Loading...
HomeMy WebLinkAboutR-4332541N C'7 C'7 0 LU 0 N O N 0 J m 0 N am U w 0 I Cn z ~I 0 0- ry C/)I D m of 0 co 00 M a 0 M I M >Q Cn 0 CN m B. (CONT.) TELECOMMUNICATION PATHWAY NOTES: t. POWER SEPARATION: • THE CONTRACTOR MUST NOT PLACE ANY DISTRIBUTION CABLING ALONGSIDE POWER LINES, OR SHARE THE SAME CONDUIT, CHANNEL OR SLEEVE WITH ELECTRICAL APPARATUS. AT NO POINT MUST THE COMMUNICATIONS CABLES BE TIED TO POWER CABLES OR OTHER BUILDING SERVICES. STATION CABLES AND TIE CABLES INSTALLED WITHIN CEILING SPACES MUST BE ROUTED THROUGH THESE SPACES AT RIGHT ANGLES TO ELECTRICAL POWER CIRCUITS. • AVOID ELECTROMAGNETIC INTERFERENCE (EMI) BY MAINTAINING ADEQUATE PHYSICAL SEPARATION BETWEEN TELECOMMUNICATION CABLING AND POSSIBLE SOURCES SUCH AS, BUT NOT LIMITED TO, ELECTRIC MOTORS, ELECTRIC PENCIL SHARPENERS, TRANSFORMERS, FLUORESCENT LIGHTS THAT SHARE DISTRIBUTION SPACE WITH TELECOMMUNICATIONS CABLING, COPIERS THAT SHARE WORK AREA SPACE WITH LINE CORDS AND TERMINALS, LARGE FAX MACHINES AND POWER CORDS THAT SUPPORTS SUCH EQUIPMENT. C. TELECOMMUNICATION CABLING NOTES: 1. THE USE OF LUBRICANTS SUCH AS CLEAR GLIDE, TO FACILITATE THE INSTALLATION OF CABLES IN OUTDOOR CONDUITS IS ENCOURAGED FOR FRICTION REDUCTION AND TO MAINTAIN THE REQUIRED PULL TENSION. YELLOW 77 AND POLYWATER IS NOT PERMISSIBLE FOR USE AS A LUBRICANT FOR TELECOMMUNICATION CABLING. THE USE OF OSP, LOW TEMPERATURE CABLE LUBRICANTS ARE NOT ACCEPTABLE IN AN INDOOR PLENUM ENVIRONMENT. UNDER NO CIRCUMSTANCES MUST CABLE PULLING LUBRICANT BE ALLOWED TO ACCUMULATE ON WALLS, FLOORS, BACKBOARDS, OR OTHER SURFACES OUTSIDE THE CONDUIT. 2. ANY CABLE DAMAGED OR EXCEEDING RECOMMENDED INSTALLATION PARAMETERS DURING INSTALLATION MUST BE REPLACED BY THE CONTRACTOR BEFORE FINAL ACCEPTANCE AT NO COST TO THE OWNER. 3. EACH RUN OF CABLE BETWEEN THE TERMINATION BLOCK OR PATCH PANEL AND THE STATION CONNECTOR MUST BE CONTINUOUS WITHOUT ANY JOINTS OR SPLICES. 4. ALL STATION CABLE MUST BE PLACED IN THE INTERIOR OF WALLS UNLESS OTHERWISE NOTED OR OBSTRUCTED. 5. PROVIDE BUSHINGS, GROMMETS AND STRAIN -RELIEF FOR CABLES TERMINATING AT WALL - MOUNTED OUTLETS AND PATCH PANELS TO ENSURE DURABLE AND ROBUST CONNECTIONS. THE BUSHINGS AND GROMMETS ARE INTENDED TO PROTECT THE CABLES FROM ANY SHARP EDGES THAT PRESENT A RISK TO THE CABLES. ENSURE THAT ALL SHARP EDGES ARE COVERED TO PROTECT THE CABLES FROM DAMAGE. 6. ALL CABLE BUNDLES EXITING FLOOR OR WALL PENETRATIONS AND RUNNING INTO FURNITURE OR CASEWORK MUST BE WRAPPED IN SPIRAL WRAP OR SPLIT -LOOM TUBING TO PROTECT THE CABLING AND PROVIDE A NEAT INSTALLATION. 7. ALL CABLE OR INNERDUCT MUST RUN PARALLEL OR AT RIGHT ANGLES TO BUILDING WALL STRUCTURES. 8. IN SUSPENDED CEILING AND RAISED FLOOR AREAS WHERE DUCT, CABLE TRAYS OR CONDUIT ARE NOT AVAILABLE, CABLE BUNDLES MUST BE SUPPORTED VIA "J" HOOKS ATTACHED TO THE BUILDING STRUCTURE AND FRAMEWORK AT A MAXIMUM OF FOUR (4) FOOT INTERVALS. MINIMUM 1" WIDE J-HOOKS MUST BE APPROPRIATELY SIZED TO ALLOW A MINIMUM OF 60% SPARE CAPACITY FOR FUTURE CABLE INSTALLATION. THE CONTRACTOR MUST INCLUDE ALL COSTS IN BASE BID FOR ANY ADDITIONAL SUPPORTS/SEISMIC BRACING REQUIRED BY THE LOCAL AUTHORITY HAVING JURISDICTION. 9. THE CONTRACTOR MUST BUNDLE, IN BUNDLES OF 24 OR LESS, STATION OR OTHER CABLING WITH 3/4" HOOK AND LOOP STRIPS SIMILAR TO VELCRO "ONE WRAP", TIGHT ENOUGH TO HOLD THE BUNDLE TOGETHER IN A CYLINDRICAL SHAPE, BUT NOT SO TIGHT AS TO DEFORM THE CABLE GEOMETRY. IT MUST BE POSSIBLE TO COMPLETELY ROTATE ALL HOOK AND LOOP TIES AROUND ALL CABLE BUNDLES. PLENUM RATED HOOK AND LOOP TIES WILL BE USED IN ANY PLENUM AREAS. 10. CABLES OR J-HOOKS MUST NOT BE ATTACHED TO LIFT OUT CEILING GRID SUPPORTS OR LAID DIRECTLY ON THE CEILING GRID. 11. CABLES OR J-HOOKS MUST NOT BE ATTACHED TO OR SUPPORTED BY FIRE SPRINKLER HEADS OR DELIVERY SYSTEMS OR ANY ENVIRONMENTAL SENSOR LOCATED IN THE CEILING AIR SPACE 12. WHERE ADDITIONAL CONDUIT(S)/SLEEVE(S) ARE REQUIRED, BUT NOT PROVIDED BY THE ELECTRICAL CONTRACTOR, THE SCS AND/OR LV CONTRACTOR MUST BE RESPONSIBLE TO PROVIDE SUCH CON DUIT(S)/SLEEVE(S). CONDUIT(S) AND SLEEVE(S) MUST BE OF SUITABLE MATERIAL, SIZED, INSTALLED, FIRE -STOPPED, AND GROUNDED AS REQUIRED BY THE NEC 2020, ANSI/TIA-569-E STANDARD AND ALL OTHER APPLICABLE CODES AND STANDARDS. SLEEVES MUST CONSIST OF METALLIC CONDUIT DE -BURRED AND GROMMETTED ON BOTH ENDS WITH FLANGES OR OTHER MEANS TO PREVENT THE SLEEVE FROM SLIPPING OR FALLING OUT OF THE PARTITION. SLEEVES MUST EXTEND A MINIMUM OF 6" ON BOTH SIDES OF THE PARTITION. OUTSIDE PERIMETER OF SLEEVES MUST BE SEALED AGAINST SOUND, AIR, WATER, HEAT, OR AS REQUIRED BY PARTITION DESIGN. INSIDE OF SLEEVE MUST BE SEALED SIMILARLY AFTER INSTALLATION OF ALL CABLING. CABLES MUST BE INDEPENDENTLY SUPPORTED ON EITHER SIDE OF THE SLEEVE. SLEEVES MUST NOT BE USED AS CABLE SUPPORTS. ANY CONDUIT(S) AND SLEEVE(S) ADDED BY THE SCS CONTRACTOR MUST BE APPROVED BY THE OWNERS REPRESENTATIVE PRIOR TO ROUGH -IN. 13. IN THE EVENT CONTRACTOR IS REQUIRED TO REMOVE CEILING TILES, SUCH WORK MUST NOT BREAK OR DISTURB GRID. REMOVAL OF THE CEILING GRID MUST BE COORDINATED WITH THE OWNERS REPRESENTATIVE. ALL INSULATION MUST BE REPLACED IN ITS ORIGINAL LOCATION. 0 12/10/2024 DS MF No. DATE DSN CHK DTF ISSUED FORBID APP REVISION --CONTINUED-- DESIGNED BY: D. STOLTZ DRAWN BY: M. SANTO CHECKED BY: M.FREEMAN APPROVED BY: D. TAFT-FARREN 14. THE NUMBER OF CABLES IN EACH CONDUIT MUST BE CONTROLLED TO ALLOW FOR FUTURE CABLE INSTALLATION AND TO STAY WITHIN THE MANUFACTURER'S MAXIMUM ALLOWABLE CABLE PULLING TENSION. CONDUIT FILL RATIOS MUST NOT EXCEED THE CURRENT REQUIREMENTS OF THE NEC 2020, ANSI/TIA-569-E, REFERENCE SECTION B.2, TABLES 1 AND 2 OF THIS DOCUMENT FOR ADDITIONAL REQUIREMENTS. 15. CONDUITS: • ALL BACKBONE CABLING WILL RUN THROUGH DEDICATED CONDUITS. • ALL NEW CONDUITS WILL BE SUPPLIED WITH A PULL STRING BY THE ELECTRICAL CONTRACTOR. • EXISTING CONDUITS MUST BE PROVEN TO BE CLEAR BY THE SCS AND/OR LV CONTRACTOR PRIOR TO PULLING OF CABLES. • SCS AND/OR LV CONTRACTOR MUST SUPPLY PULL STRING AND PULL ROPE FOR THE INSTALLATION OF ALL CABLES IN EXISTING CONDUITS. • FOR ALL CONDUITS LEFT WITH AVAILABLE CAPACITY, SCS AND/OR LV CONTRACTOR MUST REPLACE PULL STRINGS DURING THE COURSE OF WORK. • SCS AND/OR LV CONTRACTOR MUST SEAL ALL CONDUITS WITH AN APPROVED SEALING COMPOUND. D. TELECOMMUNICATION GROUNDING SYSTEM NOTES. 1. THE ELECTRICAL CONTRACTOR MUST PROVIDE A TELECOMMUNICATION GROUNDING BUSSBAR (PBB) AND TELECOMMUNICATION BONDING BACKBONE (SBB) CABLE(S) AT EACH MDF ROOM AND IDF LOCATION. TERMINATE THE SBB ON GROUND BARS LOCATED AT EACH MDF ROOM AND IDF CABINET FROM BUILDING STEEL OR MAIN ELECTRICAL GROUND, OR AS OTHERWISE INDICATED ON THE DRAWINGS. 2. THE SCS CONTRACTOR MUST UTILIZE A TELECOMMUNICATIONS BONDING BACKBONE (SBB) AS INDICATED IN THE DRAWINGS. GROUNDING MUST BE IN ACCORDANCE WITH THE NEC 2020, ANSI/TIA-607-E.1 AND ALL LOCAL CODES AND PRACTICES. 3. THE SCS CONTRACTOR MUST BE RESPONSIBLE FOR BONDING ALL METALLIC SHEATH COMMUNICATIONS CABLES ENTERING THE BUILDING PER MANUFACTURER SPECIFICATIONS AND NEC 770-33, 800-33 AND 800-40. ALL GROUNDS MUST CONSIST OF A COLOR GREEN #6-AWG COPPER WIRE AND MUST BE SUPPLIED FROM AN APPROVED BUILDING GROUND AND BONDED TO THE MAIN ELECTRICAL GROUND. ALL CABLE SHEATHS AND SPLICE CASES MUST BE GROUNDED TO A TELECOMMUNICATIONS GROUND BUS. 4. THE SCS CONTRACTOR MUST PROVIDE GROUNDING AND BONDING FROM ALL HORIZONTAL EQUIPMENT INCLUDING DISTRIBUTION AND CROSS CONNECT FRAMES, PATCH PANELS, CABLE TRAYS, EQUIPMENT RACKS, LADDER TRAYS, CONDUITS, ACTIVE TELECOMMUNICATION EQUIPMENT, SLEEVES, TEST APPARATUS. EQUIPMENT MUST BE BONDED TO THE SBB GROUND BARS UTILIZING A #6-AWG GREEN CONDUCTOR WITH 2-HOLE LONG BARREL COMPRESSION GROUNDING LUGS. a. EACH EQUIPMENT CABINET AND RACK REQUIRES ITS OWN DEDICATED RACK GROUNDING BUSBAR (RGB) WITH A BONDING CONNECTION TO THE GROUNDING INFRASTRUCTURE. THE GROUNDING INFRASTRUCTURE CONSIST OF A SBB, BY PROVIDING EVERY RACK/CABINET WITH ITS OWN DEDICATED #6 AWG (MIN.) GREEN CONDUCTORS BACK TO THE TMGB (TELECOMMUNICATIONS MAIN GROUNDING BUSBAR) / PBB (PRIMARY BUS BAR). ALL GROUND CONDUCTOR ATTACHMENTS MUST UTILIZE 2-HOLE LONG BARREL COMPRESSION LUGS. b. HORIZONTAL CABLES MUST BE GROUNDED IN COMPLIANCE WITH NFPA 70 (NEC) AND LOCAL REQUIREMENTS AND PRACTICES. c. IN RAISED -FLOOR ENVIRONMENTS, THE GROUND CONDUCTOR MUST ATTACH TO THE LOWEST HOLES ON THE FRONT RAIL OF EACH RACK/CABINET. d. RACK MOUNTED EQUIPMENT MUST BE GROUNDED VIA THE CHASSIS, IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. e. BONDING OF LADDER RACK SECTIONS: ATTACH BONDING STRAPS TO EACH LADDER RACK SECTION BY UTILIZING EITHER TWO (2) TRI- LOBULAR THREAD -FORMING SCREWS (NOT SELF -TAPPING OR SHEET METAL SCREWS) OR BY USING TWO (2) STANDARD BOLTS WITH TWO (2) "TYPE B" INTERNAL / EXTERNAL TOOTH LOCK WASHERS PER BOLT. IF THREAD -FORMING SCREWS ARE NOT USED, REMOVE PAINT AT EACH CONNECTION POINT AND USE AN APPROVED ANTI -OXIDANT PRIOR TO ATTACHING THE BONDING STRAP. E. TERMINAL BACKBOARDS NOTES. 1. WHERE INDICATED ON DRAWINGS, ELECTRICAL CONTRACTOR TO PROVIDE NEW PLYWOOD TERMINAL BACKBOARDS. USE DOUGLAS FIR PLYWOOD, INTERIOR A/C GRADE, FINISHED ONE SIDE AND PRIME COAT PAINTED ON ALL SURFACES WITH A FINISH COAT OF FIRE RETARDANT WHITE ENAMEL. ON EACH PLYWOOD SHEET LEAVE ONE (1) FIRE MARSHAL STAMP UNPAINTED FOR INSPECTION. UNLESS OTHERWISE INDICATED, USE 8'-0" HIGH X LENGTH AS SHOWN ON DRAWINGS X 3/4" THICK PLYWOOD. REFERENCE BACKBOARD ELEVATIONS FOR MORE INFORMATION. F. PENETRATIONS OF WALLS, FLOORS AND CEILINGS NOTES. 1. UNLESS SPECIFICALLY SHOWN ON THE DRAWINGS, THE CONTRACTOR MUST MAKE NO PENETRATION OF FLOORS, WALLS OR CEILING WITHOUT THE PRIOR WRITTEN APPROVAL OF THE OWNERS REPRESENTATIVE. 2. WALL PENETRATIONS: a. THE SCS AND/OR LV CONTRACTOR MUST PROVIDE FIRE STOPPING FOR ALL COMMUNICATIONS RATED (AND IN SOME CASES NON -RATED, THAT WILL BE DESCRIBED BELOW THIS SECTION) PATHWAYS AND SPACES. THESE FIRE STOPPING DEVICES MUST CONFORM TO (BUT NOT LIMITED TO) UL 1479, ASTM E814, BICSI TDMM, FIRE STOPPING, ANSI/TIA-568.0-E, ANSI/TIA-569-E, ANSI/TIA-569 ANNEX A AND TDMM 14TH EDITION - FIRESTOPPING CHAPTER, STANDARD FOR INSTALLING COMMERCIAL BUILDING TELECOMMUNICATIONS CABLING, SECTION 5, CLAUSE 5.1 THROUGH 5.2.3, MANUFACTURES GUIDELINES OR OTHER PREVAILING CODE AND MUST BE AN APPROVED UL LISTED SYSTEM. --CONTINUED-- .;acobs SUBMITTED BY: 12102124 R. PARGAS Q w _4fTmRIDE U) � W J BRT General Engineering Consultant z LL DATE: REVIEWED BY: 09/06/2024 J. ALTCHECH b. CABLE TRAY FIRE -STOPPING MUST UTILIZE THE MULTI GANG FIRE -STOPPING SYSTEM THAT WILL BE ABLE TO STACK THE UNITS HORIZONTALLY AND/OR VERTICALLY IF REQUIRED DUE TO CURRENT AND/OR FUTURE CABLING DESIGNS. c. THE CONTRACTOR MUST INSTALL PENETRATION FIRE -STOP SEAL MATERIALS IN ACCORDANCE WITH DESIGN REQUIREMENTS, AND MANUFACTURER'S INSTRUCTIONS. d. THE CONTRACTOR'S INSTALLER MUST BE CERTIFIED, LICENSED OR OTHERWISE QUALIFIED BY THE FIRE -STOPPING MANUFACTURER AS HAVING BEEN PROVIDED THE NECESSARY TRAINING TO INSTALL MANUFACTURER'S PRODUCTS PER SPECIFIED REQUIREMENTS. e. ALL THROUGH -PENETRATION MUST BE A MANUFACTURED, UL CLASSIFIED, FIRE -STOP DEVICE / SYSTEM DESIGNED TO ALLOW CABLES TO PENETRATE FIRE -RATED WALLS WITH A BUILT-IN FIRE SEALING SYSTEM THAT AUTOMATICALLY ADJUSTS TO THE AMOUNT OF CABLES INSTALLED. THE FIRE -STOPPING DEVICE MUST BE CAPABLE OF INSTALLATION IN NEW CONSTRUCTION OR RETROFIT IN EXISTING STRUCTURES. f. THE CONTRACTOR MUST NOT USE CONCRETE OR OTHER NON -REMOVABLE SUBSTANCE FOR FIRE STOPPING ON CABLE TRAYS, WIREWAYS OR CONDUITS. CONTRACTORS WHO USE THIS METHOD WILL BE REQUIRED TO REPLACE ALL CABLES AFFECTED AND PROVIDE THE ORIGINAL SPECIFIED ACCESS TO EACH EFFECTED AREA. THIS REQUIREMENT ALSO APPLIES TO MAINTAINING FIRE RATINGS OF ALL FLOORS PENETRATED BY CONDUITS OR DEVICES DESIGNATED FOR USE BY VOICE AND DATA CABLING. g. ANY PENETRATIONS THROUGH FIRE -RATED WALLS FOR CABLE PATHWAYS / CABLES MUST BE SEALED BY USE OF A NON -PERMANENT FIRE BLANKET OR OTHER METHOD IN COMPLIANCE. THE CONTRACTOR MUST USE FIRE STOPPING ON CABLE TRAYS, WIREWAYS AND CONDUITS EITHER VERTICAL OR HORIZONTAL. FOUR DIFFERENT METHODS OF FIRE -STOPPING HAVE BEEN IDENTIFIED FOR THE HORIZONTAL THROUGH PENETRATIONS BETWEEN WALLS, RATED, RATED WITH ACOUSTIC PROPERTIES, NON -RATED, AND NON -RATED WITH ACOUSTIC PROPERTIES. BELOW ARE METHODS TO ACCOMPLISH THESE DIFFERENT TYPES: • SEALING OF RATED OPENINGS BETWEEN FLOORS OR THROUGH RATED WALLS, WHETHER EXISTING OR CREATED BY THE CONTRACTOR FOR PLACEMENT OF CABLE MUST BE THE RESPONSIBILITY OF THE CONTRACTOR. SEALING MATERIAL AND APPLICATION MUST BE AN APPROVED UL LISTED SYSTEM AND MUST BE ACCOMPLISHED IN SUCH A MANNER THAT IS ACCEPTABLE TO THE LOCAL FIRE AND BUILDING AUTHORITIES HAVING JURISDICTION OVER THIS WORK. CREATION OF SUCH OPENINGS AS ARE NECESSARY FOR CABLE PASSAGE BETWEEN LOCATIONS AS SHOWN ON THE DRAWINGS MUST BE THE RESPONSIBILITY OF THE CONTRACTOR. ANY OPENINGS CREATED BY OR FOR THE CONTRACTOR AND LEFT UNUSED MUST ALSO BE SEALED AS PART OF THIS WORK. • RATED WALLS WITH THROUGH PENETRATIONS WITH ACOUSTIC PROPERTIES MUST BE INSTALLED WITH FACTORY MANUFACTURED DEVICE. SUCH AS A STI "EZ PATH" OR WIREMOLD "FLAMESTOPPER" OR EQUAL. THE TYPICAL STC RATING IS TO BE EQUAL TO OR GREATER THAN THE WALL PENETRATED, (AVG IS A RATING OF 44 STC PER UBC RATINGS). • NON -RATED PATHWAY, ALTHOUGH NOT REQUIRED TO BE FIRE -STOPPED, MUST BE A MANUFACTURED DEVICE THAT WILL ALLOW FIRE -STOPPING TO BE INSTALLED IN THE FUTURE IF REQUIRED, (I.E. WIREMOLD "FLAMESTOPPER" OR EQUAL). • A NON -RATED PATHWAY WITH ACOUSTIC PROPERTIES CAN BE FOUND IN AREAS SUCH AS, CONFERENCE ROOMS, HUMAN RESOURCE OFFICES, MEDICAL EXAMINATION ROOMS ETC. THESE ROOMS REQUIRE TO LIMIT THE AMOUNT OF AMBIENT NOISE THAT CAN TRAVEL FROM ONE ROOM TO THE OTHER THROUGH THE CEILING GRID. IF THIS WALL IS PENETRATED, INSTALL A SYSTEM THAT WILL RE-ESTABLISH THE STC RATING OF THE WALL, THE TYPICAL STC RATING IS AN AVERAGE OF 44 STC PER UBC RATINGS. SCALE: M;rmr=,, N.T.S. FILENAME: S1-BT120-J-BLD-v2020 SOUNDTRANSIT CONTRACT No.: RTA/CN 0205-24 DATE: SUBMITTAL DATE: 12/04/2024 09/06/2024 -CONTINUED-- R-4332541 DEVELOPMENT ENGINEERING msippo 11 /25/2025 U1 STRIDE BUS RAPID TRANSIT DRAWING NO.: SOUTH RENTON TRANSIT CENTER BT120-JCN002 BT105 FACILITY ID: TELECOM BT120 SHEET No: REV: GENERAL NOTES TRANSIT CENTER 619 0