CORE FACILITY CONDUIT AND CONDUCTOR SCHEDULE
RACEWAY HOMERUN SIZE PANEUSOURCE CIRCUIT DESTINATION CONDUCTORS1 GROUND NOTES
BT120-2-301
3/4"
BT120-SWBD-02
13,15
BT120-HPMP-01
2#12 CU
1#12 CU
17,19
BT120-HPMP-02
2#12 CU
2#12 CU
21,23
BT120-HPMP-03
BT120-2-302
3/4"
BT120-PB2-05
10,12
BT120-HPMP-05
2#10 CU
1#10 CU
BT120-2-303
BT120-2-304
1"
3/4"
BT120-SWBD-02
BT120-SWBD-02
33,35
BT120-HPMP-06
2#10 CU
1#10 CU
1#12 CU
1#8 CU
37,39
BT120-HPMP-07
2#10 CU
14,16
BT120-EWH-01
2#12 CU
18,20
BT120-EWH-02
2#12 CU
22,24
26,28,30
BT120-EWH-03
BT120-EWH-05
2#12 CU
3#4
BT120-2-305
1"
BT120-SWBD-02
BT120-2-306
3/4"
BT120-PB2-03
8
BT120-HTR-01
2#12 CU
1#12 CU
15
BT120-EWH-06
2#12 CU
7
BT120-ERU-01
2#12 CU
BT120-2-307
1"
BT120-PB2-03
10,12
BT120-HPMP-06 BRANCH UNIT
BT120-HPMP-06 BRANCH UNIT
2#12 CU
1#12 CU
11,13
2#12 CU
25
FLOOD CONTROL SYSTEM
2#12 CU
BT120-2-308
3/4"
BT120-PB2-03
6
GENERAL RECEPTACLES
2#12 CU
1#12 CU
9
HPMP SERVICE RECEPTACLES
2#12 CU
5
BT120-HTR-02
2#12 CU
BT120-2-309
3/4"
BT120-PB2-03
18
ELECTRICAL ROOM RECEPTACLE
2#12 CU
1#12 CU
16
PSE AMR REPEATER
2#12 CU
BT120-2-310 3/4" BT120-PB2-03 17,19 MOTORIZED DOOR 2#12 CU 1#12 CU
20 1 GENERAL RECEPTACLES 2#12 CU
SOUND TRANSIT TELECOMM ROOM
BT120-2-311
3/4"
BT120-PB2-05
BT120-PB2-05
4
RECEPTACLE
2#12 CU
1#12 CU
CU
15
BMS CONTROLLER
2#12 CU
BT120-2-312
3/4"
1
BT120-ACL-01
2#12 CU1#12
2
RECEPTACLE
2#12 CU
BT120-2-313
3/4"
BT120-PB2-05
3
SERVER RACK
SERVER RACK
2#10 CU1#10
2#10 CU
CU
5
BT120-2-314
BT120-2-315
3/4"
BT120-PB2-05
BT120-PB2-05
6
SERVER RACK
2#10 CU
1 #10 CU
8
SERVER RACK
2#10 CU
3/4"
7
SERVER RACK
2#10 CU
1#10 CU
9
SERVER RACK
2#10 CU
BT120-2-316
3/4"
BT120-PB2-05
11
SERVER RACK
2#10 CU
1#10 CU
13
SERVER RACK
2#10 CU
BT120-2-317
BT120-2-318
3/4"
BT120-PB2-03
BT120-PB2-03
18
ELECTRICAL ROOM RECEPTACLE
2#12 CU
1#12 CU
1#12 CU
16
PSE AMR REPEATER
2#12 CU
3/4"
17,19
MOTORIZED DOOR
2#12 CU
20
GENERAL RECEPTACLES
2#12 CU
KING COUNTY METRO TELECOMM ROOM
BT120-2-319 3/4" 1 RECEPTACLE 2#12 CU KCM-PB2-04 1#12 CU
10 RECEPTACLE 2#12 CU
BT120-2-320
3/4"
KCM-PB2-04
2
SERVER RACK
SERVER RACK
2#10 CU1#10
2#10 CU
CU
4
BT120-2-321
BT120-2-322
3/4"
KCM-PB2-04
KCM-PB2-04
3
SERVER RACK
2#10 CU
1 #10 CU
5
SERVER RACK
2#10 CU
3/4"
6
SERVER RACK
2#10 CU
1#10 CU
8
SERVER RACK
2#10 CU
BT120-2-323 3/4" KCM-PB2-04 7 SERVER RACK 2#10 CU 1#10 CU
9 SERVER RACK 2#10 CU
SECURITY BUILDING
BT120-2-324
3/4"
BT120-PB2-01
1,3
BT120-ACU-07
2#12 CU
1 #12 CU
BT120-2-325
3/4"
BT120-PB2-01
2
GFCI RECEPTACLE
2#12 CU
1#12 CU
4
GFCI RECEPTACLE
2#12 CU
10,12
BT120-EWH-04
2#12 CU
BT120-2-326
3/4"
BT120-PB2-01
5
RECEPTACLE
2#12 CU
1#12 CU
7
RECEPTACLE
2#12 CU
9
RECEPTACLE
2#12 CU
BT120-2-327
3/4"
BT120-PB2-01
6
RECEPTACLE
RECEPTACLE
2#12 CU1#12
2#12 CU
CU
8
NOTES:
1. ALL CONDUCTORS ARE 600 VOLT INSULATED UNLESS OTHERWISE NOTED.
0 1 12/10/2024 1 EH I DA I DT I ISSUED FORBID
No. I DATE I DSN I CHK I APP I REVISION
DESIGNED BY:
D. TAFTFARREN
DRAWN BY:
E. HAJAS
CHECKED BY:
D.ANDERSON
APPROVED BY:
D. TAFTFARREN
T AFT.
.;acobs
57079 �
�EGISTERti�
�SSIONAL IESUBMITTED BY: DATE:
12/02/24 R. PARGAS 12/10/2024
PLATFORM CONDUIT AND CONDUCTOR SCHEDULE
CONDUIT SIZE PANEL CIRCUIT SOURCE DESTINATION CONDUCTORS1 GROUND NOTES
BT120-2-001
1"
BT120-PB2-04
9,11
BT120-PB2-04
BAY 1 COMMS CABINET - ST
BT120-HHLV-23
3#10 CU
1#10 CU
BT120-2-002
1"
BT120-PB2-04
1
BT120-PB2-04
2#10 CU
1#10 CU
BT120-2-003
1"
BT120-PB2-04
5,7
BT120-PB2-04
BT120-HHLV-23
4#10 CU
1#10 CU
BT120-2-004
1"
BT120-PB2-04
1
BT120-HHLV-23
BAY 1 CANOPY LIGHTING - SOUTH
2#10 CU
1#10 CU
BT120-2-005
1"
BT120-PB2-04
5
BT120-HHLV-23
BAY 1 CANOPY VMS - SOUTH
2#10 CU
1#10 CU
BT120-2-006
1"
BT120-PB2-04
7
BT120-HHLV-23
BAY 1 TVM
2#10 CU
1#10 CU
BT120-2-007
1"
BT120-PB2-04
1
BT120-HHLV-23
BT120-HHLV-16
2#10 CU
1#10 CU
BT120-2-008
1"
BT120-PB2-04
5
BT120-HHLV-23
BT120-HHLV-16
2#10 CU
1#10 CU
BT120-2-009
1"
BT120-PB2-04
1
BT120-HHLV-16
BAY 1 CANOPY LIGHTING - NORTH
2#10 CU
1#10 CU
BT120-2-010
1"
BT120-PB2-04
5
BT120-HHLV-16
BAY 1 CANOPY VMS - NORTH
2#10 CU
1#10 CU
BT120-2-011
1"
BT120-PB2-04
5
BT120-HHLV-23
BAY 1 PYLON VMS
2#10 CU
1#10 CU
BT120-2-012
1"
BT120-PB2-04
2
BT120-PB2-04
BT120-HHLV-19
2#10 CU
1#10 CU
BT120-2-013
1"
BT120-PB2-04
13,15
BT120-PB2-04
BT120-HHLV-19
4#10 CU
1#10 CU
BT120-2-014
1"
BT120-PB2-04
13
BT120-HHLV-19
BAY 8 PYLON VMS
2#10 CU
1#10 CU
BT120-2-015
1"
BT120-PB2-04
2
BT120-HHLV-19
BAY 8 CANOPY LIGHTING
2#10 CU
1#10 CU
BT120-2-016
1"
BT120-PB2-04
13
BT120-HHLV-19
BAY 8 CANOPY VMS
2#10 CU
1#10 CU
BT120-2-017
1"
BT120-PB2-04
15
BT120-HHLV-19
BAY 8 TVM
2#10 CU
1#10 CU
BT120-2-018
1"
BT120-PB2-04
2,3,4
BT120-PB2-04
BT120-HHLV-20
6#10 CU
1#10 CU
BT120-2-019
1"
BT120-PB2-04
17,19
BT120-PB2-04
BT120-HHLV-20
3#10 CU
1#10 CU
BT120-2-020
1"
BT120-PB2-04
6,8
BT120-PB2-04
BT120-HHLV-20
3#10 CU
1#10 CU
BT120-2-021
1"
BT120-PB2-04
2
BT120-HHLV-20
BAY 2 CANOPY LIGHTING
2#10 CU
1#10 CU
BT120-2-022
1"
BT120-PB2-04
17,19
BT120-HHLV-20
BAY 8 COMMS CABINET - ST
3#10 CU
1#10 CU
BT120-2-023
1"
BT120-PB2-04
3,4
BT120-HHLV-20
BT120-HHLV-21
4#10 CU
1#10 CU
BT120-2-024
1"
BT120-PB2-04
6,8
BT120-HHLV-20
BT120-HHLV-21
3#10 CU
1#10 CU
BT120-2-025
1"
BT120-PB2-04
3
BT120-HHLV-21
BAY 3 WEST CANOPY LIGHTING
2#10 CU
1#10 CU
BT120-2-026
1"
BT120-PB2-04
3
BT120-HHLV-21
BT120-HHLV-17
2#10 CU
1#10 CU
BT120-2-027
1"
BT120-PB2-04
3
BT120-HHLV-17
BAY 7 CANOPY LIGHTING
2#10 CU
1#10 CU
BT120-2-028
1"
BT120-PB2-04
4
BT120-HHLV-21
BT120-HHLV-22
2#10 CU
1#10 CU
BT120-2-029
1"
BT120-PB2-04
6,8
BT120-HHLV-21
BT120-HHLV-22
3#10 CU
1#10 CU
BT120-2-030
1"
BT120-PB2-04
4
BT120-HHLV-22
BAY 3 EAST CANOPY LIGHTING
2#10 CU
1#10 CU
BT120-2-031
1"
BT120-PB2-04
4
BT120-HHLV-22
BT120-HHLV-18
2#10 CU
1#10 CU
BT120-2-032
1"
BT120-PB2-04
4
BT120-HHLV-18
BAY 6 CANOPY LIGHTING
2#10 CU
1#10 CU
BT120-2-033
1"
BT120-PB2-04
6,8
BT120-HHLV-22
BAY 6 COMMS CABINET - ST
3#10 CU
1#10 CU
KCM-2-001
1"
KCM-PB2-03
1,3,5
KCM-PB2-03
BT120-HHLV-31
5#10 CU
1#10 CU
KCM-2-002
1"
KCM-PB2-03
2,6,8
KCM-PB2-03
BT120-HHLV-31
5#10 CU
1#10 CU
KCM-2-003
1"
KCM-PB2-03
2
KCM-PB2-03
BT120-HHLV-30
2#10 CU
1#10 CU
KCM-2-004
1"
KCM-PB2-03
2
BT120-HHLV-30
BAY 7 CANOPY VMS
2#10 CU
1#10 CU
KCM-2-005
1"
KCM-PB2-03
3,5
BT120-HHLV-31
BAY 2 COMMS CABINET - KCM
3#10 CU
1#10 CU
KCM-2-006
1"
KCM-PB2-03
1
BT120-HHLV-31
BAY 2 CANOPY VMS
2#10 CU
1#10 CU
KCM-2-007
1"
KCM-PB2-03
2
BT120-HHLV-31
BAY 3 WEST CANOPY SPARE
KCM-2-008
1"
KCM-PB2-03
2
BT120-HHLV-31
BT120-HHLV-32
2#10 CU
1#10 CU
KCM-2-009
1"
KCM-PB2-03
6,8
BT120-HHLV-31
BAY 3 COMMS CABINET - KCM
3#10 CU
1#10 CU
KCM-2-010
1"
KCM-PB2-03
2
BT120-HHLV-31
BAY 3 EAST CANOPY VMS
2#10 CU
1#10 CU
KCM-2-011
1"
KCM-PB2-03
2
BT120-HHLV-32
BAY 6 CANOPY VMS
2#10 CU
1#10 CU
K1r1TFC-
1. ALL CONDUCTORS ARE 600 VOLT INSULATED UNLESS OTHERWISE NOTED.
4STmRIDE
BRT General Engineering Consultant
REVIEWED BY:
J. ALTCHECH
Q w
Q
w J
J
SOUNDTRANSIT
DATE:
12/10/2024
SCALE:
NTS
FILENAME:
S 1-BT120-E-v2020
CONTRACT No.:
RTA/CN 0205-24
SUBMITTAL DATE:
12/10/2024
STRIDE BUS RAPID TRANSIT
SOUTH RENTON TRANSIT CENTER
BT105
ELECTRICAL
CONDUIT AND CONDUCTOR SCHEDULE 2
SOUTH RENTON TRANSIT CENTER
R-4332500
DEVELOPMENT ENGINEERING
msippo 11 /25/2025 %ji
DRAWING NO.:
BT120-EPS122
FACILITY ID:
BT120
SHEET No: REV:
578 0