HomeMy WebLinkAbout02-17-2026 - Addendum No. 1 - Sr Center HVAC RoofBCRA
2106 Pacific Avenue, Suite 300
Tacoma, Washington 98402
(253) 627-4367
ADDENDUM NO. 1 PAGE 1 OF 1
Don Persson Renton Senior Activity Center: Exterior & HVAC Improvements
City of Renton (CAG-26-032)
February 17, 2026
City of Renton
Don Persson Renton Senior Activity Center
Exterior & HVAC Improvements
(CAG-26-032)
Renton, WA
ADDENDUM NO. 1
February 17, 2026
This Addendum forms a part of the Contract Documents and modifies the original Contract
Documents dated January 16, 2026 as noted below. Acknowledge receipt of this Addendum In the
space provided on the Bid Form. Failure to do so may subject Bidder to disqualification.
This Addendum is issued to all known Plan Holders.
This Addendum consists of 1 page plus attachments.
ATTACHMENTS
NOTE: Addendum changes to the Specification section is issued as a full specification section;
these changes are noted by BOLD/bold type.
1. City of Renton Prebid Conference Site Walk – Sign In Sheet
2. Specification Section 23 7416 PACKAGED ROOFTOP AIR-CONDITIONING UNITS
SPECIFICATIONS
SECTION 23 7416 – PACKAGED ROOFTOP AIR-CONDITIONING UNITS
1. REPLACE section 23 7416 in it’s entirety.
END OF ADDENDUM NO. 1
Renton Senior Activity Center
HVAC, Roof & Ext. Siding Replacement (CAG-25-247)
Construction Documents – January 16, 2026
BCRA Project No. 25040.00.00
23 7416 - 1
PACKAGED ROOFTOP AIR-
CONDITIONING UNITS
SECTION 23 7416
PACKAGED ROOFTOP AIR-CONDITIONING UNITS
PART 1 - GENERAL
1.01 SECTION INCLUDES
A. Packaged Rooftop Unitary Air Conditioners.
B. Unit Controls – Systems Integration
1.02 RELATED REQUIREMENTS
A. Section 23 0548 - Vibration and Seismic Controls for HVAC Piping and
Equipment.
B. Section 23 0993 – Sequence of Operations for HVAC Controls.
1.03 REFERENCE STANDARDS
A. AHRI 210/240 - Standard for Performance Rating of Unitary Air Conditioning and
Air-Source Heat Pump Equipment; Air-Conditioning, Heating, and Refrigeration
Institute.
B. AHRI 270 - Sound Rating of Outdoor Unitary Equipment; Air-Conditioning,
Heating, and Refrigeration Institute.
C. NFPA 90A - Standard for the Installation of Air-Conditioning and Ventilation
Systems; National Fire Protection Association.
D. Reference standards shall be the latest revision as accepted by the local
Authority Having Jurisdiction.
1.04 PERFORMANCE REQUIREMENTS
A. Electric Heating: See schedule.
B. Supply Air: See schedule.
C. Return Air: See schedule.
D. Electric cooling: See schedule.
1.05 SUBMITTALS
A. Refer to Section 01 3300 for submittal procedures.
Renton Senior Activity Center
HVAC, Roof & Ext. Siding Replacement (CAG-25-247)
Construction Documents – January 16, 2026
BCRA Project No. 25040.00.00
23 7416 - 2
PACKAGED ROOFTOP AIR-
CONDITIONING UNITS
B. BABAA Documentation: Provide letter from manufacturer(s) certifying that all
products provided under this Section conform to the requirements of the Build
America, Buy America Act (BABAA); refer to Section 01 6000 Product
Requirements for additional information.
C. Product Data: Provide capacity and dimensions of manufactured products and
assemblies required for this project. Indicate electrical service with electrical
characteristics and connection requirements and duct connections.
D. Shop Drawings: Indicate capacity and dimensions of manufactured products and
assemblies required for this project. Indicate electrical service with electrical
characteristics and connection requirements and duct connections.
E. Manufacturer's Instructions: Indicate assembly, support details, connection
requirements, and include start-up instructions.
F. Operation and Maintenance Data: Include manufacturer's descriptive literature,
operating instructions, installation instructions, maintenance and repair data, and
parts listing.
G. Warranty: Submit manufacturer's warranty and ensure forms have been filled out
in Owner's name and registered with manufacturer.
1.06 QUALITY ASSURANCE
A. Perform work in accordance with applicable codes.
B. Products specified in this section shall be manufactured in the United States of
America. Products shall be labeled with the manufacturer's logo and country of
origin. This paragraph will be strictly enforced; contractors shall bid on this
project accordingly.
C. Manufacturer Qualifications: Company specializing in manufacturing the type of
products specified in this section, with a minimum of five years of documented
experience.
D. Products Requiring Electrical Connection: Listed and classified by Underwriters
Laboratories Inc. as suitable for the purpose specified and indicated.
1.07 DELIVERY, STORAGE, AND HANDLING
A. Protect units from physical damage by storing them off site until roof mounting
curbs are in place, ready for immediate installation of units.
1.08 WARRANTY
A. Provide a two (2) year manufacturer’s warranty on units, covering parts and
labor.
Renton Senior Activity Center
HVAC, Roof & Ext. Siding Replacement (CAG-25-247)
Construction Documents – January 16, 2026
BCRA Project No. 25040.00.00
23 7416 - 3
PACKAGED ROOFTOP AIR-
CONDITIONING UNITS
PART 2 - PRODUCTS
2.01 BUILD AMERICA, BUY AMERICA ACT (BABAA) REQUIREMENTS
A. Products shall comply with the requirements of the Build America, Buy America
Act (BABAA), refer to Section 01 6000 Product Requirements for additional
information.
2.02 MANUFACTURERS
A. Trane
B. JCI, Johnson Controls International
C. Approved Equal
2.03 PACKAGED ROOFTOP UNITS
A. Outdoor, rooftop mounted, electrically controlled, electric heating and cooling unit
utilizing a fully hermetic, suction gas cooled, direct drive compressor(s) for
cooling duty and gas combustion or for heating duty.
B. Description: Factory assembled, single-piece heating and cooling rooftop unit.
Contained within the unit enclosure shall be all factory wiring, piping, controls,
and special features required prior to field start- up.
C. Unit shall use environmentally sound, R-454b refrigerant.
D. Units shall be installed in accordance with the manufacturer’s instructions.
E. Units must be selected and installed in compliance with local, state, and federal
codes.
F. Unit meets ASHRAE 90.1 minimum efficiency requirements.
G. Unit shall be rated in accordance with AHRI Standards 210/240 or 340/360.
H. Unit shall be designed to conform to ASHRAE 15.
I. Unit shall be CSA tested and certified in accordance with ANSI Z21.47 -
2016/CSA 2.3-2016, and CSA C22.2 No. 60335-2-40.
J. Insulation and adhesive shall meet NFPA 90A requirements for flame spread and
smoke generation.
K. Unit casing shall be capable of withstanding 750- hour salt spray exposure per
ASTM B117 (scribed specimen).
Renton Senior Activity Center
HVAC, Roof & Ext. Siding Replacement (CAG-25-247)
Construction Documents – January 16, 2026
BCRA Project No. 25040.00.00
23 7416 - 4
PACKAGED ROOFTOP AIR-
CONDITIONING UNITS
L. Unit shall be subjected to a completely automated run test on the assembly line.
The data for each unit will be stored at the factory and must be available upon
request.
M. Unit shall be designed in accordance with CSA C.22.2 NO.60335-2-40, including
tested to withstand rain.
N. Unit shall be constructed to prevent intrusion of snow into the control.
O. Electrical Characteristics: See schedule.
2.04 OPERATING CHARACTERISTICS:
A. Unit shall be capable of starting and running at 115°F (52°C) ambient outdoor
temperature, meeting maximum load criteria of AHRI Standard 210/240 or
340/360 at 10% voltage.
B. Compressors with standard controls shall be capable of operation down to 45°F
(7°C), ambient outdoor temperatures. Intermittent cooling shall be operational
down 0° F (-17° C). Low ambient kit is necessary if mechanically cooling at
ambient temperatures below 40°F (4°C).
C. Unit shall be factory configured for vertical supply & return configurations.
2.05 FABRICATION
A. Cabinet: Unit cabinet shall be constructed of galvanized steel with exterior
surfaces coated with a non-chalking, powder paint finish, certified at 750-hour
salt spray test per ASTM-B117 standards.
B. Unit cabinet exterior paint: film thickness, (dry) 3.0 MILS minimum, gloss (per
ASTM D523, 60°F / 16°C): 80+/-5, Hardness: H- 2H Pencil hardness.
C. Unit cabinet shall have electric utility entry locations marked from the factory with
a dimple for accuracy of field drilling. Entry locations shall be available for entry
through the side of the unit or from the unit underside.
D. Base Rail:
1. Unit shall have base rails on all 4 sides.
2. Holes shall be provided in the base rails for rigging shackles to facilitate
maneuvering and overhead rigging.
3. Holes shall be provided in the base rail for moving the unit by fork truck.
4. Base rail shall be a minimum 15-gauge thickness.
E. Top Panel:
Renton Senior Activity Center
HVAC, Roof & Ext. Siding Replacement (CAG-25-247)
Construction Documents – January 16, 2026
BCRA Project No. 25040.00.00
23 7416 - 5
PACKAGED ROOFTOP AIR-
CONDITIONING UNITS
1. Shall be a multi piece top panel.
F. Supply Fan: Forward curved centrifugal type, resiliently mounted with V-belt
drive, adjustable variable pitch motor pulley, and rubber isolated hinge mounted
high efficiency motor or direct drive as indicated. Isolate complete fan assembly.
Refer to Section 23 05 48.
G. Air Filters: As noted on schedule.
H. Roof Mounting: Refer to drawings for mounting conditions and or types. Unit shall
be provided with manufacturer’s matching roof curb.
I. Electrical Connections:
1. All unit power wiring shall enter unit cabinet through a field drilled hole
located by a factory provided dimple.
2. Standard unit shall have a through- the- base electrical location(s) using a
raised, embossed portion of the unit base-pan.
2.06 ELECTRIC HEAT
A. General:
1. Use nickel chromium elements for heating.
2. Shall have a single stage of capacity on 3 kW through 9 kW heaters and
two stages of capacity for all other heater sizes.
3. Shall have a primary limit control with automatic reset to prevent the
heating element system from operating at an excessive temperature.
4. Heating section assembly shall slide out of the unit for easy maintenance
and service.
5. Shall be wired for single point power supply with branch circuit fusing
(where required).
2.07 COILS:
A. Evaporator Coils, Aluminum Fin - Copper Tube:
1. Standard evaporator coils shall have aluminum plate fins mechanically
bonded to seamless internally grooved copper tubes with all joints
brazed.
2. Provide copper tube aluminum fin coil assembly with galvanized drain
pan and connection.
Renton Senior Activity Center
HVAC, Roof & Ext. Siding Replacement (CAG-25-247)
Construction Documents – January 16, 2026
BCRA Project No. 25040.00.00
23 7416 - 6
PACKAGED ROOFTOP AIR-
CONDITIONING UNITS
3. Provide capillary tubes or thermostatic expansion valves for units of 6
tons capacity and less, and thermostatic expansion valves and alternate
row circuiting for units 7.5 tons cooling capacity and larger.
4. Shall be leak tested to 150 psig, pressure tested to 250 psig, and burst
qualified to CSA C22.2 No. 60335-2-40.
5. Assembled unit shall be pressure tested to 450 psig.
B. Condenser Coils, All Aluminum Microchannel:
1. Condenser coils shall have all aluminum microchannel design consisting
of aluminum multiport flat tube design and aluminum fin. Coils shall be a
furnace brazed design and contain epoxy lined shrink wrap on all
aluminum to copper connections.
2. Microchannel condenser coils shall be leak tested to 150 psig, pressure
tested by supplier to 600 psig, and burst qualified to CSA C22.2 No.
60335-2-40.
3. Provide direct drive propeller fans, resiliently mounted with fan guard,
motor overload protection, wired to operate with compressor. Provide
high efficiency fan motors.
4. Provide refrigerant pressure switches to cycle condenser fans.
5. Assembled unit shall be pressure tested to 450 psig.
2.08 REFRIGERANT CIRCUITS
A. Refrigerant circuit shall include the following control, safety, and maintenance
features:
1. Thermostatic Expansion Valve (TXV) shall help provide optimum
performance across the entire operating range.
2. Refrigerant filter drier - Solid core design.
3. Service gauge connections on suction and discharge lines.
B. Compressors
1. Unit shall use fully hermetic scroll compressors for each independent
refrigeration circuit.
2. Compressor motors shall be cooled by refrigerant gas passing through
motor windings.
3. Compressors shall be internally protected from high discharge
temperature conditions.
Renton Senior Activity Center
HVAC, Roof & Ext. Siding Replacement (CAG-25-247)
Construction Documents – January 16, 2026
BCRA Project No. 25040.00.00
23 7416 - 7
PACKAGED ROOFTOP AIR-
CONDITIONING UNITS
4. Compressors shall be protected from an over- temperature and over-
amperage conditions by an internal, motor overload device.
5. Compressor shall be factory mounted on rubber grommets.
6. Crankcase heaters shall be installed in the factory as needed on tandem
compressor sets.
7. For heat pump units, provide reversing valve, suction line accumulator,
discharge muffler, flow control check valve, and solid-state defrost control
utilizing thermistors.
2.09 REFRIGERATION DETECTION SYSTEM
A. Unit shall have Refrigerant detection system that activates upon detection of
refrigerant above minimum threshold. The RDS shall connect to unit controls
and automatically start a sequence to dilute refrigerant gas as well as raise an
alarm when it senses the presence of refrigerant in the cabinet. The RDS shall
contain factory-installed sensors that are located to ensure accurate and timely
sensing of refrigerant.
2.10 EVAPORATOR FAN AND MOTOR
A. Evaporator fan motor:
1. Shall have permanently lubricated ball-bearings.
2. Shall have inherent automatic- reset thermal overload protection.
3. The job site selected brake horsepower shall be required to not exceed
the motor’s nameplate horsepower rating plus the service factor.
B. Evaporator Fan:
1. Forward curved centrifugal type, resiliently mounted with V-belt drive,
adjustable variable pitch pulley, and rubber isolated hinge mounted.
Provide with high efficiency motor or direct drive as indicated. Isolate
complete fan assembly.
2. Blower bearings shall have an L10 life of 100,000 hrs
3. Shall use sealed, permanently lubricated ball-bearing type.
4. Shall be constructed from steel with a corrosion resistant finish and
dynamically balanced.
2.11 CONDENSER FAN AND MOTORS
A. Condenser fan motors:
Renton Senior Activity Center
HVAC, Roof & Ext. Siding Replacement (CAG-25-247)
Construction Documents – January 16, 2026
BCRA Project No. 25040.00.00
23 7416 - 8
PACKAGED ROOFTOP AIR-
CONDITIONING UNITS
1. Shall be a totally enclosed motor.
2. Shall use permanently lubricated ball-bearings.
3. Shall have inherent thermal overload protection with an automatic reset
feature.
4. Shall use a shaft- down design.
B. Condenser Fans:
1. Shall be a direct- driven propeller type fan.
2.12 POWERED EXHAUST
A. Propeller Powered Exhaust:
1. Power exhaust shall be used in conjunction with an integrated
economizer.
2. Horizontal power exhaust shall be mounted in return ductwork.
3. Power exhaust shall be controlled by economizer controller operation.
Exhaust fans shall be energized when dampers open past the 0-100%
adjustable set point on the economizer control
2.01 MIXED AIR CASING
A. Dampers: Provide outside, return, and relief dampers with motorized damper
operator to provide full modulating economizer operation.
B. Gaskets: Provide tight fitting dampers with edge gaskets and side seals,
maximum leakage 5 percent at 2" pressure differential.
C. Damper Operator: 24 volt with gear train sealed in oil.
D. Controls: See Section 23 0913.
2.02 STANDARD FILTER SECTION
A. Shall consist of factory installed, low velocity, disposable 2- in. thick fiberglass
filters of commercially available sizes.
B. Units can accept 2” or 4” filters and have a field convertible transition.
C. Filters shall be accessible through an access panel; hinged panel with toolless
access is available as described in the Special Features Options and
Accessories section of this specification.
Renton Senior Activity Center
HVAC, Roof & Ext. Siding Replacement (CAG-25-247)
Construction Documents – January 16, 2026
BCRA Project No. 25040.00.00
23 7416 - 9
PACKAGED ROOFTOP AIR-
CONDITIONING UNITS
2.03 SPECIAL FEATURES OPTIONS & ACCESSORIES
A. Low Leak Economizer:
1. Integrated, tie-bar driven parallel modulating blade design type capable of
simultaneous economizer and compressor operation.
2. Damper blades shall be galvanized steel with tie-bar metal linkages.
Plastic or composite blades on intake or return shall not be acceptable.
3. Damper blades shall be class 1A dampers.
4. Shall include all hardware and controls to provide free cooling with
outdoor air when temperature and/or humidity are below set points.
5. Shall be equipped with tie-bar driven dampers for both the outdoor
ventilation air and the return air for positive air stream control.
6. Economizers shall comply with, and be certified to, the AMCA 511
standard.
7. Standard leak rate shall be equipped with dampers not to exceed 3
cfm/ft2 leakage at 1 in. wg pressure differential.
8. Economizer controller shall be the Johnson Controls SE Economizer
Controller.
a. On-board Fault Detection and Diagnostics (FDD) that senses and
alerts when the economizer is not operating properly, meets the
requirements for California Title 24, IECC 2015, and ASHRAE
90.1.
b. Display alarms if the following occur:
1) Economizers are economizing when conditions do not
support.
2) Economizers are not economizing when conditions do
support.
3) Damper Stuck.
4) Excess Outdoor Air.
5) Failed Sensor.
c. Automatic sensor detection.
d. Capabilities for use with multiple-speed indoor fan systems.
Renton Senior Activity Center
HVAC, Roof & Ext. Siding Replacement (CAG-25-247)
Construction Documents – January 16, 2026
BCRA Project No. 25040.00.00
23 7416 - 10
PACKAGED ROOFTOP AIR-
CONDITIONING UNITS
e. Utilize digital sensors: Dry bulb and Enthalpy.
f. UL, CSA, and ICES-003 recognized and FCC compliant to
CFR47.
9. Shall be capable of introducing up to 100% outdoor air.
10. Shall be equipped with powered exhaust capable of relieving up to 100%
return air and contain seals that meet ASHRAE 90.1 requirements.
11. Shall be designed to close damper(s) during loss- of- power situations
with spring return built into motor.
12. Dry bulb outdoor air temperature sensor shall be provided as standard.
Single or dual enthalpy sensing is available as a factory or field installed
sensing option. Outdoor air sensor set point shall be adjustable and shall
range from 40° to 80°F / 4° to 27°C. Additional sensor options shall be
available as accessories.
13. The economizer controller shall also provide control of an accessory
power exhaust unit function. Factory set at 100%, with a range of 0% to
100%.
14. The economizer shall maintain minimum airflow into the building during
occupied period and provide design ventilation rate for full occupancy.
15. Dampers shall be completely closed when the unit is in the unoccupied
mode.
16. Economizer controller shall accept a 2- 10 Vdc CO2 sensor input for
IAQ/DCV control. In this mode, dampers shall modulate the outdoor air
damper to provide ventilation based on the sensor input.
17. Economizer controller shall provide indications when in free cooling
mode, in the DCV mode, or the exhaust fan contact is closed.
B. Motorized Damper:
1. Damper shall be a Two- Position Damper. Damper travel shall be from
the full closed position to the full open position, depending on model
selected.
2. Assembly shall include adjustable block off to allow air entry of 0% to
25% or 0% to 100% (dependent on selected option) of maximum allowed
outside air.
3. Damper shall include multiple blades, tie-bar driven dampers and actuator
motor.
Renton Senior Activity Center
HVAC, Roof & Ext. Siding Replacement (CAG-25-247)
Construction Documents – January 16, 2026
BCRA Project No. 25040.00.00
23 7416 - 11
PACKAGED ROOFTOP AIR-
CONDITIONING UNITS
4. Damper shall close upon indoor (evaporator) fan shutoff and/or loss of
power.
5. The damper actuator shall plug into the rooftop unit’s wiring harness plug.
No hard wiring shall be required.
C. IntelliSpeed staged air volume system (6.5 – 12.5 Ton models):
1. Evaporator fan motor:
a. Shall have permanently lubricated bearings.
b. Shall have a maximum continuous bhp rating for continuous duty
operation; no safety factors above that rating.
c. Shall be Variable Frequency duty and 2-speed control.
2. Variable Frequency Drive (VFD):
a. Shall be installed inside the unit cabinet, mounted, wired and
tested.
b. Shall contain Electromagnetic Interference (EMI) frequency
protection.
c. Insulated Gate Bi Polar Transistors (IGBT) used to produce the
output pulse width modulated (PVM) waveform.
d. Built in LED display and controls. Does not require additional kit or
options.
e. RS485 capability standard.
f. Electronic thermal overload protection.
g. 5% swinging chokes for harmonic reduction and improved power
factor.
h. All printed circuit boards shall be conformal coated.
2.01 OUTSIDE AIR HOOD
A. The outside air intake hood shall include an aluminum water entrainment filter
mounted directly to inside face of intake.
2.02 HINGED AND TOOL-LESS ACCESS PANELS:
A. Cabinet panels shall be hinged.
B. Shall provide easy access with tool-less latching mechanism.
Renton Senior Activity Center
HVAC, Roof & Ext. Siding Replacement (CAG-25-247)
Construction Documents – January 16, 2026
BCRA Project No. 25040.00.00
23 7416 - 12
PACKAGED ROOFTOP AIR-
CONDITIONING UNITS
C. Shall be on major panels of: filter, control box, fan motor, and gas or electric heat
controls.
2.03 POWERED CONVENIENCE OUTLETS:
A. Outlet shall be powered from main line power to the rooftop unit.
B. Outlet shall be factory installed and internally mounted with easily accessible
115- v female receptacle.
C. Outlet shall include 15-amp GFI receptacles with independent fuse protection.
D. Voltage required to operate convenience outlet shall be provided by a factory
installed step-down transformer.
E. Outlet shall be accessible from outside the unit.
2.04 SINGLE ENTHALPY SENSOR:
A. The single enthalpy sensor option or kit shall provide a relative humidity sensor
to be mounted in the outdoor air stream to provide single enthalpy economizer
control.
B. The sensor allows the unit to determine if outside air is suitable for free cooling.
2.05 PHASE MONITOR
A. Shall provide protection against phase reversal, phase loss, and phase
unbalance.
B. Switch shall automatically shut off unit control circuit if any of the above
conditions is detected.
C. Shall have visual LED indication of operational status.
2.06 SMART EQUIPMENT CONTROLS
A. Shall be ASHRAE 62-2001 compliant.
B. Shall accept 20-30 VAC input power, 50/60Hz. 24 VAC nominal.
C. Shall include an option of an Economizer microprocessor controller which
communicates directly with the Unit Control Board and has 8 Analog outputs, 2
Analog inputs, 2 Binary outputs, 3 Binary outputs.
Renton Senior Activity Center
HVAC, Roof & Ext. Siding Replacement (CAG-25-247)
Construction Documents – January 16, 2026
BCRA Project No. 25040.00.00
23 7416 - 13
PACKAGED ROOFTOP AIR-
CONDITIONING UNITS
D. Controller shall accept the following inputs: space temperature, return air
temperature sensor, set point adjustment, outdoor air temperature, indoor air
quality, outdoor air quality, indoor relative humidity, compressor lock out,
fire/smoke shutdown, single and dual enthalpy, fan status, remote time clock,
Sensor Actuator (SA) Bus communicated temperature/humidity/CO2 values from
Network sensors, Field Controller (FC) Bus Network Overrides for space
temperature, outdoor air temperature, space humidity, outdoor air quality, Indoor
air quality, System purge.
E. Shall accept a CO2 sensor or multiple CO2 sensors networked together in the
conditioned space and be Demand Control Ventilation (DCV) ready.
F. Shall provide compressor short-cycle protection with minimum compressor
runtime set at 3 minutes standard and adjustable from 2 to 7 minutes.
G. Built in lead-lag compressor sequencing to support balanced utilization of
refrigerant circuits.
H. Shall provide the following outputs: economizer, fan, cooling stage 1, cooling
stage 2, heat stage 1, heat stage 2, heat stage 3/ exhaust/ reversing valve/
dehumidify/ occupied.
I. Unit shall provide surge protection for the controller through a circuit breaker.
J. Shall have open communication protocols with all required points exposed.
Protocols supported include: BACnet®, MS/TP, Modbus®, and N2
communication.
K. Shall have an LCD display on the Unit Control Board to display fault messages
as well as navigate the menu structure to review and change set points.
L. Shall utilize a USB connection to allow for uploading and downloading of data.
M. Shall include an RJ-12 port to be used with a Wi-Fi signal transmitting device and
allow unit(s) access via any non-proprietary smart device.
N. Shall have the capability to control the Verasys control system.
O. Shall not require any proprietary software or contractor tool to start-up,
commission and troubleshoot unit operation.
P. Software upgrades will be accomplished by local download via USB port on main
Unit Control Board.
Q. Unit shall be UL tested and certified in accordance with CSA/ANSI
Z21.47:21/CSA 2.3:21, CAN/CSA-C22.2 No 60335-2-40:22 and 60335-2-40-1-
:16, and UL 60335-2-40 (4th edition).
Renton Senior Activity Center
HVAC, Roof & Ext. Siding Replacement (CAG-25-247)
Construction Documents – January 16, 2026
BCRA Project No. 25040.00.00
23 7416 - 14
PACKAGED ROOFTOP AIR-
CONDITIONING UNITS
2.01 DELIVERY, STORAGE, AND HANDLING:
A. Unit shall be stored and handled per manufacturer’s recommendations.
B. Overhead crane can be used to place the units on a roof using rigging holes built
into the unit base rails without any additions to the unit.
C. Unit shall only be stored or positioned in the upright position.
PART 3 - EXECUTION
3.01 EXAMINATION
A. Verify that the roof is ready to receive work and opening dimensions are as
indicated on shop drawings.
B. Verify that proper power supply is available.
3.02 INSTALLATION
A. Install in accordance with manufacturer's instructions.
B. Install in accordance with NFPA 90A.
C. Condensate Drainage: provide PVC P-traps on unit condensate drains with trap
depth so as to prevent unit sucking in air through condensate drain.
3.03 SYSTEM STARTUP
A. Provide the services of manufacturer's field representative for starting and testing
unit.
1. Prepare a manufacturer’s startup report and turn over to the Owner and
Commissioning Agent.
END OF SECTION