HomeMy WebLinkAboutTSI #4 PVC Conduit
State
Department of Transportation
I
I
I
I
I
I I
Request for Approval of Material
Contract Number FA Number SR Date
Section / Title of Project County
Contractor Subcontractor
This form shall be completed prior to submittal. If this form is not complete at time of submittal it may be returned for information that was omitted.
PE Use Bid Item and Sub-Item No.
Material Type, Product Name & Model Number
Name and Location of Fabricator, Manufacturer or Pit Number Specification Reference
For WSDOT Use Only
RAM #
Unifier Submittal #
PE/QPL Code Hdqtr./QPL Code HQ Use
Project Engineer/Representative Date State Materials Engineer/Representative Date
Acceptance Action Codes for use by Project Engineer and State Materials Laboratory
1. Acceptance Criteria: Acceptance based upon “Satisfactory” Test Report for samples of materials to be incorporated into project.
2. Acceptance Criteria: Mfg. Cert. of Compliance for ‘Acceptance’ prior to use of material.
3. Acceptance Criteria: Catalog Cuts for ‘Acceptance’ prior to use of material. Catalog Cut Approved Yes No
4. Acceptance Criteria: Submit Shop Drawings for ‘Approval’ prior to fabrication of material.
5. Acceptance Criteria: Only ‘Approved for Shipment’, ‘WSDOT Inspected’ or ‘Fabrication Approved Decal’ material shall be used.
6. Acceptance Criteria: Submit Certificate of Materials Origin to Project Engineer Office.
7. Acceptance Criteria: Request Transmitted to State Materials Laboratory for Approval Action.
8. Source Approved:
9. Approval Withheld: Submit samples for preliminary evaluation.
10. Approval Withheld:
11. Miscellaneous Acceptance Criteria.
Remarks (PE):
Remarks (HQ):
DOT Form 350-071 Revised 07/2023
Project Engineer Distribution
Contractor Region Operations Engineer Fabrication Inspection Region Materials State Materials Lab - MS 47365
CANTEX INC. | 301 Commerce Street, Suite 2700, Fort Worth, TX 76102 | 817.215.7000 | www.cantexinc.com
Nonmetallic PVC Schedule 80 Conduit
Nonmetallic PVC Schedule 80 Conduit
Belled End - 10’ Lengths
CANTEX Schedule 80 PVC Conduit is designed for underground or aboveground applications that are at risk
of physical damage.
•Nonmetallic PVC material which is corrosion, rust & sunlight
resistant
•ETL listed
•Conforms to UL651 and NEMA TC-2
•Rated for use with 90-degree C conductors
•Made in USA
•Sunlight Resistant
•10’ Lengths
•20’ Lengths available (See note below)
Part No.Size Feet per Pack T Min OD ID Min E B D Nom L Min
A53AE12 1/2 6,000 .147 .840 .502 .852 .836 1.500 120
A53AG12 3/4 4,400 .154 1.050 .698 1.064 1.046 1.750 120
A53BA12 1 3,600 .179 1.315 .910 1.330 1.310 2.000 120
A53BC12 1-1/4 3,300 .191 1.660 1.227 1.677 1.655 2.250 120
A53BE12 1-1/2 2,250 .200 1.900 1.446 1.918 1.894 2.500 120
A53CA12 2 1,400 .218 2.375 1.881 2.393 2.369 3.000 120
A53CE12 2-1/2 930 .276 2.875 2.250 2.890 2.868 3.250 120
A53DA12 3 880 .300 3.500 2.820 3.515 3.492 3.750 120
A53DE12 3-1/2*630 .318 4.000 3.486 4.015 3.992 4.000 120
A53EA12 4 570 .337 4.500 3.737 4.515 4.491 4.500 120
A53FA12 5 380 .375 5.563 4.713 5.593 5.553 5.500 120
A53GA12 6 260 .432 6.625 5.646 6.658 6.614 6.125 120
Dimensions are nominal
PVC Schedule 80 Conduit Belled End-20’ Lengths
CANTEX Schedule 80 Conduit is available in 20’ lengths with the exception of the ½ and 3/4 inch trade sizes.
The measurements for each trade size listed above are the same with the exception of the length (L) which is
240 inches. The following is a list of the product numbers for each 20” conduit trade size: A53BA42 is the 1”
trade size; A53BC42 is the 1 1/4 “ trade size; A53BE42 is the 1 1/2’ trade size; A53CA42 is the 2” trade size;
A53CE42 is the 2 ½” trade size; A53DA42 is the 3” trade size; and A53EA42 is the 4” trade size.
Nonmetallic PVC Schedule 40 & 80 Conduit
BID ITEMS #34 SPEC#9-29.1(4)B
CANTEX INC. | 301 Commerce Street, Suite 2700, Fort Worth, TX 76102 | 817.215.7000 | www.cantexinc.com
Schedule 80 Standard Radius Elbows - Bell End
Schedule 80 Standard Radius 90° Elbow - Bell End
Schedule 80 Standard Radius 45° Elbow - Bell End
CANTEX 90-Degree Bell End
Schedule 80 Standard Radius
Elbows are used to change
the direction of a conduit run
by 90 degrees.
•Schedule 80 Extra Heavy
Wall Nonmetallic PVC
construction for strength
and durability
•For indoor or outdoor use•Suitable for aboveground
or buried
•Bell end for easy instal-
lation
•ETL Listed
•Made in USA
Part Number Trade Size Carton Qty.“R”“O”“H’“S” MIN “B” MIN “L”
5221056 1-1/4 30 7.250 7.250 7.250 2.000 1.500 11.375
5221057 1-1/2 30 8.250 8.250 8.250 2.000 2.000 13.000
5221058 2 15 9.500 9.500 9.500 2.000 2.000 15.000
5221059 2-1/2 18 10.500 10.500 10.500 3.000 2.250 16.500
5221060 3 14 13.000 13.000 13.000 3.125 2.500 20.375
5221061 4 10 16.000 16.000 16.000 3.375 3.250 25.125
5221062 5 30*24.000 24.000 24.000 3.625 4.250 37.625
5221117 6 25*30.000 30.000 30.000 3.750 5.000 47.125
* Pallet Quantity Dimensions are nominal
Conforms to UL651 and NEMA TC3
Material is Rigid PVC
Bend Tolerance is ±2°
Part Number Trade Size Carton Qty.“R”“O”“H’“S” MIN “B” MIN “L”
5221006 1-1/4 25 7.250 2.125 5.125 2.000 1.500 5.688
5221007 1-1/2 20 8.250 2.438 5.813 2.000 2.000 6.500
5221008 2 10 9.500 2.813 6.750 2.000 2.000 7.500
5221009 2-1/2 20 10.500 3.063 7.438 3.000 2.250 8.250
5221010 3 8 13.000 3.813 9.188 3.500 2.500 10.188
5221011 4 20 16.000 4.688 11.188 3.375 3.250 12.563
5221012 5 30*24.000 7.000 17.000 3.625 4.250 18.875
5221013 6 25*30.000 8.875 21.250 3.750 5.000 23.563
* Pallet Quantity Dimensions are nominal
CANTEX 45-Degree Bell End
Schedule 80 Standard Radius
Elbows are used to change the
direction of a conduit run by 45
degrees.
Conforms to UL651 and NEMA TC3
Material is Rigid PVC
Bend Tolerance is ±2°
•Schedule 80 Extra Heavy
Wall Nonmetallic PVC con-
struction for strength and
durability
•For indoor or outdoor use•Suitable for aboveground or
buried
•Bell end for easy installation
•ETL Listed
•Made in USA
BID ITEM#34 SPEC#9-29.1(4)B
CANTEX INC. | 301 Commerce Street, Suite 2700, Fort Worth, TX 76102 | 817.215.7000 | www.cantexinc.com
Schedule 40 Center Stop Coupling
Standard UL Schedule 40 Center Stop Coupling
Schedule 40 Standard Center Stop Couplings are used to join
lengths of conduit pipe together with two solvent weld socket ends.
•For use with Schedule 40 and Schedule 80 conduit
•Center stop to help determine proper depth of connection
•For use aboveground and underground and non-conduc-
tive and sunlight resistant
•Meets NEMA TC-3 Standards
•UL and CSA listed
•Made in USA
Part Number Trade Size Carton Qty.“W’“L”“ID”“D”
6141623 1/2 200 1.063 1.500 .875 .625
6141624 3/4 125 1.313 1.563 1.063 .625
6141625 1 70 1.625 2.000 1.313 1.000
6141626 1-1/4 40 2.000 2.125 1.688 1.000
6141627 1-1/2 30 2.250 2.375 1.938 1.063
6141628 2 40 2.688 2.600 2.375 1.192
6141629 2-1/2 20 3.250 3.500 2.875 1.750
6141630 3 40 4.000 3.875 3.500 1.188
6141631 3-1/2 30 4.1250 4.000 4.000 1.938
6141632 4 20 5.000 4.188 4.500 2.000
6141633 5 10 6.125 5.375 5.625 2.500
6141634 6 8 7.250 5.000 6.625 2.250
* 6141635D 8 1 9. 313 13.000 8.625 5.000
* Not UL Listed
Dimensions are nominal
SINGLE SOURCE FOR PVC ELECTRICAL
CANTEX offers an all-inclusive line of Schedule 40 & Schedule 80 PVC
electrical fittings and accessories. With several decades of experience
manufacturing PVC fittings and accessories, you can trust CANTEX to
provide quality products.
All of our PVC fittings are easy-to-install and offer non-conductivity, high
impact, tensile strength, industry certifications, and resistance to a wide
range of chemicals, acids, and salt. Our schedule 40 & 80 fittings and
accessories connect seamlessly with other standard schedule 40 & 80
products making it easy to convert entire electrical infrastructures to
PVC. See our full line of PVC electrical products at www.cantexinc.com.
BID ITEM#34 SPEC#9-29.1(4)B
CANTEX INC. | 301 Commerce Street, Suite 2700, Fort Worth, TX 76102 | 817.215.7000 | www.cantexinc.com
End Bell
PVC End Bell
SINGLE SOURCE FOR PVC ELECTRICAL
CANTEX offers an all-inclusive line of Schedule 40 & Schedule 80 PVC
electrical fittings and accessories. With several decades of experience
manufacturing PVC fittings and accessories, you can trust CANTEX to
provide quality products.
All of our PVC fittings are easy-to-install and offer non-conductivity, high
impact, tensile strength, industry certifications, and resistance to a wide
range of chemicals, acids, and salt. Our schedule 40 & 80 fittings and
accessories connect seamlessly with other standard schedule 40 & 80
products making it easy to convert entire electrical infrastructures to
PVC. See our full line of PVC electrical products at www.cantexinc.com.
Part Number Trade Size Carton Qty.“L”“ID”“OD”
5144003 1/2 100 1.000 .625 1.250
5144004 3/4 100 1.000 .875 1.500
5144005 1 50 1.250 1.063 1.750
5144006 1-1/4 50 1.313 1.375 2.125
5144007 1-1/2 50 1.563 1625 2.500
5144008 2 40 1.563 2.063 2.813
5144009 2-1/2 30 1.875 2.500 3.375
5144010 3 50 2.063 3.000 4.125
5144011 3-1/2 50 2.250 3.500 4.625
5144012 4 50 2.375 4.000 5.125
5144013 5 25 2.438 5.063 6.375
5144014 6 15 2.875 6.063 7.375
End Bells are used in concrete vault walls to provide a smooth,
safe entrance to the conduit outside. Protects wiring which is
being pulled through the vault wall.
* 8 inch trade size is not UL or CSA Listed
Dimensions are nominal
•For use with Schedule 40 and Schedule 80 conduit•Protects wiring which is being pulled through concretevault walls•Easy installation•Meets NEMA TC-9 Standards•UL and CSA listed•Made in USA
BID ITEM#34 SPEC#9-29.1(4)B
www.atkore.com
*UL 651 does not include 8”
ATCE-SPEC-6711-2402
Trade Size
Dimensions (in)
Average OD Minimum
Average ID
Minimum Wall
Thickness, T
Bell Entrance
A
Bell Bottom
B
Bell Length
C
1/2 0.840 0.502 0.147 0.852 0.836 1.75
3/4 1.050 0.698 0.154 1.064 1.046 2.25
1 1.315 0.910 0.179 1.330 1.310 2.25
11/4 1.660 1.227 0.191 1.677 1.655 2.25
11/2 1.900 1.446 0.200 1.918 1.894 2.75
2 2.375 1.881 0.218 2.393 2.369 4.00
21/2 2.875 2.250 0.276 2.890 2.868 4.00
3 3.500 2.820 0.300 3.515 3.492 4.00
31/2 4.000 3.280 0.318 4.015 3.992 4.00
4 4.500 3.737 0.337 4.515 4.491 5.00
5 5.563 4.713 0.375 5.593 5.553 5.75
6 6.625 5.646 0.432 6.658 6.614 6.50
8*8.625 7.455 0.500 8.670 8.610 6.50
Trade Size 10-foot Length 20-foot Length Approximate
Weight per 100’
(lbs)Part Number Crate Quantity (ft) Part Number Crate Quantity (ft)
1/2 8005010 6,000 8005020 12,000 21
3/4 8007510 4,400 8007520 8,800 28
1 8010010 3,600 8010020 7,200 41
11/4 8012510 3,300 8012520 6,600 57
11/2 8015010 2,250 8015020 4,500 73
2 8020010 1,400 8020020 2,800 100
21/2 8025010 930 8025020 1,860 153
3 8030010 880 8030020 1,760 205
31/2 8035010 630 8035020 1,260 250
4 8040010 570 8040020 1,140 312
5 8050010 380 8050020 760 433
6 8060010 260 8060020 520 595
8*8080010 140 8080020 280 904
•Conforms to UL 651 and NEMA TC 2
•Sunlight resistant per UL 651
•Listed for 90º C conductors or cable
•Product manufactured with one integral
solvent-weld bell standard per length
BID ITEM#34
PVC Rigid Schedule 80 Conduit
SPEC#9-29.1(4)B
www.alliedeg.us ATCE-SPEC-5015-1909
Conforms to NEMA TC-3
Trade Size Bell EntranceA Bell BottomB Bell LengthC Tangent Length D1/2 0.852 0.836 1.250 1.7503/4 1.064 1.046 1.250 1.75011.330 1.310 1.625 2.1251-1/4 1.677 1.655 1.750 2.250
1-1/2 1.918 1.894 2.250 2.250
2 2.393 2.369 2.250 2.250
2-1/2 2.890 2.868 2.750 3.250
3 3.515 3.492 2.875 3.375
3-1/2 4.015 3.992 3.000 3.500
4 4.515 4.491 3.500 3.625
5 5.593 5.553 4.375 4.625
6 6.658 6.614 5.250 5.500
8 8.670 8.610 6.250 6.500
Dimensions are nominal (inches) and are subject to normal manufacturing tolerances
Not all Radii/Angles are available in every size - consult sales catalog for details
Available with Standard or Special (18", 24", 36", 48", 60") Radius
Available in both Bell-End and Plain-End versions. Bell dimensions do not apply to Plain End Elbows
6" & below tested and certified by ETL Intertek to UL651
•Dimensions are nominal (inches) and are subject to normal manufacturing tolerances
•Not all radii/angles are available in every size – consult sales catalog for details
•Available with standard or special (18", 24", 36", 48", 60") radius
•Available in both Bell-End and Plain-End versions. Bell dimensions do not apply to Plain End Elbows
• 6" and below tested and certified by ETL Intertek to UL651. UL 651 does not include 8"
•Conforms to NEMA TC-3
Trade Size(in)Bell Entrance A Bell BottomB Bell Length C Target LengthD
1/2 0.852 0.836 1.250 1.750
3/4 1.064 1.046 1.250 1.750
1 1.330 1.310 1.625 2.125
11/4 1.677 1.655 1.750 2.250
11/2 1.918 1.894 2.250 2.250
2 2.393 2.369 2.250 2.250
21/2 2.890 2.868 2.750 3.250
3 3.515 3.492 2.875 3.375
31/2 4.015 3.992 3.000 3.500
4 4.515 4.491 3.500 3.625
5 5.593 5.553 4.375 4.625
6 6.658 6.614 5.250 5.500
8 8.670 8.610 6.250 6.500
Conforms to NEMA TC-3
Trade Size
Bell Entrance
A
Bell Bottom
B
Bell Length
C
Tangent Length
D
1/2 0.852 0.836 1.250 1.750
3/4 1.064 1.046 1.250 1.750
1 1.330 1.310 1.625 2.125
1-1/4 1.677 1.655 1.750 2.250
1-1/2 1.918 1.894 2.250 2.250
2 2.393 2.369 2.250 2.250
2-1/2 2.890 2.868 2.750 3.250
3 3.515 3.492 2.875 3.375
3-1/2 4.015 3.992 3.000 3.500
4 4.515 4.491 3.500 3.625
5 5.593 5.553 4.375 4.625
6 6.658 6.614 5.250 5.500
8 8.670 8.610 6.250 6.500
Dimensions are nominal (inches) and are subject to normal manufacturing tolerances
Not all Radii/Angles are available in every size - consult sales catalog for details
Available with Standard or Special (18", 24", 36", 48", 60") Radius
Available in both Bell-End and Plain-End versions. Bell dimensions do not apply to Plain End Elbows
6" & below tested and certified by ETL Intertek to UL651
BID ITEM# 34
Elbows Schedule 40 and Schedule 80
SPEC#9-29.1(4)B
www.atkore.com
•Listed to UL 651
•Conforms to NEMA TC 3
•Injection molded with center stop
*8 inch products are not included in UL 651 or NEMA TC 3
ATCE-SPEC-6708-2402
Trade Size Part Number
Average Dimensions (in)Package Quantity
Length (L) Socket Depth (D) Socket ID
½CP05 1.51 0.72 0.85 200
¾CP07 1.58 0.75 1.06 125
1 CP10 1.89 0.91 1.33 70
1¼CP12 2.03 0.97 1.68 40
1½CP15 2.42 1.15 1.92 30
2 CP20 2.45 1.17 2.39 40
2½CP25 3.76 1.80 2.89 20
3 CP30 3.97 1.91 3.52 40
3½CP35 4.23 2.02 4.02 30
4 CP40 4.22 2.03 4.52 20
5 CP50 4.08 1.97 5.59 10
6 CP60 6.43 3.00 6.69 8
8*CP80 8.34 4.02 8.65 1
BID ITEM# 34
PVC Molded Couplings
SPEC#9-29.1(4)B
www.atkore.com ATCE-SPEC-6707-2402
Trade Size Part Number
Average Dimensions (in)
Package QuantityLength
(L)Socket ID Flared End ID
(A)
1/2 MEB05 1.00 0.85 0.63 100
3/4 MEB07 1.00 1.06 0.88 100
1 MEB10 1.20 1.33 0.95 50
11/4 MEB12 1.24 1.68 1.32 50
11/2 MEB15 1.36 1.92 1.64 50
2 MEB20 1.55 2.39 2.12 40
21/2 MEB25 1.89 2.89 2.58 30
3 MEB30 1.93 3.52 3.12 50
31/2 MEB35 2.11 4.02 3.62 50
4 MEB40 2.18 4.52 4.10 50
5 MEB50 2.39 5.59 5.11 25
6 MEB60 2.57 6.69 6.12 15
8 MEB80 6.00 8.67 8.12 1
•Suitable for use with Schedule 40 or Schedule 80 conduit
•Also compatible with EB or DB duct
BID ITEM# 34
PVC Molded End Bells
SPEC#9-29.1(4)B
Solvent Cement & Primer for Conduit & Fittings
Part Number Size Carton Qty.
7210601 1/2 Pint 24
7210602 Pint 12
7210603 Quart 12
Part Number Size Carton Qty.
7210501 1/2 Pint 24
7210502 Pint 12
7210503 Quart 12
Low Voc Conduit Cement No. 99 - Gray
Low Voc Conduit All Weather Cement
Part Number Size Carton Qty.
7211303 Quart 12
Part Number Size Carton Qty.
7210411 1/2 Pint 24
7210412 Pint 12
7210413 Quart 12
CANTEX PVC cements and primers are for use on rigid PVC Electrical conduit and fittings.
We recommend the use of CANTEX PVC cements and primers with CANTEX PVC products
since they are especially formulated for use with our products.
DO NOT USE FOR WATER, SEWER OR DWV INSTALLATIONS.
ENT NO. 50 Low Voc Cement
Solvent Cement for EZ-FLEX ENT
Part Number Size Carton Qty.
7210402 Pint 12
7210403 Quart 12
Pipe Size 1/2”3/4”1”1-1/4”1-1/2”2”2-1/2”3”4”5”6”
Cement 1/2 1/2 1/2 1 1 1 1-1/2 1-1/2 2 2-1/2 4
Primer 1/2 1/2 1/2 1 1 1 1-1/2 1-1/2 2 2-1/2 4
ESTIMATED SOLVENT REQUIREMENT PER 1,000 FEET IN QUARTS One weld per 20 feet
Conduit Primer No. 10
Operating temperature
range is -15˚F to 110˚F.
Operating temperature
range is 50˚F to 100˚F.
CANTEX INC. | 301 Commerce Street, Suite 2700, Fort Worth, TX 76102 | 817.215.7000 | www.cantexinc.com
Low Voc Conduit Cement No. 99
BID ITEM#34 SPEC#9-29.1(4)B
PLASTI-WELD™
403 SERIES MEDIUM GRAY
PVC SOLVENT CEMENT
Page 1 of 2
TECHNICAL SPECIFICATION: Plasti-Weld 403 Series Medium Gray PVC Solvent Cement is recommended for solvent welding all schedules
and classes of PVC pipe and fittings up to 6” with interference fit. Medium Gray PVC Solvent Cement can be used for potable water, sewer
and drain, waste and vent systems. This product is compliant with California South Coast Air Quality Management District (SCAQMD) Rule
1168 and Ozone Transport Commission (OTC) regulations for Volatile Organic Compound emission levels. Note: This product is not for use
in a system using or being tested by compressed air or gases.
PHYSICAL/CHEMICAL PROPERTIES
Appearance Gray Liquid
Viscosity minimum 500 cps @ 73° F ± 2° F
Density 7.74 ± 0.2 lbs/gallon
Lap Shear Strength (minimum per ASTM Standards)
2 hours 250 psi
16 hours 500 psi
72 hours 900 psi
Set Up Time
30° F to 50° F 5 – 6 minutes
50° F to 70° F 3 – 4 minutes
70° F to 90° F 1 – 2 minutes
Shelf Life 3 years from manufacture date
Maximum VOC per SCAQMD 1168/316A or BAAQMD
Method 40: 510 g/L
INGREDIENTS (CAS Number)
Acetone (67-64-1)
Amorphous Silica (112945-52-5)
Cyclohexanone (108-94-4)
Gray Colorant (N/A)
Methyl Ethyl Ketone (78-93-3)
PVC Resin (9002-86-2)
Tetrahydrofuran (109-99-9)
LISTINGS
NSF Standard 61 IAPMO Listed
for PW, DWV, SEWER
Meets ASTM Standard D 2564
PRODUCT NUMBER SIZE PACK CARTON WEIGHT
40366S 4 fl. oz. 24 9 lbs.
40356S 8 fl. oz 24 16 lbs.
40346S 16 fl. oz. 24 27 lbs.
40336S 32 fl. oz. 12 26 lbs.
40324 Gallon 6 52 lbs.
1/2010
PLASTI-WELD™
403 SERIES MEDIUM GRAY
PVC SOLVENT CEMENT
Page 2 of 2
PRECAUTIONS
Read all information carefully before using this product.
DANGER: EXTREMELY FLAMMABLE. VAPORS MAY CAUSE
FLASH FIRES. MAY IRRITATE EYES AND SKIN. VAPOR
HARMFUL. MAY IRRITATE RESPIRATORY TRACT AND CAUSE
CENTRAL NERVOUS SYSTEM DEPRESSION. HARMFUL OR FATAL
IF SWALLOWED.
May cause irritation to eyes, skin, and nose, throat, and
respiratory tract. May cause coughing, sore throat, difficulty
breathing, headache, dizziness, nausea. Long term repeated
overexposures to solvents may cause damage to the brain,
nervous system, reproductive system, respiratory system,
mucous membranes, liver, and kidneys. KEEP OUT OF REACH OF
CHILDREN.
FIRST AID: If swallowed, DO NOT INDUCE VOMITING. Drink
water and call a doctor or poison control center immediately.
This product may be aspirated into the lungs and cause chemical
pneumonitis, a potentially fatal condition. If contact with eyes,
flush with water for 15 minutes and seek medical attention if
irritation persists. If contact with skin, flush with water and then
use baby oil or hand cleaner to remove residue. If inhaled and ill
feelings develop, get fresh air and obtain medical attention if ill
feelings persist. FOR EMERGENCY FIRST AID INSTRUCTIONS
CALL 1-877-740-5015.
FIRE: Use dry chemical, foam, or carbon dioxide extinguisher.
Water spray may be applied to reduce potential vapors or for
cooling. Burning liquid extinguished with water will float and
may re-ignite on surface of water.
SPILLS: Remove all sources of ignition and ventilate area.
Personnel cleaning up the spill should wear appropriate personal
protective equipment, including respirators if vapor
concentrations are high. Soak up spill with absorbent material.
Put absorbent material in covered, labeled metal containers.
Dispose of in accordance with local regulations.
A fire or explosion may result if dry granular calcium
hypochlorite is used to disinfect plastic piping systems and is
exposed to organic vapors found in solvent cements, cleaners or
primers. Do not disinfect piping system with dry granules. Do
not store dry granular calcium hypochlorite near solvent
cements, cleaners or primers. DO NOT REUSE EMPTY
CONTAINER. KEEP OUT OF REACH OF CHILDREN.
Refer to material safety data sheet for more information.
1/2010
DIRECTIONS FOR USE
Read all directions carefully before using this product.
• Do not breathe vapors. Use only in well ventilated area. If
forced air ventilation is used, be sure it does not cause a fire
hazard from solvent vapors. If adequate ventilation cannot be
provided, wear a NIOSH-approved respirator for organic
solvents. • Do not use or store near heat, sparks, or flames.
Do not smoke, eat or drink when using. Do not take internally.
Vapors may accumulate in low places and may ignite
explosively. • Store and use at temperatures between 40ºF
and 110ºF. At temperatures outside of this range, special care
must be taken to prepare good joints and prevent exposures
to solvents. • Stir or shake before using; if jelly-like, don’t use.
Keep container closed when not in use. • Avoid eye and skin
contact - wear safety glasses with side shields and wear
rubber gloves. • Do not thin.
1.Square pipe ends and remove all burrs and dirt.
2.Check dry fit of pipe and fitting. Pipe should easily go 1/3
of the way into the fitting. If the pipe bottoms, it should
be snug.
3.Use a suitable applicator at least 1/2 the size of the pipe
diameter. For larger size pipe systems use a natural
bristle brush or roller.
4.Clean pipe and fitting with a listed primer.
5.Apply liberal coat of cement to pipe to the depth of the
socket; leave no uncoated surface.
6.Apply a thin coat of cement to inside of fitting; avoid
puddling of cement. Puddling can cause weakening and
premature failure of pipe or fitting. Apply a second coat
of cement to the pipe.
7.Assemble parts QUICKLY. Cement must be fluid. If
cement surface has dried, recoat both parts.
8.Push pipe FULLY into fitting using a 1/4 turning motion
until pipe bottoms.
9.Hold pipe and fitting together for 30 seconds to prevent
pipe push-out – longer at low temperatures. Wipe off
excess.
10.Allow 15 minutes for good handling strength and 2 hours
cure time at temperatures above 60ºF before hydrostatic
pressure testing up to 180 psi. Longer cure times may be
required at temperatures below 60ºF or with pipe
diameters over 3”. DO NOT TEST WITH AIR.
This product is not for use with caustic or acidic chemical
solutions. Consult Technical Department for more
information.
Before purchase and use of a product, review the product application and be
certain the product, installation and use will be in compliance with any applicable codes and regulations.