Loading...
HomeMy WebLinkAboutR-4332499N co co 6 W 0 N O N IiI 0 N m co 0 w C� �I z Q I 0 a - I D m 0 I 0 co 00 LO � M a0 � Q I N U) ti 0 L N O O �p N cy) co � N _ co m 0 SITE CONDUIT AND CONDUCTOR SCHEDULE CONDUIT TAG SIZE SOURCE DESTINATION CONDUCTOR... GROUND NOTES BT120- N4- 201 A 4" PSE TRANSFORMER BT120-HHLV-26 4#300KCMIL BT120- N4- 201 B 4" PSE TRANSFORMER BT120-HHLV-26 4#300KCMIL BT120- N4- 201 C 4" BT120-HHLV-26 BT120-SWGR-01 4#300KCMIL BT120- N4- 201 D 4" BT120-HHLV-26 BT120-SWGR-01 4#300KCMIL BT120- N4- 202 2-1/2" BT120-SWGR-01 BT120-HHLV-12 4#4/0 1#6 FUTURE GARAGE BT120- N4- 203 2-1/2" BT120-HHLV-12 BT120-HHLV-13 4#4/0 1#6 FUTURE GARAGE BT120- N4- 204 A 4" PSE TRANSFORMER BT120-HHLV-27 W/ PULLSTRING SPARE BT120- N4- 204 B 4" PSE TRANSFORMER BT120-HHLV-27 W/ PULLSTRING SPARE BT120- E4- 201 A 2-1/2" BT120-GEN-01 BT120-HHLV-12 4#4/0 1#2 BT120- E4- 201 B 2-1/2" BT120-GEN-01 BT120-HHLV-12 4#4/0 1#2 BT120- E4- 202 A 2-1/2" BT120-HHLV-12 BT120-ATS-01 4#4/0 1#2 BT120- E4- 202 B 2-1/2" BT120-HHLV-12 BT120-ATS-01 4#4/0 1#2 BT120- E4- 203 2-1/2" BT120-GEN-01 BT120-HHLV-12 4#4/0 1#6 BT120- E4- 204 2-1/2" BT120-HHLV-12 BT120-HHLV-13 4#4/0 1#6 BT120- N2- 201 1" BT120-PB2-03 BT120-HHLV-12 4#10 #10 BATTERY CHARGER/HEATER BT120- N2- 202 1" BT120-HHLV-12 BT120-GEN-01 4#10 #10 BATTERY CHARGER/HEATER BT120- N2- 203 2" BT120-PB2-02 BT120-HHLV-14 4#1 #8 BT120-PB2-04 BT120- N2- 204 2" BT120-HHLV-14 BT120-HHLV-15 4#1 #8 BT120-PB2-04 BT120- N2- 205 2" BT120-HHLV-15 BT120-PB2-04 4#1 #8 BT120-PB2-04 BT120- N2- 206 2" KCM-UPS-1 BT120-HHLV-28 3#1 #8 KCM-PB2-03 BT120- N2- 207 2" BT120-HHLV-28 BT120-HHLV-29 3#1 #8 KCM-PB2-03 BT120- N2- 208 2" BT120-HHLV-29 BT120-HHLV-30 3#1 #8 KCM-PB2-03 BT120- N2- 209 2" BT120-HHLV-30 KCM-PB2-03 3#1 #8 KCM-PB2-03 BT120- N2- 210 1" BT120-PB2-06 BT120-HHLV-14 4#8 #10 DUAL EV CHARGER BT120- N2- 211 1" BT120-HHLV-14 EV CHARGER 4#8 #10 DUAL EV CHARGER BT120- N2- 212 1" BT120-PB2-03 BT120-HH-SL-43 2#10 #10 IRRIGATION CONTROLLER BT120- N2- 213 1" BT120-HH-SL-43 BT120-HH-SL-77 2#10 #10 IRRIGATION CONTROLLER BT120- N2- 214 1" BT120-HH-SL-77 IRRIGATION CONTROLLER 2#10 #10 IRRIGATION CONTROLLER BT120- SC- 201 1" BT120-HHSC-25 BT120-GEN-01 4#16 #16 GENERATOR SIGNAL BT120- SC- 202 2" BT120-HHSC-25 BT120-GEN-01 CAT5e GENERATOR BMS MONITORING BT120- SC- 203 1" BT120-ATS-01 BT120-HHSC-25 4#16 #16 GENERATOR SIGNAL BT120-SC- 204 2" BMS CONTROLLER BT120-HHSC-25 CAT5e GENERATOR BMS MONITORING NOTES: 1. ALL CONDUCTORS ARE COPPER AND 600 VOLT INSULATED UNLESS OTHERWISE NOTED. HANDHOLE SCHEDULE HANDHOLE # SIZE OUTSIDE DIM INSCRIPTION* CATALOG NUMBER** NOTES B 1 0-HHLV- 1 REMOVED BT120-HHLV-02 REMOVED BT120-HHSC-03 REMOVED BT120-HHSC-04 REMOVED BT120-HHLV-05 REMOVED BT120-HHSC-06 REMOVED BT120-HHLV-07 REMOVED BT120-HHLV-08 REMOVED BT120-HHSC-09 REMOVED BT120-HHLV-10 REMOVED BT120-HHSC-11 REMOVED BT120-HHLV-12 3'-8" X 2'-8" X 3'-6"H ELECTRICAL ST OLD CASTLE PRECAST: 233-LA BT120-HHLV-13 '-8" X '- " 3'-6" 2 ELECTRICAL ST OLD CASTLE PRECAST: 233-LA BT120-HHLV-14 3'-4" 2-4' X '-2'H ELECTRICAL ST CHRISTY: B40 W/ GALVANIZED STEEL CHECKER PLATE BOLT DOWN COVER BT120-HHLV-15 3'-4" X 2'-4" X 1'-2"H ELECTRICAL ST CHRISTY: B40 W/ GALVANIZED STEEL CHECKER PLATE BOLT DOWN COVER DECORATIVE COVER BT120-HHLV-16 2'-9" X 1'-10" X 1'-0"H ELECTRICAL ST H2 PRECAST: TYPE-2 HANDHOLE DECORATIVE COVER BT120-HHLV-17 2'-9" X 1'-10" X 1'-0"H ELECTRICAL ST H2 PRECAST: TYPE-2 HANDHOLE DECORATIVE COVER BT120-HHLV-18 2'-9" X 1'-10" X 1'-0"H ELECTRICAL ST H2 PRECAST: TYPE-2 HANDHOLE DECORATIVE COVER BT120-HHLV-19 2'-9" X 1'-10" X 1'-0"H ELECTRICAL ST H2 PRECAST: TYPE-2 HANDHOLE DECORATIVE COVER BT120-HHLV-20 2'-9" X 1'-10" X 1'-0"H ELECTRICAL ST H2 PRECAST: TYPE-2 HANDHOLE DECORATIVE COVER BT120-HHLV-21 2'-9" X 1'-10" X 1'-0"H ELECTRICAL ST H2 PRECAST: TYPE-2 HANDHOLE DECORATIVE COVER BT120-HHLV-22 2'-9" X 1'-10" X —1 VO"H ELECTRICAL ST H2 PRECAST: TYPE-2 HANDHOLE DECORATIVE COVER BT120-HHLV-23 2'-9" X 1'-10" X 1'-0"H ELECTRICAL ST H2 PRECAST: TYPE-2 HANDHOLE DECORATIVE COVER 2 -H S -2 '- 2'- 3 -6" I A IO D C E RCS : 2 3- A BT120-HH-SL-XX 25" X 16" X 12"H LIGHTING CHRISTY: B16 W/ GALVANIZED STEEL CHECKER PLATE BOLT DOWN COVER BT120-HHLV-26 3'-8" X 2'-8" X 3'-6111-1 PSE OLD CASTLE PRECAST: 233-LA PSE 233 CONCRETE HANDHOLE BT120-HHLV-27 3'-8" X 2'-8" X 3'-6"H PSE OLD CASTLE PRECAST: 233-LA I PSE 233 CONCRETE HANDHOLE BT120-HHLV-28 3'-4" X 2'-4" X 1'-2"H ELECTRICAL KCM ELECTRICAL KCM CHRISTY: B40 W/ GALVANIZED STEEL CHECKER PLATE BOLT DOWN COVER CHRISTY: B40 W/ GALVANIZED STEEL CHECKER PLATE BOLT DOWN COVER H2 PRECAST: TYPE-2 HANDHOLE DECORATIVE COVER DECORATIVE COVER BT120-HHLV-29 3'-4" X '- " 1'- �ZELECTRICALKCM BT120-HHLV-30 2'-9" 1 -1 1'0"H BT120-HHLV-31 2'-9" X 1'-10" X 1'-0"H ELECTRICAL KCM H2 PRECAST: TYPE-2 HANDHOLE DECORATIVE COVER BT120-HHLV-32 2'4' X 1'-10" X 1'-0111-1 ELECTRICAL KCM H2 PRECAST: TYPE-2 HANDHOLE DECORATIVE COVER NOTE: *INSCRIPTION SHALL INCLUDE THE VAULT/HANDHOLE NUMBER 2 **HANDHOLES IN PLATFORM AND HIGH PEDESTRIAN AREAS SHALL HAVE ECORATIVE COVER SEE DETAIL 2 ON SHEET BT120-JCD207 FOR DECORATIVE COVER DETAIL. 2 06/27/2025 EH DA I DT ADDENDUM #2 1 06/13/2025 EH DA DT ADDENDUM #1 0 12/10/2024 EH DA DT ISSUED FOR BID No. I DATE I DSN I CHK I APP I REVISION DESIGNED BY: D. TAFTFARREN DRAWN BY: E. HAJAS CHECKED BY: D.ANDERSON APPROVED BY: D. TAFTFARREN .;acobs SUBMITTED BY: 6/27/25 R. PARGAS 4b5TmRIDE BRT General Engineering Consultant DATE: REVIEWED BY: 12/10/2024 J. ALTCHECH Q w Q Lnco W J Z J SOUNDTRANSIT DATE: 12/10/2024 SCALE: NTS FILENAME: S 1-BT120-E-v2020 CONTRACT No.: RTA/CN 0205-24 SUBMITTAL DATE: 12/10/2024 STRIDE BUS RAPID TRANSIT SOUTH RENTON TRANSIT CENTER BT105 ELECTRICAL CONDUIT AND CONDUCTOR SCHEDULE SOUTH RENTON TRANSIT CENTER R-4332499 DEVELOPMENT ENGINEERING msippo 11 /25/2025 Ul DRAWING NO.: BT120-EPS121 FACILITY ID: BT120 SHEET No: REV: 577 2