPANCY SENSOR AT THE SECURITY BUILDING AND An ENERGY
RECOVERY UNIT FOR VENTILATION NEEDS AT THE CORE FACILITIES BUILDING. SEE ASHRAE
62.1 VENTILATION COMPLIANCE SCHEDULE.
C403.7.4.2 THE PROJECT OCCUPANCY SENSOR AT SECURITY BUILDING WILL AUTOMATICALLY
TURN OFF THE SUPPLY AIR FAN WITHIN 30 MINUTES OF THE OCCUPANTS LEAVING THE
BUILDING.
C403.7.8 THE OCCUPANCY SENSOR FAN AT SECURITY BUILDING WILL COMPLY WITH THE
REQUIREMENT OF SHUTOFF DAMPERS AND BE CLASS 1 LEAKAGE OF LESS THAN 4 CFM/SF AT
1.0 INCH WATER GAUGE WHEN TESTED IN ACCORDANCE WITH AMCA 500D.
C403.8 THIS PROJECT DOES NOT HAVE ANY FAN SYSTEM MOTOR NAMEPLATES EXCEEDING 5
HP.
C403.10 CONSTRUCTION OF HVAC SYSTEM ELEMENTS COMPLY WITH THIS SECTION. DUCTS
CONVEYING OUTSIDE AIR WILL BE INSULATED TO R-7, PER TABLE C403.10.1.1 OUTDOOR AIR
DUCTS INSIDE A CONDITIONED SPACE CRITERIA <2800 CFM WILL BE USED FOR THIS PROJECT.
PER C403.10.1.2 ALL OTHER DUCTS SUPPLY, RETURN, EXHAUST DUCTS WILL BE INSULATED
USING A DUCT LOCATION AS INSIDE UNCONDITIONED SPACES, R-6.
C403.10.2 THIS PROJECT USES LOW PRESSURE DUCT SYSTEMS OPERATING AT < 2 INCHES
WATER GAUGE, CONSTRUCTED PER IMC AND THAT WILL BE LONGITUDINAL AND TRANSVERSE
JOINTS SEAMS ANS CONNECTIONS SEALED WITH WELDS, GASKETS, MASTICS OR TAPES IN
ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS AND THE
SPECIFICATIONS.
C403.10.3 PIPING INSULATION WILL BE APPLIED PER TABLE C403.10.3 PER FLUID OPERATING
TEMPERATURES, INSULATION CONDUCTIVITY AND NOMINAL PIPE OR TUBE SIZE.
C404 NOTES SEE PLUMBING, C405 NOTES SEE ELECTRICAL.
C406.1 ADDITIONAL ENERGY EFFICIENCY CREDIT REQUIREMENTS, THIS PROJECT COMPLIES
WITH EXCEPTION 1 BY BEING LOW ENERGY SPACES WITH SUFFICIENT PACKAGES FROM TABLE
TO ACHIEVE A MINIMUM OF THREE CREDITS.
C407 TOTAL BUILDING PERFORMANCE METHOD IS NOT USED ON THIS PROJECT.
C408.1 SYSTEM COMMISSIONING, IS NOT REQUIRED PER EXCEPTIONS 1 HVAC AND 2 PLUMBING.
C408.2 EXCEPTION 1. TOTAL MECHANICAL SYSTEMS IS LESS THAN 240 MBH COOLING AND LESS
THAN 300 MBH HEATING.
C408.3 EXCEPTION 2. LARGEST SERVICE WATER HEATING SYSTEM CAPACITY IS LESS THAN 200
MBH.
C409 ENERGY METERING AND ENERGY MANAGEMENT. SEE ELECTRICAL, THE HVAC
CONTRACTOR WILL NOT BE RESPONSIBLE FOR ANY ENERGY METERING OR ENERGY
MANAGEMENT.
pacobs
SUBMITTED BY:
R. PARGAS
Tm)?IDE
BRT General Engineering Consultant
DATE: REVIEWED BY:
12/10/2024 J. ALTCHECH
WASHINGTON STATE ENERGY CODE DESIGN CONDITIONS
SCALE:
Q
w
NTS
Q
FILENAME:
cnC/)
w
J
S1-BT120-MH-v2020
z
J
SOUNDTRANSIT
CONTRACT No.:
RTA/CN 0205-24
DATE:
SUBMITTAL DATE:
12/10/2024
12/10/2024
THIS DESIGN WAS ENGINEERED WITH WSEC CHAPTER 3
CLIMATE ZONE 4 C (MARINE), KING COUNTY, WASHINGTON
INTERIOR DESIGN CONDITIONS PER WSEC SECTION C302.1
MAXIMUM OF 72 F FOR HEATING, MINIMUM OF 75 F FOR COOLING
EXTERIOR DESIGN CONDITIONS, OUTDOOR DESIGN TEMPERATURES
THIS DESIGN WAS ENGINEERED WITH WSEC SECTION 302.2, APPENDIX C
TABLE C-1 CONDITIONS.
OUTDOOR TEMPERATURES: (SEA TAC AIRPORT)
COOLING SUMMER:
83 OF DRY BULB
65 OF WET BULD
HEATING WINTER
24 OF DRY BULB
NA
R-4332430
FDEVELOPIMENT ENGINEERING
o 11 /25/2025
STRIDE BUS RAPID TRANSIT DRAWING NO.:
SOUTH RENTON TRANSIT CENTER BT120-MHN001
BT105
MECHANICAL-HVAC
LEGEND, ABBREVIATIONS AND ENERGY CODES
CORE FACILITY
FACILITY ID:
BT105
SHEET No: REV:
508 0