AIR TO AIR ENERGY RECOVERY UNIT SCHEDULE
EXTERNAL
SP
FILTERS
UNIT DIMENSIONS
SUMMER CONDITIONS
WINTER
CONDITIONS
TOTAL
EQUIP
TAG
MFR
MODEL
SERVICE
OUTDOOR
AIR
INDOOR
AIR
MOTOR
VOLTAGE
MCP
(AMPS)
MOCP
(AMPS)
OPERATING
WEIGHT
REMARKS
SUPPLY
FAN
EXHAUST
FAN
SUPPLY
EXHAUST
WIDTH
HEIGHT
DEPTH
OAT
REA EAT
SOA LAT
OAT
DB
REA
EAT DB
SOA
LAT DB
DB
WB
DB
WB
DB
WB
(IN WG)
(IN WG)
MERV
(IN)
(IN)
(IN)
(OF)
(OF)
(OF)
(OF)
(OF)
(OF)
(OF)
(OF)
(OF)
(LBS)
BT120-ERU-01
RENEWAIRE
HE10IN
CORE BUILDING
575
600
2
1.8
13
44
50
24
95
75
80 67
83
67
24
70
57
120
14.6 20
385
1, 2, 3, 4
REMARKS:
ABBREVIATIONS:
1. ADVANCED VARIBLE SPEED/ ECM - DIRECT DRIVE MOTOR
3.
FACTORY FUSED
DISCONNECT.
SOA -
SUPPLY OUTSIDE AIR (PUSHED)
OAT - OUTSIDE AIR TEMPERATURE
2. TYPE: STATIC PLATE, HEAT AND HUMIDITY TRANSFER
4.
ORDER WITH DOUBLE WALL CONSTRUCTION. PAINTED WHITE.
REA -
RETURN EXHAUST AIR (PULLED)
LOUVERS SCHEDULE
MIN. FREE
FREE AREA
EXT. S.P.
MATERIAL
SIZE
BLADES
EQUIPMENT TAG
LOCATION
SYSTEM/SERVING
MANUFACTURER
MODEL
CFM
AREA
VELOCITY
(IN. WG)
TYPE
(SQ INCHES)
TYPE
REMARKS
(SQ FTG)
(FPM)
LVR-01
CORE FACILITY
EXHAUST AIR
RUSKIN
ELF375 DXH
600
1.19
310
0.05
AL
20x20
-
1, 2, 3
LVR-02
CORE FACILITY
OUTSIDE AIR
RUSKIN
ELF375 DXH
575
1.15
310
0.05
AL
20x20
-
1, 2, 3
REMARKS
1
DRAINABLE LOUVER. INSTALL AS HIGH AS PRACTICAL OVER JANITORS DOOR.
2
NO GRAVITY DAMPERS SINCE ENERGY RECOVERY UNITS FANS RUN CONTINUOUSLY.
3
FACTORY MERV 13 FILTERS OR EQUAL.
ELECTRIC HEATER SCHEDULE
DIMENSIONS
TOTAL
ELECTRIC
EQUIPMENT TAG
LOCATION
TYPE
ARRANGEMENT
W X H X D
OPERATING WT
REMARKS
(INCHES)
(LBS)
WATTS
AMPS
V / PH / HZ
BT120-HTR-01
JANITOR ROOM
210
1.8
120 / 1 / 60
WALL
SURFACE
24 x 4 x 4
6
6
1, 2, 3, 4
1, 2, 3, 4
BT120-HTR-02
SECURITY STORAGE
210
1.8
120 / 1 / 60
WALL
SURFACE
24 x 4 x 4
REMARKS
1.
BASIS OF DESIGN: KING KCV-1202
3. USED FOR FREEZE PROTECTION.
2.
SET THRM TO TURN UNIT ON AT 40
F. 4. MFG LINE VOLTAGE THRMOSTAT.
2021 WASHINGTON MECHANICAL CODE VENTILATION COMPLIANCE SCHEDULE
LOCATION
ROOM
ROOM AREA
PEOPLE
CFM OSA
REQUIRED
CFM OSA
SUPPLIED
CFM EA
REQUIRED
CFM EA
EXHAUSTED
REMARKS
CORE FACILITY
SECURITY OFFICE
345 SF
3
40
75
0
0
1
CORE FACILITY
SEC STORAGE
100 SF
0
0
25
0
0
1
CORE FACILITY
LACTATION
135 SF
1
15
75
0
50
1
CORE FACILITY
JANITOR
140 SF
0
0
50
140
150
1
CORE FACILITY
OPERATOR RESTROOM 07
100 SF
1
15
25
100
100
1,4
CORE FACILITY
OPERATOR RESTROOM 06
100 SF
1
15
25
100
100
1,4
CORE FACILITY
OPERATOR RESTROOM 05
100 SF
1
15
25
100
100
1,4
CORE FACILITY
OPERATOR RESTROOM 04
100 SF
1
15
25
100
100
1,4
CORE FACILTIY
ELECTRICAL ROOM
390 SF
0
0
100
0
0
CORE FACILITY
TELECOM AREA
445 SF
0
0
100
0
0
CORE FACILITY
STORAGE AREA 1
500 SF
0
0
50
0
0
3
REMARKS:
1. BASED OFF 2021 WASHINGTON MECHANICAL CODE TABLE 403.3.1.1
2. NOT USED.
3. NO AIR REQUESTED OR REQUIRED. NORMALLY UNOCCUPIED SPACE.
4. PRIVATE USE, SINGLE PERSON OCCUPANCY.
THERMOSTATS SCHEDULE
EQUIPMENT TAG
LOCATION
EQUIPMENT
CONTROLLED
MANUFACTURER
MODEL
TYPE
ARRANGEMENT
REMARKS
BT105-THRM-01
STORAGE 1
BT105-ACU-01
DAIKIN
DTST-TOU-ADA-A
WALL
SURFACE
1, 2, 3
BT105-THRM-02
ELECTRICAL ROOM
BT105-ACU-02
DAIKIN
DTST-TOU-ADA-A
WALL
SURFACE
1,2
BT105-THRM-03
ELECTRICAL ROOM
BT105-ACU-03
DAIKIN
DTST-TOU-ADA-A
WALL
SURFACE
1,2
BT105-THRM-04
TELECOM
BT105-ACU-04
DAIKIN
DTST-TOU-ADA-A
WALL
SURFACE
1,2
BT105-THRM-05
TELECOM
BT105-ACU-05
DAIKIN
DTST-TOU-ADA-A
WALL
SURFACE
1,2
BT105-THRM-16
OPERATOR RESTROOM 07
BT105-ACU-16
DAIKIN
DTST-ONE-ADA-A
WALL
SURFACE
1,2
BT105-THRM-26
OPERATOR RESTROOM 06
BT105-ACU-26
DAIKIN
DTST-ONE-ADA-A
WALL
SURFACE
1,2
BT105-THRM-36
OPERATOR RESTROOM 05
BT105-ACU-36
DAIKIN
DTST-ONE-ADA-A
WALL
SURFACE
1,2
BT105-THRM-46
OPERATOR RESTROOM 04
BT105-ACU-46
DAIKIN
DTST-ONE-ADA-A
WALL
SURFACE
1,2
BT105-THRM-56
LACTATION ROOM
BT105-ACU-56
DAIKIN
DTST-ONE-ADA-A
WALL
SURFACE
1,2
BT105-THRM-07
SECURITY OFFICE
BT105-ACU-07
DAIKIN
BRC1E73
WALL
SURFACE
1,2
BT105-THRM-11
JANITOR ROOM
BT105-HTR-01
KING
KCVT-1L-W
HTR UNIT
ACCESSORY
3,4
BT105-THRM-12
SECURITY STORAGE
BT105-HTR-02
KING
KCVT-1L-W
HTR UNIT
ACCESSORY
3,4
REMARKS
1. FROM HEAT PUMP MFG. 4. HTR MFG SINGLE POLE THRMOSTAT KIT.
2. HEATING AND COOLING RANGE BY CLIENT.
3. USED FOR FREEZE PROTECTION.
0 12/10/20241 DW I MP
No. DATE I DSN I CHK
JHS ISSUED FOR BID
APP REVISION
DESIGNED BY:
D. WONG
DRAWN BY:
L. GOUDEAU
CHECKED BY:
M. PHILLIPS
APPROVED BY:
J. SACKINGER
Y
WA,S�l��.�f'� 7
pacobs
A 30676
AL� SUBMITTED BY:
Signed: 12-10-2024 R. PARGAS
4STmRIDE
BRT General Engineering Consultant
DATE: REVIEWED BY:
12/10/2024 J. ALTCHECH
GRILLES AND DIFFUSERS
TAG
SG-1
SG-2
EG-1
EG-2
BRAND
TITUS
TITUS
TITUS
TITUS
MODEL
271 FS
271 FS
350ZFL
350ZFL
MATERIAL
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
DAMPER
OBD
OBD
AG-15 OBD
AG-15 OBD
FASTENING
EXTERNAL
EXTERNAL
EXTERNAL
EXTERNAL
MAX. PD AT CFM
0.1
0.1
0.1
0.1
MAX. NC AT CFM
REMARKS
32
32
32
32
A, C
A, B,
A, C
A, B
REMARKS
A. IF MOUNTED ON WALL THEN BLADES PARALLEL TO FLOOR.
B. DUCT MOUNTED, COLOR WHITE.
C. SURFACE MOUNTED, COLOR WHITE.
QUj
J
Q
�co
W J
Z J
SOUNDTRANSIT
DATE:
12/10/2024
SCALE:
NTS
FILENAME:
S1-BT120-MH-v2020
CONTRACT No.:
RTA/CN 0205-24
SUBMITTAL DATE:
12/10/2024
STRIDE BUS RAPID TRANSIT
SOUTH RENTON TRANSIT CENTER
BT105
MECHANICAL-HVAC
SCHEDULES
R-4332436
DEVELOPMENT ENGINEERING
msippo 11 /25/2025 01
DRAWING NO.:
BT120-MHS003
FACILITY ID:
BT105
SHEET No: REV:
514 0