HomeMy WebLinkAboutR-4332477m co lt 0 `W 1 O N O N > Iil O N IM- W rr U) U w C� I z Q ry ~I 0 n f'yI 0 D am 0 I 0 c0 co 2 a o N o7 N C/) ,;I- D 0 N O LO m m z COPPER GROUND CONDUCTOR, TYP 4" MIN 4" MIN 4" MIN D 4" MIN NOTES: 1. PROVIDE 6" MINIMUM COMPACTED GRAVEL, 3/4" MINUS, UNDER ALL CONCRETE ENCASED DUCT RUNS. DUCT BANK SCALE: NTS z z in 4 IVIIIV U 4 IVIIIV 2" CLR, (TYP TOP AND SIDES) #4@18" TOP AND BOTTOM WITH 2'-0" LAP, TYP #4 LONGITUDINAL BARS @18" OC MAX, LAP BOTTOM BARS 1'-6" AND LAP OTHER BARS 1'-11" MIN, TYP #4 STIRRUPS @18" MAX, TYP 3" CLR, (TYP BOT) FINISHED FLOOR c 0 <a 0< Vo O0 0< O 0 0 I 0 0 0 0 % 00, ;K CONDUIT D=3"FOR 2"AND LARGER CONDUITS UNLESS OTHERWISE NOTED D = 2" FOR 1 1/2" AND SMALLER CONDUITS UNLESS OTHERWISE NOTED PLUG vo c 0 <0 0< 0 00"<O O 0 0o 0 0 vv 0 1* 0o COUPLING NOTES: 1. CONDUITS WHICH ARE STUBBED UP IN A CONCRETE SLAB FOR FUTURE EXTENSION SHALL BE INSTALLED IN ACCORDANCE WITH THIS DETAIL. FLUSH CONDUIT STUB SCALE: NTS 0 12/10/2024 EH DA DT ISSUED FOR BID No. DATE DSN CHK APP REVISION DESIGNED BY: D. TAFTFARREN DRAWN BY: I. KARNAS CHECKED BY: D.ANDERSON APPROVED BY: D. TAFTFARREN o o .oi• .o' v vv vv .v ..o ..o t 00 00 oc • d°v dvv Tv-" • d v v 'o v v• 'o .v % 00 00 00 00 o V' z o o v� . :-Iw = Ln 4" MIN D' 'D I 4" MIN D D DUCT BANK-2 SCALE: NTS WALL N c) 3/4" ,)2', 4" :�►A L COPPER GROUND CONDUCTOR, TYP #411 @ 18" VERT LEGS 1'-0" M I N #411 @ 18" VERT LEGS 1'-6" MIN FOR LARGER DUCT BANKS, CONTINUE PATTERN OF REBAR, CONDUIT SEPARATION AND CONCRETE COVER. LENGTH OF SUIT 5/8" MIN CONCRETE 0 0 0 ANCHOR, SEE NOTE 1 0�<0 0 = SCHEDULE 80 PVC SPACER, SEE PLAN NOTE 4" 2" " 3/4 � I � GROUND BUS, HARD DRAWN COPPER BAR 3/8" THICK GROUND CABLE (SIZE AS SHOWN ON DRAWING) NON-METALLIC CONDUIT 0 0 0 -0 <0 0 :O o 00 <0 a 0 0 c 0 <o 0 O0 0< 0 O ELEVATION SILICON BRONZE BOLTS, NUTS AND WASHERS. SIZE TO SUIT, TYP GROUND CABLE CONNECTOR EXOTHERMIC WELD TO CABLE NOTES: 1. MAXIMUM SPAN BETWEEN SUPPORTS NOT TO EXCEED 24". GROUND BUS SCALE: NTS pacobs SUBMITTED BY: 12102124 R. PARGAS TmRIDE 49 BRT General Engineering Consultant DATE: REVIEWED BY: 12/10/2024 J. ALTCHECH FLEXIBLE NEOPRENE SLEEVE ADAPTER REQUIRED FOR PVC CONDUITS CONDUIT, SIZE PER PLANS NOTE 3 co PREMOLDED JOINT FILLER AT CONSTRUCTION JOINT CLOSED CELL NEOPRENE STAINLESS STEEL CLAMP, TYP HUB RGS CONDUIT, TYP PROVIDE CONTINUOUS GROUND PATH PER NEC REQUIREMENTS NOTES: 1. DETAIL APPLIES TO CONDUIT EMBEDDED IN STRUCTURAL CONCRETE AT BUILDING INTERFACES AND AT STRUCTURAL EXPANSION JOINTS. 2 DETAIL APPLIES TO ALL EXPANSION JOINTS FOR THE UNDERGROUND CONCRETE ENCASED CONDUITS. 3 PVC CONDUIT INSTALLATIONS SHALL HAVE 18 INCHES MIN LENGTH OF RGS CONDUIT EACH SIDE OF FITTING. EXPANSION/DEFLECTION COUPLING SCALE: NTS GROUND CABLE TO SERVICE EQUIPMENT TOP OF FOUNDATION z 0 co N GROUND ELECTRODE SCALE: NTS SCALE: Q w NTS Q FILENAME: U)C/) w J S 1-BT120-E-v2020 z J SOUNDTRANSIT CONTRACT No.: RTA/CN 0205-24 DATE: SUBMITTAL DATE: 12/10/2024 12/10/2024 ' GROUND CLAMP, DEVICE O O LOCATION INSTALL NEAR SERVICE ENTRANCE 1/2" (#4 MIN) REBAR TIE TOGETHER AND EMBED IN FOUNDATION BOTTOM OF FOUNDATION � f 20' LONG MIN, 2 TYP BEND AROUND CORNERS AS REQUIRED STRIDE BUS RAPID TRANSIT SOUTH RENTON TRANSIT CENTER BT105 ELECTRICAL DETAILS SOUTH RENTON TRANSIT CENTER R-4332477 DEVELOPMENT ENGINEERING 0msippo 11 /25/2025 DRAWING NO.: BT120-EPD104 FACILITY ID: BT120 SHEET No: REV: 555 0