WAP - TO BASKET TRAY
SCALE: NOT TO SCALE
TO MDF/IDF
WAP - TO CEILING TILE DETAIL
SCALE: NOT TO SCALE
BT120-JCD502
BT120-JCD502
WAP - IN OPEN CEILING SPACE
SCALE: NOT TO SCALE BT120-JCD502
WAP - TO HARD LID CEILING
SCALE: NOT TO SCALE
BT120-JCD502
GENERAL NOTES:
A. PROVIDE ALL MOUNTING HARDWARE INCLUDING BOLTS ANCHORS AND ATTACHMENTS.
B. SUBMIT ANCHOR TYPE FOR SPECIFIC APPLICATION (DRYWALL, CONCRETE, BLOCK WALL ETC.,) FOR STRUCTURAL
ENGINEERS APPROVAL.
C. DO NOT ANCHOR EQUIPMENT UNTIL AFTER APPROVAL OF ANCHOR TYPE FROM OWNERS REPRESENTATIVE.
D. PROVIDE ALL CONDUIT PATHWAYS CONNECTORS, BOXES, COVERS, AND SUPPORTING HARDWARE U.O.N.
E. PAINT ALL EXPOSED CONDUIT AND TO MATCH COLOR AND SHEEN OF THE SURFACE AT INSTALLATION LOCATION.
F. THE MOUNTING DETAILS ON THIS PAGE ARE DIAGRAMMATIC AND ARE ONLY INTENDED TO CONVEY THE GENERAL SCOPE
INVOLVED IN MOUNTING A WIRELESS ACCESS POINT.
G. PROVIDE ALL FASTENERS, BRACKETS, ATTACHMENTS, BOLT ANCHORS AND ATTACHMENTS, ETC. PER MANUFACTURER'S
REQUIREMENTS.
H. PROVIDE ALL CUTTING AND PATCHING OF SURROUNDING SURFACES AS REQUIRED FOR PROPER INSTALLATION. PATCHING
SHALL BE OF THE SAME MATERIALS, WORKMANSHIP, AND FINISH, AND ACCURATELY MATCH THE SURROUNDING WORK TO
THE SATISFACTION OF THE OWNERS REPRESENTATIVE.
I. ALL SUPPORTS, BOLTS, STRAPS, AND FASTENERS INSTALLED ON EXTERIOR OF ANY STRUCTURE SHALL BE CORROSION -
RESISTANT. CONNECTORS AND COUPLERS SHALL BE RAIN TIGHT THREADED FITTINGS.
J. SUPPORT CABLE ABOVE CEILING USING J-HOOK. CABLE SHALL BE SUPPORTED A MAXIMUM OF EVERY 48-60 INCHES. CABLES
ROUTED ABOVE CEILING SPACE SHALL NOT DRAPE ONTO CEILING TILE. CABLE SHALL NOT BE ATTACHED TO WATER PIPES,
AIR DUCTS, ELECTRICAL CONDUIT OR CEILING GRID WIRE.
KEY NOTES:
10 PROVIDE J-HOOK. SEE NOTE J ABOVE.
OPROVIDE (2) CATEGORY 6A CABLES TO NEW MDF OR IDF ROOM AS REQUIRED PER PLANS AND SPECIFICATIONS. IF LENGTH
PERMITS PROVIDE A 10' SERVICE COIL IN THE NEAREST PULL BOX OR ACCESSIBLE CEILING SPACE ABOVE THE WIRELESS
ACCESS POINT SUPPORTED BY A DEDICATED J-HOOK AND COILED IN A WORKMANSHIP LIKE MANNER. PROVIDE PLENUM
RATED VELCRO WRAPS FOR THE MANAGEMENT OF THE SERVICE COIL, TIE -WRAPS ARE NOT PERMITTED. REFER TO PLANS
AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
3 PROVIDE 2 PORT FACEPLATE OR SURFACE MOUNTED BOX, AND CATEGORY 6A STATION CONNECTOR, REFER TO PLANS AND
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
4 PROVIDE (2) CATEGORY 6A PATCH CORDS TO WIRELESS ACCESS POINT. REFER TO PLAN AND SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
OPROVIDE WIRELESS ACCESS POINT (WAP).
OMOUNTING PLATE SUPPLIED WITH WIRELESS ACCESS POINT. CONTRACTOR TO DOCUMENT AND VERIFY EACH RECEIVED.
MOUNTED TO DUAL GANG RING AND 5S/DPDG BOX.
OPROVIDE TILE BRIDGE FOR ALL ACCESSIBLE CEILING MOUNTED WIRELESS ACCESS POINTS. MOUNT PER MANUFACTURERS
INSTALLATION GUIDELINES.
(�)CEILING TILE / CEILING GRID SYSTEM (ACCESSIBLE CEILING SPACE)
(9) PROVIDE 3/8" MIN. HILTI KB3 WEDGE ANCHOR FOR CONCRETE CONSTRUCTION, MIN. EMBEDMENT PER. MANUFACTURES
INSTALLATION GUIDELINES.
10 PROVIDE 1-1/4" CONDUIT TO THE NEAREST WIRE BASKET PATHWAY OR ACCESSIBLE CEILING SPACE. SUPPORTED PER THE
NEC, AND GENERAL ELECTRICAL SPECIFICATIONS. REFER TO ELECTRICAL DRAWINGS FOR CONDUIT ROUTING AND
ADDITIONAL INFORMATION.
PROVIDE 5S/DP MINIMUM OUTLET BOX, WITH DUAL GANG RING SUPPORTED PER THE NEC, AND GENERAL ELECTRICAL
11 SPECIFICATIONS. SUPPORTED BY 3/8" ALL THREAD MIN.
12 3/8" MIN THREADED ROD.
13 PROVIDE 7/8" SHALLOW SLOTTED CHANNEL UNISTRUT, MUST SPAN FOR 2 POINTS OF ATTACHMENT TO THE UNDERSIDE OF
THE WIREBASKET WITH MINIMUM 1/4" MOUNTING SCREWS. VERIFY ATTACHMENT PLAN AND LOCATION WITH OWNERS
REPRESENTATIVE PRIOR TO INSTALLATION.
14 SECURITY SCREWS
15 3/4" KNOCK OUT
16 WAP BRACKET
(17 SCREW ANCHOR IN CEILING
18 CABLE LEVELS
19 2 CAT 6A JACKS
20 2 EA OF 10' CAT6A PATCH CORDS
21 LABEL ENDS OF PATCH CORDS
R-4332556
DEVELOPMENT ENGINEERING
msippo 11 /25/2025 U1
DESIGNED BY: SCALE: DRAWING NO.:
D. STOLTZ �1� s Q w NOT TO SCALE STRIDE BUS RAPID TRANSIT gT120-JCD502
DRAWN BY: U FILENAME: SOUTH RENTON TRANSIT CENTER
M. SANTO z vaC� S. w S1-BT120-J-BLD-v2020 BT105 FACILITY ID:
CHECKED BY: 57079 BRT General Engineering Consultant z " SOUNDTRANSIT CONTRACT No.: TELECOM BT120
M. FREEMAN �o� �FcISTER� RTA/CN 0205-24 SHEET No: REV:
0 12/10/2024 DS MF DTF ISSUED FORBID APPROVED BY: �SSI�NAL ESUBMITTED BY: DATE: REVIEWED BY: DATE: SUBMITTAL DATE: INSTALLATION DETAILS
i2/oz/24 TRANSIT CENTER 634 0
No. DATE DSN CHK APP REVISION D. TAFT-FARREN R. PARGAS 09/06/2024 J. ALTCHECH 12/04/2024 09/06/2024