WIRING DEN
OR ELECTR
EQUIPMENT
CONDUIT
PIPE STRAF
FLOOR OR
PLATFORM
CONCRETE OR MASONRY
WALL OR COLUMN
NOTES 2 AND 3
FOR CONTROL
STATIONS MOUNT
AT 4'-0"±
NOTES:
1. ALL MOUNTING HARDWARE SHALL BE STAINLESS STEEL. USE BOTH WASHER
AND LOCK WASHERS UNDER ALL NUTS.
2. ON CONCRETE WALLS USE STAINLESS STEEL CONCRETE ANCHORS.
MOUNT ENCLOSURE ON SPACERS OF MIN 1/2" SCHEDULE 80 PVC CONDUIT.
3. BOXES 6 INCHES SQUARE AND SMALLER SHALL BE SUPPORTED BY TWO ANCHORS,
MIN. LARGER BOXES SHALL BE SUPPORTED AS REQUIRED BY CALCULATION;
FOUR ANCHORS MIN.
4. SUBMIT FINAL DESIGN AND CALCULATIONS FOR SUPPORT AND ANCHORAGE
AS SPECIFIED
DEVICE MOUNTING WALL OR COLUMN
SCALE: NTS
OR
1/2"
Em
TOP
FRONT
DRILL HOLE, AS
REQUIRED FOR
CONDUIT FITTING
MIN 12 GAUGE SHEET
METAL GALVANIZED
AFTER FABRICATION
FLEXIBLE
CONDUIT
CONDUIT
CONNECT
CONDUIT
CONNECT
SIDE
FLEXIBLE CONDUIT SUPPORT(4)
SCALE: NTS
DESIGNED BY:
R. SHADID
DRAWN BY:
G. KING
CHECKED BY:
F. GIST
0 12/10/2024 RS FG FG ISSUED FORBID APPROVED BY:
No. DATE DSN CHK APP REVISION F. GIST
CONDUIT CONCRETE ANCHOR
SUPPORT AS SPECIFIED
00 �:peo0,01 O°o
0
O
0.'0 O
� Q
0 � �
•
v
Lill= Oo O
°o.
0 O,-o
4, O O
o p U.o.
O O . . O .O .
CONCRETE ANCHOR INSTALLATION
SCALE: NTS
GRADE
GROUNDING
CONNECTORS:
"O-Z/G E D N EY"
TYPE ABG, OR EC
GROUND TEST WELL
SCALE: NTS
GROUNDING WELL
•��1
CONDUI
CLAMP
CONCRETE
ANCHOR
FORMED
STEEL CHANNEL
NOTES:
1. SUPPORT ALL EXPOSED CONDUITS ON FORMED STEEL CHANNELS.
2. SUBMIT FINAL DESIGN AND CALCULATIONS FOR SUPPORT AND ANCHORAGE
AS SPECIFIED.
CONDUIT SUPPORT ON STRUCTURE
SCALE: NTS
EXISTING
BUILDING
WALL
LB LB CONDULET
CONDULET
a 9
a <,
FINISH GRADE
14
'RAVEL \�
:ROUNDING —
',ONDUCTOR
NOTES:
ND ROD 1. INSTALL CONDUITS THROUGH EXISTING WALLS IN ACCORDANCE
WITH THIS DETAIL IF NOT OTHERWISE INDICATED.
.;acobs
SUBMITTED BY:
11/15/24 R. PARGAS
2. DRILL HOLE USING METHODS THAT LEAVE A SMOOTH OPENING.
SEAL OPENING AROUND CONDUIT, INSIDE, AND OUTSIDE, WITH
ONE PART POLYURETHANE IMMERSIBLE SEALANT.
CONDUIT ENTRANCE g
SCALE: NTS
SCALE:
Q w M;rr
NTS
Q FILENAME:
U
45T)?IDE w J S1-BT120-J-BLD-v2020
BRT General Engineering Consultant z " SOUNDTRANSIT CONTRACT No.:
RTA/CN 0205-24
DATE: REVIEWED BY: DATE: SUBMITTAL DATE:
09/06/2024 J. ALTCHECH 12/04/2024 09/06/2024
GALVANIZED STEEL
SHEET METAL
ESCUTCHEON,TYP
GALVANIZED STEEL PIP
SLEEVE OR CORE DRILL
HOLE IN CONCRETE WA
JSULATION AS REQUIRED
O FILL CAVITY
:ONDUIT
NOTES:
1. CONDUITS WHICH INDIVIDUALLY PASS THRU AN INTERIOR WALL
SHALL BE INSTALLED IN ACCORDANCE WITH THIS DETAIL. IF
WALL IS A FIRE WALL, FILL CAVITY WITH FIRE STOP SEALANT
AS SPECIFIED.
INTERIOR WALL PENETRATION
SCALE: NTS
STRIDE BUS RAPID TRANSIT
SOUTH RENTON TRANSIT CENTER
BT105
SECURITY
STANDARD DETAILS
DEVELOPMENT ENGINEERING 4
msippo 11 /25/2025 '
R-4332571
DRAWING NO.:
BT120-JCD554
FACILITY ID:
BT120
SHEET No: REV:
649 0