LIGHTING
MANUAL
CONTROL
MATRIX
MANUAL
MANUAL
OCCUPANCY
VACANCY
ADJUST
DAYLIGHT
SPACE
ON
OFF
ON
NO
OFF
(DIMMING)
NO
SENSOR
NO
PHOTOCELL
TIMECLOCK
SEQUENCE OF OPERATIONS
LIGHTS WILL BE CONTROLLED BY A MANUAL ON/OFF SWITCH.
LIGHTS WILL BE CONTROLLED BY A MANUAL ON/OFF SWITCH WITH A BUILT-IN OCCUPANCY SENSOR.
ELECTRICAL ROOM
YES
YES
NO
NO
NO
WHEN SPACE IS DETECTED AS BEING UNOCCUPIED FOR 20 MINUTES, SENSOR WILL TURN LIGHTS OFF.
JANITOR'S
YES
YES
NO
YES
NO
NO
NO
NO
USE OF MANUAL SWITCH WILL TURN LIGHTS ON WHEN THEY'RE OFF, AND WILL TURN THE LIGHTS OFF
WHEN THEY'RE ON.
LIGHTS WILL BE CONTROLLED BY MANUAL ON/OFF SWITCH WITH A BUILT-IN OCCUPANCY SENSOR
AND DIMMER. WHEN LIGHTS ARE OFF AND OCCUPANCY SENSOR DETECTS THAT SPACE IS OCCUPIED,
IT WILL TURN LIGHTS ON TO 50% OUTPUT. WHEN SPACE IS DETECTED AS BEING UNOCCUPIED FOR 20
LACTATION ROOM
YES
YES
YES, 50%
YES
YES
NO
NO
NO
MINUTES, SENSOR WILL TURN LIGHTS OFF. USE OF MANUAL SWITCH WILL TURN LIGHTS TO 100% ON
WHEN LIGHTS ARE AT 50% OR OFF, AND WILL TURN THE LIGHTS OFF WHEN THEY'RE AT 100% ON.
LIGHTS WILL BE CONTROLLED BY A MANUAL ON/OFF SWITCH WITH BUILT-IN OCCUPANCY SENSOR AND
DIMMER. WHEN LIGHTS ARE OFF AND OCCUPANCY SENSOR DETECTS THAT SPACE IS OCCUPIED, IT
WILL TURN LIGHTS ON TO 100% OUTPUT. WHEN SPACE IS DETECTED AS BEING UNOCCUPIED FOR 20
OPERATOR RESTROOMS
YES
YES
YES, 100%
YES
YES
NO
NO
NO
MINUTES, SENSOR WILL TURN LIGHTS OFF. USE OF MANUAL SWITCH WILL TURN LIGHTS TO 100% ON
WHEN LIGHTS ARE OFF, AND WILL TURN THE LIGHTS OFF WHEN THEY'RE ON.
LIGHTS WILL BE CONTROLLED BY MANUAL ON/OFF SWITCH WITH MANUAL DIMMING CONTROL. WHEN
LIGHTS ARE OFF AND OCCUPANCY SENSOR DETECTS THAT SPACE IS OCCUPIED, IT WILL TURN LIGHTS
ON UP TO 50% OUTPUT. WHEN SPACE IS DETECTED AS BEING UNOCCUPIED FOR 15 MINUTES, SENSOR
SECURITY
YES
YES
YES, 50%
YES
YES
YES
NO
NO
WILL TURN LIGHTS OFF. LIGHTS SHALL SHALL DIM AS LOW AS 15% SO AS TO ACHIEVE 15 FOOT
CANDLES ON THE FLOOR. USE OF MANUAL SWITCH WILL TURN LIGHTS ON WHEN LIGHTS ARE OFF,
AND WILL TURN THE LIGHTS OFF WHEN THEY'RE ON.
LIGHTS WILL BE CONTROLLED BY A MANUAL ON/OFF SWITCH WITH A BUILT-IN OCCUPANCY SENSOR.
WHEN SPACE IS DETECTED AS BEING UNOCCUPIED FOR 20 MINUTES, SENSOR WILL TURN LIGHTS OFF.
STORAGE ROOM
YES
YES
NO
YES
NO
NO
NO
NO
USE OF MANUAL SWITCH WILL TURN LIGHTS ON WHEN THEY'RE OFF, AND WILL TURN THE LIGHTS OFF
WHEN THEY'RE ON.
LIGHTS WILL BE CONTROLLED BY A MANUAL ON/OFF SWITCH WITH A BUILT-IN OCCUPANCY SENSOR.
WHEN SPACE IS DETECTED AS BEING UNOCCUPIED FOR 20 MINUTES, SENSOR WILL TURN LIGHTS OFF.
TELECOMM ROOM
YES
YES
NO
YES
NO
NO
NO
NO
USE OF MANUAL SWITCH WILL TURN LIGHTS ON WHEN THEY'RE OFF, AND WILL TURN THE LIGHTS OFF
WHEN THEY'RE ON.
UPON LOSS OF NORMAL POWER ALL EMERGENCY FIXTURES WILL AUTOMATICALLY SWITCH TO
EMERGENCY FIXTURES
N/A
N/A
N/A
N/A
N/A
NO
NO
NO
BATTERY OPERATION AND TURN FULL ON. RETURNING TO OPERATE SAME AS NORMAL LIGHTING UPON
RESPORATION OF NORMAL POWER
LIGHTS SHALL BE CONTROLLED BY A COMBINATION OF A CENTRALIZED PHOTOCELL & A TIME
CONTROL. PHOTOCELL SHALL TURN TRIGGER THE LIGHTS TO TURN OFF WHEN THERE IS ENOUGH
BUS BAYS
NO
NO
NO
NO
NO
NO
YES
YES
DAYLIGHT FOR NORMAL OPERATIONS. EXTERNAL TIME CONTROL WILL BE SET TO TURN OFF LIGHTS
DURING THE PERIOD FROM 1 HOUR AFTER FACILITY CLOSES TO 1 HOUR BEFORE FACILITY OPENS.
ELECTRICAL YARD CANOPY
REMOVED
LIGHTS SHALL BE CONTROLLED BY A CENTRALIZED PHOTOCELL; PHOTOCELL SHALL TURN LIGHTS OFF
EXTERIOR OF BUILDINGS
NO
NO
NO
NO
NO
NO
YES
NO
WHEN THERE IS ENOUGH DAYLIGHT FOR NORMAL OPERATIONS.
LAYOVER/CHARGING BAYS
REMOVED
LIGHTS SHALL BE CONTROLLED BY A COMBINATION OF A CENTRALIZED PHOTOCELL & A TIME
CONTROL. PHOTOCELL SHALL TURN LIGHTS OFF WHEN THERE IS ENOUGH DAYLIGHT FOR NORMAL
SITE LIGHTING
NO
NO
NO
NO
NO
NO
YES
YES
OPERATIONS.
1 06/13/2025 JS LS DT ADDENDUM #1
0 12/10/2024 JS MM DT ISSUED FOR BID
No. I DATE I DSN I CHK I APP I REVISION
DESIGNED BY:
J. SAXER
DRAWN BY:
E. HAJAS
CHECKED BY:
L. GLASER
APPROVED BY:
D. TAFTFARREN
AFT F
Paco s.
57079
R`GIST BY- w�
�sSI�NAL V, SUBMITTED BY:
6113125 R. PARGAS
STmRIDE
BRT General Engineering Consultant
DATE: REVIEWED BY:
12/10/2024 J. ALTCHECH
Q w
U)�
W J
J
z " SOUNDTRANSIT
DATE:
12/10/2024
SCALE:
NTS
FILENAME:
S 1-BT120-E-v2020
CONTRACT No.:
RTA/CN 0205-24
SUBMITTAL DATE:
12/10/2024
STRIDE BUS RAPID TRANSIT
SOUTH RENTON TRANSIT CENTER
BT105
ELECTRICAL
LIGHTING CONTROL MATRIX
SOUTH RENTON TRANSIT CENTER
R-4332506
DEVELOPMENT ENGINEERING
msippo 11 /25/2025 Ul
DRAWING NO.:
BT120-ELS102
FACILITY ID:
BT120
SHEET No: REV:
584 1