Loading...
HomeMy WebLinkAboutR-4332440N C'7 C'7 0 LU 0 N 0 N 0 N H m V1 U w C� H I V) Z Q ry H I c) d ry I D m 0 I 0 co 00 LO d 0 N I N >Q CD U) 0 0 o cy) N m BMS POINTS LIST SYSTEM EQUIPMENT TYPE EQUIPMENT ID BMS 1/0 DESCRIPTION POINT TYPE BMS NOTES INDICATE/ ALARM CONTROL OUTPUT ELECTRICAL LIGHTING CONTROL PANEL BT105-LCP-01 STATUS DV X THE PACKAGED LIGHTING CONTROL PANEL SHALL COMMUNICATE WITH THE BMS THROUGH THE BACNET INTERFACE. THE BMS SHALL MONITOR THESE POINTS FOR EACH LIGHTING CIRCUIT/ZONE ON THE LIGHTING CONTROL PANEL. ELECTRICAL LIGHTING CONTROL PANEL BT105-LCP-01 SCHEDULE AV X THE PACKAGED LIGHTING CONTROL PANEL SHALL COMMUNICATE WITH THE BMS THROUGH THE BACNET INTERFACE. THE BMS SHALL MONITOR THESE POINTS FOR EACH LIGHTING CIRCUIT/ZONE ON THE LIGHTING CONTROL PANEL. ELECTRICAL LIGHTING CONTROL PANEL BT105-LCP-02 STATUS DV X THE PACKAGED LIGHTING CONTROL PANEL SHALL COMMUNICATE WITH THE BMS THROUGH THE BACNET INTERFACE. THE BMS SHALL MONITOR THESE POINTS FOR EACH LIGHTING CIRCUIT/ZONE ON THE LIGHTING CONTROL PANEL. ELECTRICAL LIGHTING CONTROL PANEL BT105-LCP-02 SCHEDULE AV X THE PACKAGED LIGHTING CONTROL PANEL SHALL COMMUNICATE WITH THE BMS THROUGH THE BACNET INTERFACE. THE BMS SHALL MONITOR THESE POINTS FOR EACH LIGHTING CIRCUIT/ZONE ON THE LIGHTING CONTROL PANEL. ELECTRICAL LIGHTING CONTROL PANEL BT105-LCP-03 STATUS DV X THE PACKAGED LIGHTING CONTROL PANEL SHALL COMMUNICATE WITH THE BMS THROUGH THE BACNET INTERFACE. THE BMS SHALL MONITOR THESE POINTS FOR EACH LIGHTING CIRCUIT/ZONE ON THE LIGHTING CONTROL PANEL. ELECTRICAL LIGHTING CONTROL PANEL BT105-LCP-03 SCHEDULE AV X THE PACKAGED LIGHTING CONTROL PANEL SHALL COMMUNICATE WITH THE BMS THROUGH THE BACNET INTERFACE. THE BMS SHALL MONITOR THESE POINTS FOR EACH LIGHTING CIRCUIT/ZONE ON THE LIGHTING CONTROL PANEL. ELECTRICAL UPS BT105-UPS-01 BMS INTERFACE AV/DV X THE PACKAGED CONTROLLER SHALL COMMUNICATE WITH THE BMS THROUGH THE BACNET INTERFACE. THE BMS SHALL MONITOR THESE POINTS. ELECTRICAL UPS BT105-UPS-01 STATUS DV X THE PACKAGED CONTROLLER SHALL COMMUNICATE WITH THE BMS THROUGH THE BACNET INTERFACE. THE BMS SHALL MONITOR THESE POINTS. ELECTRICAL UPS BT105-UPS-01 GENERAL ALARM DV X THE PACKAGED CONTROLLER SHALL COMMUNICATE WITH THE BMS THROUGH THE BACNET INTERFACE. THE BMS SHALL MONITOR THESE POINTS. ELECTRICAL ATS BT105-ATS-01 BMS INTERFACE AV/DV X THE PACKAGED ATS CONTROLLER SHALL COMMUNICATE WITH THE BMS THROUGH THE BACNET INTERFACE. THE BMS SHALL MONITOR THESE POINTS AT A MINIMUM. ELECTRICAL ATS BT105-ATS-01 ATS-UTILITY POSITION DV X THE PACKAGED ATS CONTROLLER SHALL COMMUNICATE WITH THE BMS THROUGH THE BACNET INTERFACE. THE BMS SHALL MONITOR THESE POINTS AT A MINIMUM. ELECTRICAL ATS BT105-ATS-01 UTILITY POWER AVAILABLE AV X THE PACKAGED ATS CONTROLLER SHALL COMMUNICATE WITH THE BMS THROUGH THE BACNET INTERFACE. THE BMS SHALL MONITOR THESE POINTS AT A MINIMUM. ELECTRICAL ATS BT105-ATS-01 STANDBY POWER AVAILABLE AV X THE PACKAGED ATS CONTROLLER SHALL COMMUNICATE WITH THE BMS THROUGH THE BACNET INTERFACE. THE BMS SHALL MONITOR THESE POINTS AT A MINIMUM. ELECTRICAL ATS BT105-ATS-01 ATS-STANDBY POSITION DV X THE PACKAGED ATS CONTROLLER SHALL COMMUNICATE WITH THE BMS THROUGH THE BACNET INTERFACE. THE BMS SHALL MONITOR THESE POINTS AT A MINIMUM. ELECTRICAL ATS BT105-ATS-01 ATS FAIL DV X THE PACKAGED ATS CONTROLLER SHALL COMMUNICATE WITH THE BMS THROUGH THE BACNET INTERFACE. THE BMS SHALL MONITOR THESE POINTS AT A MINIMUM. ELECTRICAL POWER QUALITY METER BT105-SWGR-01 BMS INTERFACE AV/DV X THE PACKAGED CONTROLLER SHALL COMMUNICATE WITH THE BMS THROUGH THE BACNET INTERFACE. THE BMS SHALL MONITOR THESE POINTS. ELECTRICAL GENERATOR BT105-GEN-01 BMS INTERFACE AV/DV X THE PACKAGED CONTROLLER SHALL COMMUNICATE WITH THE BMS THROUGH THE BACNET INTERFACE. THE BMS SHALL MONITOR THESE POINTS. NOTES: Al = ANALOG INPUT, AO = ANALOG OUTPUT, DI = DIGITAL INPUT, DO - DIGITAL OUTPUT. AV = ANALOG POINT THOUGH BACNET INTERFACE / PACKAGED CONTROLLER. DV = DIGITAL POINT THROUGH BACNET INTERFACE / PACKAGED CONTROLLER. GENERAL NOTES: 1. SEE DWG BT120-MHS005 - MHS007 AND MHS010 COMMUNICATION SET FOR BMS CONTROLLER DETAILS, CABLES AND TAGS LOCATION. 2. SEETHE CONTROLS NETWORK DIAGRAM BT120-MHS006 FOR SENSOR AND DEVICE CONNECTIONS. ADD POINTS OR DEVICES AS REQUIRED FOR A COMPLETE SYSTEM. 0 1 12/10/2024 I DW I MP I JHS I ISSUED FOR BID No. I DATE I DSN I CHK I APP I REVISION DESIGNED BY: M. LUCERO DRAWN BY: R. PREWITT CHECKED BY: J.BEAUDRY APPROVED BY: J. SACKINGER 30676 ESS1oN Signed: 12-10-2024 .;acobs SUBMITTED BY: R. PARGAS 4STmRIDE BRT General Engineering Consultant DATE: REVIEWED BY: 12/10/2024 J. ALTCHECH Q w Q cn � W J J z " SOUNDTRANSIT DATE: 12/10/2024 SCALE: NTS FILENAME: S1-BT120-MH-v2020 CONTRACT No.: RTA/CN 0205-24 SUBMITTAL DATE: 12/10/2024 STRIDE BUS RAPID TRANSIT SOUTH RENTON TRANSIT CENTER BT105 MECHANICAL-HVAC CONTROLS SCHEDULE CORE FACILITY R-4332440 DEVELOPMENT ENGINEERING msippo 11 /25/2025 Ul DRAWING NO.: BT120-MHS010 FACILITY ID: BT105 SHEET No: REV: 518 0