KEY NOTES:
119 MOUNT GFCI RECEPTACLES HORIZONTALLY ABOVE COUNTER AT 36" 301
AFF.
ATTACH PHOTOCELL TO HORIZONTAL SUPPORT AT 11' ABOVE
FINISHED GRADE, UNDER THE CANOPY WITH SENSOR AIMED NORTH.
120 LOCATE DISCONNECT SWITCH BENEATH TANKLESS WATER HEATER. 303 ATTACH PHOTOCELL TO EXTERIOR WALL AT 11' ABOVE FINISHED
SEE PLUMBING PLANS DETAIL 6/BT120-MPD001. GRADE WITH SENSOR AIMED NORTH.
121 INSTALL RECEPTACLES TO BOTTOM SIDE OF CABLE TRAY. 304
COORDINATE WITH DIV 27 CONTRACTOR INSTALLING THE CABLE
TRAY. TYPICAL OF RACK RECEPTACLES IN ALL IT ROOMS.
CONNECT PHOTOCELL TO PANEL BT120-LCP-01 USING CAT6 CABLE
RUN IN 3/4" CONDUIT.
305
CONNECT PHOTOCELL TO PANEL BT120-LCP-02 USING CAT6 CABLE
122
PROVIDE 5/8" X 10' COPPER GROUND ROD IN LIGHTING HANDHOLES
RUN IN 3/4" CONDUIT.
LOCATED IN THE SCL EASEMENT AREA UNDER POWER LINES. BOND
WITH #6 GND TO LIGHT POLE.
307
PENDANT MOUNT FIXTURE(S) TO HANG 10' 0" AFF FROM TOP OF
FIXTURE.
123
INDOOR UNIT POWERED BY OUTDOOR UNIT. PROVIDE 4-WIRE #14 AWG
CABLE BETWEEN INDOOR AND OUTDOOR MECHANICAL UNIT. SEE
308
PENDANT MOUNT FIXTURES TO HANG 8' 0" AFF FROM TOP OF
MECHANICAL SHEET BT120-MHS002 PLANS FOR INDOOR/OUTDOOR
FIXTURE.
UNIT PAIRING.
O124
INDOOR UNIT POWERED BY BT120-HPMP-06 BRANCH UNIT. PROVIDE
309
PENDANT MOUNT FIXTURES TO HANG 8' 6" AFF FROM TOP OF
FIXTURE.
3#14 AWG PLUS #14 AWG GND CABLE BETWEEN INDOOR UNIT AND
BRANCH UNIT. SEE MECHANICAL SHEET BT120-MHS001 FOR
CONNECTION SCHEMATIC.
310
USE CHASE PROVIDED BY STRUCTURAL AT COLUMNS FOR LIGHTING
CONDUIT. SEE POWER SHEET BT120-EPP212 THROUGH BT120-EPP214
FOR CONDUIT PLAN.
12
THE LIGHTNING PROTECTION SYSTEM IS A DEFERRED DESIGN BY THE
LIGHTNING PROTECTION SYSTEM CONTRACTOR. PROVIDE LIGHTNING
PROTECTION SYSTEM. SEE SPECIFICATIONS FOR ADDITIONAL
311
MOUNT FIXTURE SO IT IS MOUNTED 8' 0" AFG. COORDINATE WITH
REQUIREMENTS.
ARCHITECTURE.
130
480V LIGHTING CIRCUITS TO INDIVIDUALLY FEED THROUGH SEPARATE
312
MOUNT FIXTURE SO IT IS MOUNTED 10' 0" AFG. COORDINATE WITH
LIGHTING CONTROLLER CONTACTORS.
ARCHITECTURE.
131
120V LIGHTING CIRCUITS TO INDIVIDUALLY FEED THROUGH SEPARATE
313
TERMINATE AND CAP CONDUIT UNDERGROUND FOR FUTURE USE.
LIGHTING CONTROLLER CONTACTORS.
PROVIDE MARKING SIGN ABOVE GRADE DENOTING THE BURIED
CONDUIT END LOCATIONS.
132
ALL SITE LIGHTING CIRCUITS TO PANEL BT120-PB4-01 ON THIS SHEET.
133
CONDUIT STUB UP THROUGH COLUMN RACEWAY FOR LIGHTING AND
VMS SIGNAGE.
13
2'X2' PIECE OF 3/4" PLYWOOD MOUNTED 5' AFF FOR PSE AMR/AMI
REPEATER. PROVIDE DEDICATED 120V RECEPTACLE BELOW
PLYWOOD.
138
8"X8"X6" NEMA 3R ENCLOSURE FOR PSE ANTENNA. MOUNT ON
OUTSIDE WALL 8' TO 10' ABOVE FINISHED GRADE.
139
PROVIDE 2" CONDUIT FROM NEMA 3R ENCLOSURE STUBBED INTO
ELECTRICAL ROOM ABOVE PLYWOOD BOARD.
140 PROVIDE GROUNDING FOR FENCE AT FENCE END POSTS, POSTS
EVERY 160 FEET, AND POSTS ON EACH SIDE OF AN SCL OVERHEAD
LINE. SEE SHEET BT120-EPD111 FOR GROUNDING DETAIL.
141 CONDUIT GROUP INCLUDES CONDUIT TAGS: BT120-N4-202,
BT120-E4-202A, BT120-E4-202B, BT120-N2-201, BT120-SC-203,
BT120-SC-204.
142 CONDUIT GROUP INCLUDES CONDUIT TAGS: BT120-E4-201A,
BT120-E4-201 B, BT120-E4-203, BT120-SC-201, BT120-SC-202,
BT120-N2-202.
143 CONDUIT GROUP INCLUDES CONDUIT TAGS: BT120-N4-201A AND
BT120-N4-201 B.
144 PROVIDE RECEPTACLE FOR FLOOD CONTROL SYSTEM. COORDINATE
EXACT LOCATION WITH PLUMBING CONTRACTOR PRIOR TO ROUGH -IN.
14 CONTRACTOR TO INSTALL CONDUIT TO EXISTING SERVICE TAP
LOCATION AND TERMINATE CONDUIT PER PSE REQUIREMENTS.
CONTRACTOR WILL NEED TO COORDINATE CONDUIT TERMINATION
REQUIREMENTS WITH PSE PRIOR TO INSTALLATION OF 4"C AND 2/0
SVC CABLE.
148 CONTRACTOR SHALL FURNISH AND INSTALL THE DUAL EV CHARGER.
THE DUAL EV CHARGER SHALL BE CHARGEPOINT CT4021 DUAL PORT K2
BOLLARD MOUNT.
149 ALL PSE TRANSFORMER AND VAULTS PROVIDED BY PSE.
CONTRACTOR SHALL COORDINATE EXCAVATION OF VAULT PITS WITH
PSE SERVICE DRAWING.
DESIGNED BY:
D. TAFTFARREN
DRAWN BY:
E. HAJAS
2
06/27/2025
EH
DA
DT
ADDENDUM #2
CHECKED BY:
1
06/13/2025
EH
DA
DT
ADDENDUM #1
D. ANDERSON
0
12/10/2024
EH
DA
DT
ISSUED FORBID
APPROVED BY:
No.
DATE
DSN
CHK
APP
REVISION
D. TAFTFARREN
.;acobs
SUBMITTED BY:
6127125 R. PARGAS
1
DATE:
12/10/2024
Q w
STmRIDE U
U) C/)
W J
BRT General Engineering Consultant z LL
REVIEWED BY:
J. ALTCHECH
SCALE:
M;Vmr=" NTS
FILENAME:
S 1-BT120-E-v2020
SOUNDTRANSIT CONTRACT No.:
RTA/CN 0205-24
DATE: SUBMITTAL DATE:
12/10/2024 12/10/2024
STRIDE BUS RAPID TRANSIT
SOUTH RENTON TRANSIT CENTER
BT105
ELECTRICAL
PROJECT KEYNOTE LIST
R-4332445
DEVELOPMENT ENGINEERING
msippo 11 /25/2025
DRAWING NO.:
BT120-EPNO04
FACILITY ID:
BT120
SHEET No: REV:
523 2