Longacres Master Plan Project EIS
PEER REVIEW COMMENT AND STATUS OF RESPONSE FORM
Deliverable: Peer Review of Drainage Reports Reviewed: 11/14/25
Peer Review Team Member: Richard Price Comment Response Provided: (date)
Comments Due: (EA to provide date) Comment Response Accepted: (date)
Item
#
Reviewer Report Reviewed Page Line(s) Review Comment Level of
Comment1
Status of
Response
Explanation
Drainage Report All Add page numbers 3
Drainage Report All Document needs significant editing—both
grammatical/spelling and technical. In many
places the grammatical errors change the technical
meaning (e.g., “discharge to a series of BioPods
and Bioscapes.” Vs. “discharge to a BioPod or
Bioscape”), or are grammatically incorrect and
make the sentence non-sensical.
Some of these are listed specifically in comments
below, but not all.
1,2,3 CPL Response: Typos
have been removed and
discrepancies in
terminology resolved.
PDF
4
Both “Drainage Plan” and “Temporary Erosion
and Sedimentation Control Plan” are defined by
the acronym (TESC)?
3 CPL Response: TESC
removed from PDF 4 where
Drainage Plan is
referenced. TESC is only
TESC as suggested.
PDF
4
“This project proposes to construct a drainage
system with a new network of underground pipes
and catch basins to collect surface water runoff
throughout the site and direct it to a water quality
treatment facilities.” Not a true statement
1 CPL Response: That intent
is for all new and disturbed
existing areas. We will
clarify as needed as we
believe the statement to be
correct in the context of
the plans.
PDF
5
“This project proposes to construct a drainage
system with a new network of underground pipes
and catch basins, to collect the drainage from the
roofs and roadways as well as the surface water
1 CPL Response: Multiple
facilities make up the water
quality treatment system.
CPL Response: We will
Draft – for Internal Review
runoff throughout the walkways and other areas
adjacent to the buildings within the project site.
This system will direct runoff from the roadways to
the water quality treatment system.” There are
multiple water quality treatment systems and
techniques described, not one.
clarify in the language of
the TIR.
PDF
5
All water quality on site will be provided in a
treatment system Reword
3 CPL Response: Updated
per comment.
PDF
7
“These pipes are designed to carry stormwater
runoff…” Change “pipes” to “Conveyances”
2 CPL Response: Updated
per comment.
PDF
8
#8 Correct “Bioops” 3 CPL Response: Updated
per comment.
PDF
8
Master Drainage Plan: Does this plan “govern” or
provide context”?
1 CPL Response: Context
only, have updated
wording.
PDF
9
“we will provide fine mesh screens on all discharge
pipes.” Address maintenance/flooding issues
1 CPL Response: The mesh
is sized per previous
agreement with City, to
allow flooding to enter
system mitigation but not
allow any errant fishes into
the system. Maintenance
should be moderate, as all
drainage is routed first
through water quality
facilities, unlike old Boeing
site operations.
PDF
12
“conveyed to a series of BioPods and Bioscapes”
Is this a treatment train in series? Mentioned
twice.
1 CPL Response: Changed
“and” to “or”. Final
decision will occur prior to
Civil permit submittal after
EIS. Treatment levels are
equivalent.
PDF
13
Table 1: Longacre areas Pervious + Impervious
does not equal Total ?
2 CPL Response: We have
updated the Tables to
explain the totals more
Draft – for Internal Review
clearly, and confirmed the
summations are accurate.
Appe
ndice
s
Add Title sheet between each appendix and
add title on each sheet
3 CPL Response: Updated
per comment.
Figur
es
Numerous figures not referenced in text. 3 CPL Response: Updated
per comment.
Figur
es
“Figures” include several documents/exhibits.
Suggest separate or rename Appendix A-1, A-2,
A-3 with appropriate titles
3 CPL Response: Updated
per comment.
Figur
es
“Figures” include several documents/exhibits.
Suggest rename or separate.
3 CPL Response: Updated
per comment.
Fig
5C
Text illegible CPL Response: Updated
per comment.
1Comment Level Codes: 1 = Critical Issue - Address; 2 = Factual Issue – Check; 3 = Editorial – Consider.