GENERAL NOTES:
1. SHELTER LIGHTS ARE OWNER FURNISHED AND CONTRACTOR INSTALLED.
2. SHELTER NEMA ENCLOSURE INCLUDING INTERNAL COMPONENTS ARE OWNER FURNISHED
AND CONTRACTOR INSTALLED.
3. UL FIELD VERIFICATION CERTIFICATION OF THE ELECTRICAL INSTALLATIONS AT THE SHELTER
AND TECH PYLON IS BY THE CONTRACTOR. SEE SPECIFICATIONS.
4. SEE SHEET 1 E2.03 FOR SHELTER LIGHTING ENCLOSURE WIRING SCHEMATIC.
CONDUIT SUPPORT, TYP
24V DC CABLE TO SHELTER LIGHTING
(LIGHT FIXTURES ARE OWNER FURNISHED,
CONTRACTOR INSTALLED)
3/4" LFMC UP TO MAP FRAME
120V PHOTOCONTROL. INTERMATIC K4121C OR APPROVED EQUAL
MALEABLE IRON COVER WITH 1/2" HUB FOR PHOTOCONTROL MOUNTING. APPLI
JBK-50 OR APPROVED EQUAL
4" ROUND WEATHERPROOF MALLEABLE IRON JUNCTION BOX WITH MOUNTING
LUGS SURFACE MOUNTED AT TOP OF CANOPY STRUCTURE. APPLETON JBX-75
APPROVED EQUAL.
4" SQUARE MEALLEABLE IRON WEATHERPROOF JUNCTION BOX
FOR CANOPY 24V POWER CONNECTIONS TO CANOPY LIGHTING
3/4" LFMC UP TO PHOTOCONTROL JUNCTION BOX AT
CANOPY
I kwi-
sm3/4" LFMC UP TO PHOTOCONTROL
12"
=X 18" X 4" N E MA 3 R
SHELTER LIGHTING POWER ENCLOSURE
: (OWNER FURNISHED, CONTRACTOR INSTALLED)
as 3/4" LFMC UP FROM CONDUIT STUB TO SHELTER
LIGHTING POWER ENCLOSURE.
3/4" RGS POWER CONDUIT. ELECTRICAL
POWER CONDUIT MUST BE CLOSEST TO
WEBBING. SEE DETAIL 4 ON 3E2.04
° '4
SEE SHELTER GROUNDING DETAILS ON 1 E2.04
_ - ° a - By '- ° 11
a - - - . 1 1/2" PVC COMM CONDUIT. STUBBED AND CAPPED
GI
EXTEND
TO GROI
HEAVY DU_
DEEP STEE
2-GANG DE
12
(C
ATTACH[
RGS CON
BONDING JUMPER EX
STRUCTURAL STEEL
VG, XHHW, 2/C CABLE
3ROUND, TYP. TO LIGHT
ZES
WG, XHHW, 2/C CABLE
GROUND, TYP. TO LED
:RS
24V DC POWER SUPPLY, TYP OF 3
(OWNER FURNISHED)
SHELTER LIGHT POWER - ELEVATION SHELTER LIGHT POWER ENCLOSURE - DETAIL
DETAIL DETAIL DEVELOPMENT ENGINEERING
w a SCALE: NTS SCALE: NTS Michael Sippo 09/11/2024
Yz
0, c w
ca o 0
J c6 w
cu J T-421425
DESIGNED: APPROVED: DATE:
oEo• AL
METROTRANSIT CAPITAL
APITAL DIVISION
wAD READY SUBMITTAL hyNG
RAPIDRIDE I LINE(453-5000
of wAs6, r DRAWN:
o 0 pacobs1100 112TH AVE NE, SUITE 500 41 •
o r BELLEVUE, WA 98004 fT King County
o � y 3 .� � A. KING
o 0 �� j CHECKED: PROJECT N0: R E N TO N SEGMENT DRAWING N0:
ID
o Y •o ��Gr`STEg�'9 �� X.ZHANG E00566E18 METRO SHELTER LIGHTING POWER ENCLOSURE 1 E2.02
o� L w concord ► _ • SHEET NO: OF
0 w LU S`SIONAL 1� CHECKED: CONTRACT NO: DETAILS ca p w No. REVISION BY APP'D DATE tA ENGINEERING �� �� 309 473
J � Q 6/12/2024
0 a- x K. CHANG YUEN CXXXXXXXX