BMS POINTS LIST
SYSTEM
EQUIPMENT TYPE
EQUIPMENT ID
SERVING AREA
PLC INPUT / OUTPUT DESCRIPTION
POINT TYPE
PLC TAG
BMS
NOTES
INDICATE/
ALARM
CONTROL
OUT PUT
HVAC
HEAT PUMP
BT120-ACU-01
ROOM TEMPERATURE SENSOR
ANALOG INPUT
X
TEMPERATURE MONITOR ROOM, DOES INTERFACE WITH EQUIPMENT
HVAC
HEAT PUMP
BT120-ACU-02, 03
ROOM TEMPERATURE SENSOR
ANALOG INPUT
X
TEMPERATURE MONITOR ROOM, DOES INTERFACE WITH EQUIPMENT
HVAC
HEAT PUMP
BT120-ACU-04, 05
ROOM TEMPERATURE SENSOR
ANALOG INPUT
X
TEMPERATURE MONITOR ROOM, DOES INTERFACE WITH EQUIPMENT
HVAC
HEAT PUMP
BT120-ACU-16
ROOM TEMPERATURE SENSOR
ANALOG INPUT
X
TEMPERATURE MONITOR ROOM, DOES INTERFACE WITH EQUIPMENT
HVAC
HEAT PUMP
BT120-ACU-26
ROOM TEMPERATURE SENSOR
ANALOG INPUT
X
TEMPERATURE MONITOR ROOM, DOES INTERFACE WITH EQUIPMENT
HVAC
HEAT PUMP
BT120-ACU-36
ROOM TEMPERATURE SENSOR
ANALOG INPUT
X
TEMPERATURE MONITOR ROOM, DOES INTERFACE WITH EQUIPMENT
HVAC
HEAT PUMP
BT120-ACU-46
ROOM TEMPERATURE SENSOR
ANALOG INPUT
X
TEMPERATURE MONITOR ROOM, DOES INTERFACE WITH EQUIPMENT
HVAC
HEAT PUMP
BT120-ACU-56
ROOM TEMPERATURE SENSOR
ANALOG INPUT
X
TEMPERATURE MONITOR ROOM, DOES INTERFACE WITH EQUIPMENT
HVAC
HEAT PUMP
BT120-ACU-07
ROOM TEMPERATURE SENSOR
ANALOG INPUT
X
TEMPERATURE MONITOR ROOM, DOES INTERFACE WITH EQUIPMENT
HVAC
HEATER
BT120-HTR-01
ROOM TEMPERATURE SENSOR
ANALOG INPUT
X
TEMPERATURE MONITOR ROOM, DOES INTERFACE WITH EQUIPMENT
HVAC
HEATER
BT120-HTR-02
ROOM TEMPERATURE SENSOR
ANALOG INPUT
X
TEMPERATURE MONITOR ROOM, DOES INTERFACE WITH EQUIPMENT
HVAC
VENTILATOR
BT120-ERU-01
DIRTY FILTER LOADING ALARM
ANALOG INPUT
X
ALARMS WHEN ONBOARD BMS CARD INDICATES DIRTY FILTER
HVAC
VENTILATOR
BT120-ERU-01
FAN PROVING ALARM
DIGITAL INPUT
X
ALARMS WHEN ONBOARD BMS CARD INDICATES FANS DID NOT PROVE
HVAC
VENTILATOR
BT120-ERU-01
MONITOR AIRFLOW RANGE
DIGITAL INPUT
X
ALARMS WHEN ONBOARD BMS CARD INDICATES AIRFLOW OUT OF RANGE
ELECTRICAL
UTILITY
MONITOR VOLTAGE AND FREQUENCY
ANALOG INPUT
X
ALARMS IF VOLTAGE OR FREQUENCY IS OUT OF RANGE
ELECTRICAL
GENERATOR
MONITOR VOLTAGE AND FREQUENCY
ANALOG INPUT
X
ALARMS IF VOLTAGE OR FREQUENCY IS OUT OF RANGE
ELECTRICAL
GENERATOR
COMMON WARNING ITEMS
DIGITAL INPUT
X
ALARMS IF COMMON WARNINGS ARE INDICATED
ELECTRICAL
GENERATOR
COMMON SHUTDOWN ITEMS
DIGITAL INPUT
X
ALARMS IF UNWANTED SHUTDOWN OCCURS
LIGHTING
ELECTRICAL ROOM
LIGHTING CONTROL PANEL
TBD
X
MONITOR LIGHTING CONTROL PANEL
LIGHTING
BUS BAY
LIGHTING CONTROL PANEL
TBD
X
MONITOR LIGHTING CONTROL PANEL
LIGHTING
CHARGING YARD
LIGHTING CONTROL PANEL
TBD
X
MONITOR LIGHTING CONTROL PANEL
GENERAL NOTES:
1. SEE DWG BT120-MHS005 - MHS007 AND MHS010 COMMUNICATION SET FOR BMS CONTROLLER DETAILS, CABLES AND TAGS LOCATION.
2. SEE THE CONTROLS NETWORK DIAGRAM BT120-MHS006 FOR SENSOR AND DEVICE CONNECTIONS. ADD POINTS OR DEVICES AS REQUIRED FOR A COMPLETE SYSTEM.
0 1 12/10/2024 I DW I MP I JHS I ISSUED FOR BID
No. I DATE I DSN I CHK I APP I REVISION
DESIGNED BY:
D. WONG
DRAWN BY:
L. GOUDEAU
CHECKED BY:
M. PHILLIPS
APPROVED BY:
J. SACKINGER
/mow o� wA ��',�t
30676
�0�' ��GISTEgFO- Fv
ESS1oN
Signed: 12-10-2024
.;acobs
SUBMITTED BY:
R. PARGAS
4STmRIDE
BRT General Engineering Consultant
DATE: REVIEWED BY:
12/10/2024 J. ALTCHECH
Q w
Q
cn �
W J
J
z SOUNDTRANSIT
DATE:
12/10/2024
SCALE:
NTS
FILENAME:
S1-BT120-MH-v2020
CONTRACT No.:
RTA/CN 0205-24
SUBMITTAL DATE:
12/10/2024
STRIDE BUS RAPID TRANSIT
SOUTH RENTON TRANSIT CENTER
BT105
MECHANICAL-HVAC
BMS POINTS LIST
CORE FACILITY
R-4332437
DEVELOPMENT ENGINEERING
msippo 11 /25/2025 Ul
DRAWING NO.:
BT120-MHS005
FACILITY ID:
BT105
SHEET No: REV:
515 0