NUMBER OF
CONDUITS AS
REQUIRED
MIN 3/4"x5"x FULL WIDTH
OF ENCASEMENT
NEOPRENE BRG PAD
CORBEL, SEE
STRUCTURAL
DRAWINGS
ADAPTER
REQUIRED FOR
PVC CONDUITS
CONDUIT,
SIZE PER
PLANS
/411
PREMOLDED
JOINT FILLER
RGS CONDUIT,
6" MIN
SST CLAMP, TYP
ELEVATION
CLOSED
CELL
NEOPRENE
- M
RGS
CONDUIT
HUB
PROVIDE
CONTINUOUS
GROUND PATH
PER NEC
REQUIREMENTS
245 HOOPS, 2" CLEAR
EXPANSION/DEFLECTIONCOUPLING
BUILDING
FOUNDATION
AND CORBEL
#4 DOWELS @ 1'-6"
ADHESIVE DOWELS
W/ 6" MIN EMBEDMENT.
MIN 2 TOP AND BOTTOM.
(4 TOTAL)
NOTES:
1. DETAIL APPLIES TO CONDUIT AT BUILDING INTERFACES.
CONCRETE ENCASED DUCT
SCALE: NTS
SUPPORT, NOTE 3
FLEX CONDUIT
TO MOTOR OR
OTHER DEVICE
FLOOR FLANGE AND
A MINIMUM OF 4
CONCRETE ANCHORS
FLOOR —
:o. o.
0 0�<p o
0 0
z
0
RIGID METAL
CONDUIT
(1" MIN SIZE)
"T" CONDULET
o. •o. o. o, o.
p o0 oa<p o <
O O O
NOTES:
1. INSTALLATION OF CONDUIT TO A MOTOR OR OTHER DEVICE WHERE
A FLEXIBLE CONNECTION IS REQUIRED AND NO JUNCTION BOXES OR
CONTROL DEVICES ARE REQUIRED SHALL BE MADE IN ACCORDANCE
WITH THIS DETAIL.
2. ALL HARDWARE SHALL BE STAINLESS STEEL.
3. SUBMIT FINAL DESIGN AND CALCULATIONS FOR SUPPORT AND
ANCHORAGE AS SPECIFIED.
CONDUIT TO EQUIPMENT FROM CEILING
SCALE: NTS
0 12/10/2024 EH DA DT ISSUED FOR BID
No. DATE DSN CHK APP REVISION
75
Xry
QO
2U
pw
wz�
Xm�
LU X
O��
zoo
J Q o
=w
U)=)
= J
I- Q
(D
z
w
J
DESIGNED BY:
D. TAFTFARREN
DRAWN BY:
I. KARNAS
CHECKED BY:
D.ANDERSON
APPROVED BY:
D. TAFTFARREN
GROUND WIRE
EQUIPMENT
ENCLOSURE
METAL
CONDUIT
GROUNDING
BUSHING
NOTES:
1. THE ENDS OF ALL CONDUITS REQUIRED TO BE GROUNDED
BY THE SPECIFICATIONS SHALL BE GROUNDED IN ACCORDANCE
WITH THIS DETAIL.
CONDUIT GROUNDING
SCALE: NTS
1
GROUT FILL CEL
CONTAINING BO.'
DO NOT LOCA7
IN A REINFORCE
CEL
PLAN
SINGLE DEVICE BOX
WITH PLASTER RING
E DEVICE BOX
'LASTER RING
Cn
z
O
Q
U
LL
U
w
d
W
W
o_
NOTES: SECTION
1. ALL WIRING DEVICE BOXES MOUNTED IN CONCRETE BLOCK
WALLS SHALL BE INSTALLED IN ACCORDANCE WITH THIS DETAIL.
2. PARALLEL CONDUIT NOT PERMITTED IN CELLS WITH VERTICAL
REINFORCING. DO NOT CUT OR DISPLACE VERTICAL REINFORCING
OR DOWELS.
DEVICE MNT BOX IN CONCRETE MASONRY WALL
SCALE: NTS
pacobs
�0" SUBMITTED BY:
12/O2/24 R. PARGAS
Q w
TmRIDE
U
U)C/)
49
W J
BRT General Engineering Consultant z U_
DATE: REVIEWED BY:
12/10/2024 J. ALTCHECH
LOCK NUT
BOTTOM OF STEEL OR
f' f"%A Inn rTr C -rn1 1f' -r1 Inr
z
DOUBLE RACK
NOTES:
SEISMIC BRACE
FO ROOF OR
FOP OF FLOOR
3EAM ABOVE
JNLESS BRACED
FO WALL.
1. LENGTH VARIES WITH NUMBER OF CONDUITS TO BE SUPPORTED AND SPACING
BETWEEN CONDUITS.
2. SUBMIT FINAL DESIGN AND CALCULATIONS FOR SUPPORT AND ANCHORAGE
AS SPECIFIED.
3. USE STAINLESS STEEL HARDWARE IN WET AND/OR CORROSIVE AREAS.
4. SPACE CONDUIT SUFFICIENTLY TO ALLOW REMOVAL OF ONE CONDUIT WITHOUT
DISTURBING ADJACENT CONDUITS.
CONDUIT RACKING SYSYEM
SCALE: NTS
SCALE:
NTS
FILENAME:
S 1-BT120-E-v2020
SOUNDTRANSIT CONTRACT No.:
RTA/CN 0205-24
DATE: SUBMITTAL DATE:
12/10/2024 12/10/2024
STRIDE BUS RAPID TRANSIT
SOUTH RENTON TRANSIT CENTER
BT105
ELECTRICAL
DETAILS
SOUTH RENTON TRANSIT CENTER
R-4332476
DEVELOPMENT ENGINEERING
U
msippo 11 /25/2025 11
DRAWING NO.:
BT120-EPD103
FACILITY ID:
BT120
SHEET No: REV:
554 p