HomeMy WebLinkAboutS-404603w z < Q Z 0 L / , z w O LL1 UJ LJ z 1--1 1 LU LU (n V /I 0 z M TTTI 0 Sanitary Sewer Notes and Specifications THESE NOTES SHALL APPEAR ON PROJECTS FOR THE WASTEWATER UTILITY. 1. All work and work material shall be in conformance with the standards and specifications of the City of Renton Planning/Building/Public Works Department and the latest edition of the WSDOT/APWA Standards and Specifications, as approved and modified by the City of Renton in the Renton Standard Plans & Specifications. A set of approved plans shall be kept on site at all times during construction, 2, The hours of work in the street right of way shall be per City specifications on weekdays unless otherwise approved in writing by the Planning/Building/Public Works Department. An approved traffic control plan must be obtained prior to beginning any work within public right of way. 3. All locations of existing utilities shown are approximate and it shall be the contractor's responsibility to verify the true and correct location so as to avoid damage or disturbance. 4. A pre -construction conference and a 24 hour notice shall be required prior to starting new construction, It shall be the contractor's responsibility to secure all necessary permits prior to starting construction. (Inspection will be accomplished by a representative of the City of Renton,) It shall be the contractor's responsibility to notify the Public Works inspector 24 hours in advance of backfilling all construction. 5. Contractor is solely responsible for the means, methods and sequences of construction and for the safety of workers and others on the construction site. 6. It shall be the responsibility of the contractor to obtain street use and any other related permits prior to any construction. 7. Plans approved by the City of Renton, Public Works Department shall take precedence over all other plans. S. A copy of these approved plans must be on the job site whenever construction is in progress, 9. The contractor shall provide the City of Renton with an as -built drawing of the sanitary sewer system, which has been stamped and signed by a licensed professional engineer or licensed professional surveyor. 10. Backfill shall be placed equally on both sides of the pipe in layers with a loose average depth of 6 inches, maximum depth of 8 inches, thoroughly tamping each layer to 95 percent of maximum density. These compacted layers must extend for one pipe diameter on each side of the pipe or to the side of the trench. Materials to complete the fill over pipe shall be the same as described, 11.Open cut road crossings for utility trenches on existing traveled roadway shall be backfilled with crushed rock and mechanically compacted unless otherwise approved by 12. Datum for Vertical Control shall be North American Vertical Datum 1988 Meters, and for Horizontal Control shall be North American Datum 1983/1991 Meters unless otherwise approved by the City of Renton Public Works Department. Reference benchmark and elevations are noted on the plans. 13. All disturbed areas shall be seeded and mulched or otherwise stabilized to the satisfaction of the Department for the prevention of on -site erosion after the completion of construction, 14. All pipe and appurtenances shall be laid on a properly prepared foundation in accordance with the standards and specifications of the City of Renton Planning/Building/Public Works Department and the latest edition of the WSDOT/APWA Standards and Specifications, as approved and modified by the City of Renton in the Renton Standard Plans & Specifications. This shall include necessary leveling of the trench bottom or the top of the foundation material, as well as placement and compaction of required bedding material, to uniform grade so that the entire length of the pipe will be supported on a uniformly dense, unyielding base. Pipe bedding shall be pea gravel 6 inches above and below the pipe. 15. Sanitary sewer pipe shall be polyvinyl chloride (PVC) rubber gasketed ASTM D 3034, SDR 35, or ductile iron class 50, unless otherwise approved by the Wastewater Utility. 16. In unimproved areas, manhole to extend minimum 6 inches and maximum 12 inches above finished grade or must have minimum 2' diameter concrete ring poured at grade. In paved area, cover must slope in all directions to match paving. IN COMPLIANCE WITH CITY OF RENTON STANDARDS WASTEWATER UTILITY } dchristen 04/02/2019 DEVELOPMENT ENGINEERING jchavez 03/29/2019 0� SEAL WTH AR 4000 OR APPROVED EQUAL AND DRY SAND AFTER PATCHING PLAN NTS PUBLIC SANITARY SEWER EXTENSION A DEPTH OF CLASS "B" ASPHALT TO BE 2" BELOW BOTTOM OF THE UPPER ADJUSTMENT RING OR A MINIMUM OF 8" WHICHEVER S GREATER. MORTAR JOINT(5) (3/8" MIN.) SEE NOTE 3 AND SPECIAL PROVISION 7-05.3(1) L ADJUSTMENT RING (1" MIN.) OR BRICKS. SEE NOTE 4 S'F_ C I'O N-_A - A NOTFS 1. REMOVE PAVEMENT AND BASE MATERIALS FOR A DISTANCE 3 ALL JOINTS BETWEEN THE CONE, ADJUSTMENT RINGS, WHICH IS EQUAL TO THE DIAMETER OF THE FRAME PLUS FOUR BRICKS AND FRALIE SHALL BE GROUTED FEET, ADJUST CASTING FRAME TO PAVEMENT SURFACE USING RISER RINGS OR CONCRETE BLOCKS PER STD PLAN 4 ADJUSTMENT OF THE FRAME TO GRADE SHALL BE 400.1. ACCOMPLISHED WITH A COMBINATION OF ADJUSTMENT RINGS, BRICKS AND MORTAR ONLY BRICKS SHALL BE 2 REPLACE EXCAVATED MATERIAL WITH A MINIMUM OF 8" OF STAGGERED TO CREATE A RUNNING BOND OR 1I2 BOND. T!) CLASS 'B" ASPHALT OR TO A DEPTH THAT IS 2" BELOW THE USE OF SHIMS IS F±R0419ITEO. 801TOM OF THE UPPER ADJUSTMENT RING WHICHEVER IS GREATER OR AS APPROVED BY THE ENGINEER. SM. PIAN - KS TYPICAL UTILITY COVER _ _- PUBLIC WOR,A PAO _ �-�.-"�._�..- +� + ADJUSTMENT FOR j DEPAR i MENT _l' Ctl't PAVEMENT OR OVERLAY S o"e�`. uww.. o DAiK 7' 1 L 'B' } NOT TO SCALE MANHOLE FRAME AND COVER SEE STD. PLAN 401 ADJUSTMENT RINGS (2" MIN.) SEE NOTE 6 MORTAR JOINT(S) (3/8" MIN.) SEE NOTE 5 CONE (ECCENTRIC) RUBBER GASKETED JOINTS IN ACCORDANCE WITH ASTM C-443 STEPS - POLYPROPYLENE STEPS SHALL BE INCLUDED CONCRETE RISER BY PIPE INC., OR APPROVED EQUAL. LADDER -POLYPROPYLENE SHALL BE ATTACHED -0 MANiOLE MAX. PIPE SIZE - 'E' CONCRETE SHELF PRECAST BASE SECTION OR CAS- IN SHELF. A, B, :C, 1:). E, 48" MH 4B" 6" MIN. 5"M-N 24" MIN, 21" 1. D. 54" MH ~� 54" 8" MIN. 5.5" MIN. 24" MIN. 24" LD. 60" MH 60" 8" MIN. 6" MIN, 42" MIN. 30" I.D. NOTES: 1. STEPS TO BE POLYPROPYLENE SAFETY STEPS. 2, STEPS ARE TO BE IN 'LACE BEFORE MANHOLE SECTIONS ARE INSTALLED. 3. CASTING SHALL BE PER S ID. PLAN 401. 4. MANHOLE SECTIONS TO BE OF REINFORCED PRECAST CONCRETE. 5. ALL JOINTS BETWEEN THE CONE, RISER RINGS, BRICKS AND CASTING SHALL BE GROUTED. 6. ADJUSTMENT OF THE CASTING TO GRADE SHALL BE ACCOMPLISHED WITH A COMBINATION OF ADJUSTMENT RINGS, BRICKS AND MORTAR ONLY. BRICKS SHALT_ BE STAGGERED TO CREATE A RUNNING BOND OR 1/2 BOND. THE USE Or SL1IM5 IS PROHIBITED, 7. SANITARY SEWER MANHOLES SHALL HAVE ALL INTERIOR SURFACES, INCLUDING CHANNELING, COATED (SEALED) WITH A H'GH SOLIDS URETHANE COATING; WASSER M.C-AROSHIELD OR APPROVED EQUAL; COLOR OF COATING SHALL BE WHITE. B. RUBBER GASKETED JOINTS SHALL BE IN CONFORMANCE VATH ASTM C-443, 9. CHANNEL HEIGHT SHALL BE A MINIMUM OF 3/4 OF THE INSIDE DIAMETER OF THE LARGESr PIPE. 10, CONNECTIONS TO MANHOLE SHALL BE MADE USING GPK ADAPTOR, KOR-N-SEAL BOOTS OR APPROVED EQUA. 11.IN UNIMPROVED AREAS, MANHOLES SHALL EXTEND A MINIMUM OF 6" AND A MAXIMUM OF 12" ABOVE FINISHED GRADE OR MUST HAVE A MINIMUM 2' DIAMETER CONCRETE RINGS POURED AT GRADE. IN PAVED AREAS, COVER MUST SLOPE IN ALL DIRECTIONS TO MATCH PAVING, STD. PLAN - 400.1 +fL®l+ PUBLIC WORKS STANDARD SANITARY MANHOLE - Tl DEPARTMENT SEPTEMBER 2011 �•� S.MIDD �1� J • LARSON and ASSOCIATES0C1ATE8 ' i ! i 10 ryM� ""' """ c0,6- . � �. ,# ��' . CIS Eg Q4' 9027 PACIFIC A WWU& SUITE 4 N ' E�G� •� TACOMA. WA 98444 (253) 474-3404 I , `� 1 ��•• 30LTHOLES - 3 PLCS EQUALLY SPACED 120• APART ON 23 1/16' (586mm) DIA B.C. (SEE DETAIL) SEWER N111E M "tA COVER & FRAME PLAN VIEW 25' DIA, E635mm] 1` 3/4' C25,m] 1 C19mm7 r 8 3/4'1 L 2 1/2' - 1?22mm] C64mm] TYP COVER SECTION VIEW _ 26 1/2' DIA [673mm] 25 1/4' DIA [641Mr^] F 1 1/16' 1/4' (Gmm) D:A I 127mml NEL'PRENE GASKET tl }6' jjAT [15' mm] 5/8' J 23 3/8' DIA CL OPEN E16mm] 1[594mm. 27 5/16' DIA _ [694mm] 34 1/8' DIA__ COVER BOTTOM VIEW BLT SDC, (ALLEN HEAD) 5/8'-11 X 1.5 SS RUBBER WASHER EON BOLTING DETAIL 1/4' 1 1/16' C6mm] 127mm; I/B' C3mm] 1/0' CR3mm] GASKET GROOVE DETAIL [867mm1 N01E& FRAME SECTION VIEW 1. ALL COVERS SHALL BE LOCKING LID PER EAST JORDAN IRON WORKS INC. No. 3717C1 OR EQUAL. 2. USE FRAME AND COVER FOR STORM (SPECIFY "DRAIN" ON COVER), SANITARY (SPECIFY "SEWER"), OR WATER (SPECIFY "WA -TER"), STD. PLAN - 401 + + PUBLIC WORKS MANHOLE FRAME AND COVER - - )� DEPARTMENT F--'D DECEMBER 2008 -EX. SEWER MAIN SPOOL (LENGTH AS NEEDED) 8" SEWER STUSE PROPERTY UNf 7r FUTURE 4" SIDE SrWER SEWER MAIN TEE X 6" TEE I z� =J I i COUPLING (TYP.) a I I �I 3 II I r --- __. _..-__---- T _----__- J T-_---_--_ BEND AS - REQUIRED, 2"x 4" STUD MARKING POST PANTED 8" CAP J WHITE WITH THE WORD "SEWER" STENGLED IN 3" HIGH BLACK LETTERS AND #6 WIRE WRAPPED AROUND THE STUD AND EXTENDED TO THE TOP OF THE STUD. 6'X6"X6' SURFACE CLEANOUT WITH CAST IRON RING AND COVER (EAST JOROAN IRON WORKS PRODUCT NO, 00367502 OR APPROVED EQUAL, SPECIFY "SEWER" ON LID), (SEE STD. PLAN 403.1 rDR INSTALLATION) JM EAGLE THREADED CLEAN -OUT ADAPTER HUB & PLUG (OR APPROVED EQUAL) EXISTING SANITARY E3 SEWER MAIN y X IN. L E FUTURE 4" SIDE SEWER 1 �6" SEWER STUB 6"X8'X8' WYE FUTURE 6"x 4' REDUCER `SEWER MAIN SIZE X 8" TEE 0QMIAffLL iltx=&E5.E4it SIDE SEWER.D(}y CI1L�ILI4 ExISIDNG.SEriELt_9tA1R A. VITRIFIED CLAY MAIN - CUT IN A NEW PVC 'TEE" USING "STRONG" -BACK" FLEXIBLE COUPLINGS (FERNCO OR APPROVED EQUAL). B. CONCRETE MAIN - CUT IN A NEW PVC "TEE' USING "STRONG -BACK" FLEXIBLE COUPLINGS (FERNCO OR APPROVED EQUAL). C. PVC & C900 PVC MAIN -- CUT IN NEW TEE USING RIGID COUPLINGS OR CORE -DRILLED WITH A ROMAC SADDLE (OR APPRCVED EQUAL). D. DUCT LE IRON MAN - CORE -DRILLED WITH A ROMAC SADDLE (OR APPROVED EQUAL) E. MANHOLE CONNECTION - ALL CONNECTIONS TO MANHOLES SHALL BE AT MANUFACTURED KNOCK -OUTS OR THE STRUCTURE SHALL BE CORE -DRILLED. 5 30M PSI MIX /ah CONCRETE ' pN D�M�N BLOCKING ry5 *�• 9� d _�CMIN SLOPE 6" TEE // HORIZONTAL 6" MIN. SEWER / SEWER MAIN MAIN 90NGREIE BLOCKING ANGLE OF_TTEE AT MAIN BETWEEN 25' AND 45' TYPICAL SIDE SEWER NOTE: UNLESS OTHERWISE SHOWN ON PLAN, SIDE SEWER SHALL HAVE A MINIMUM 2,5' COVER AT PROPERTY UNE OR 3-5' LOWER THAN THE LOWEST HOUSE ELEVATON, WHICHEVER IS LOWER. STANDARD SIDE SEWER STD. PLAN .406.1 URIPUBLIC WORKS AF -VE n DEPARTMENT INSTALLATION (SEWER MAIN TO PROPERTY LINE)e� LARSON_AND_ASSOCIATES SCALE. "= DESIGNED: 1 40' GJM DRAWN: JHD ONE INCH CHECKED: AT FULL SCALE GJM IF NOT ONE INCH NO. REVISION BY DATE APPR APPROVED: SCALE ACCORDINGLY APPROVED VERTICAL NAVD 1988 HORIZONTAL: NAD 1983/1991 DATU M RECESSED LIFT POCKET • SEWER 10-1/2" 1/4 i`-12-1/2"- 2-1/4" 14" 2-3/4" 2-1/4 CAST IRON RING AN Not to Scale FRAME III ALIC=M i'-n" NOTES: 1. 8" AND 6" CLEAN -OUT RINGS AND COVERS ON SEWER MAINS SHALL BE EAST JORDAN IRON WORKS, INC. No. 3698 (PRODUCT NO. 00369803) OR APPROVED EQUAL. CLEAN OUT SHALL BE A WATER TIGHT ASSEMBLY. 2. IN UNIMPROVED AREAS, POUR A V-0" THICK, 2'- 0" SQUARE CONCRETE, CLASS 3000, PAD AROUND THE RING AND COVER. OR DABLE STD. PLAN - 403.1 �® PUBLIC WORKS 8" OR 6" CLEANOUT °� DEPARTMENT FOR SANITARY SEWER MAIN IWk N nb, D*E VARIES4.5' MIN. LANE LINE \MARKING SAWCUT AFTER BACKFILL DEPTH OF EXISTING PAVEMENT 1 � 2" - 6" HMA (SEE NOTE 2) I 1' EDGE OF PAVEMENT, EDGE OF CURB & GUTTER, OR MIN. MIN. CENTER OF LANE MARKING 2" HMA (SEE NOTE 2) 6" CRUSHED SURFACING TOP COURSE (CSTC) (9-03.9(3)) PER WSDOT STANDARD 2" SAWCUT AND REMOVE SPECIFCATIONS, COMPACTED TO 95% OR PLANE, SEAL WITH MODIFIED PROCTOR AR-4000W CSTC, BANK RUN GRAVEL FOR TRENCH BACKFILL. (9-03.19), GRAVEL BORROW (9-03.14(1)) PER --- WSDOT STANDARD SPECIFICATIONS OR NATIVE MATERIAL IF APPROVED IN WRITING BY ENGINEER BASED ON GEOTECH REPORT, COMPACTED TO WIDTH OF TRENCH AS REQUIRED BY SIZE OF O 95% MODIFIED PROCTOR. PROPOSED IMPROVEMENT (SEE WSDOT STANDARD SPECIFICATION 2-09.4) PLUS AN PIPE ZONE BEDDING MATERIAL AND COMPACTION AS ALLOWANCE FOR ANY SHORING, SHORING, IF J REQUIRED BY THE WSDOT STANDARD SPECIFICATIONS NEEDED, SHALL MEET THE REQUIREMENTS OF FOR THE TYPE OF IMPROVEMENT INSTALLED, EXCEPT: WSDOT STANDARD SPECIFICATION 7-08.3(1)B * FOR STORM AND WATER PIPE, PER STD PLAN 220.0 F�--� * FOR SANITARY SEWER, PER STD PLAN 405 TRENCH WIDTH ' FOR JOINT UTILITY TRENCH, SAND WITH 95% PASSING A #4 SIEVE AND LESS THAN 5% PASSING A #200 SIEVE NOTES: 1. WHEN EXISTING PAVEMENT IN A LANE REQUIRING A FULL WIDTH REPLACEMENT IS BROKEN OR DETERIORATED TO A PAVEMENT CONDITION INDEX RATING OF 70 OR LESS, THE EXISTING PAVEMENT IN THAT LANE, AND FOR THAT DISTANCE SO CLASSIFIED, SHALL BE REMOVED AND REPLACED WITH HMA MATCHING THE DEPTH USED IN THE EXISTING STREET OR THE DEPTH PER CITY STANDARD, WHICHEVER IS GREATER. 2 PRINCIPAL/ MINOR/COLLECTOR, ARTERIAL, & INDUSTRIAL ACCESS STREETS - MATERIAL AND THICKNESS SHALL BE HMA CL f" PG 64-22 AND MATCH EXISTING THICKNESS AND IN NO CASE LESS THAN 6". RESIDENTIAL ACCESS STREETS - HMA CL }" PG 64-22. THE THICKNESS SHALL BE THAT OF THE EXISTING PAVEMENT SECTION AND IN NO CASE LESS THAN 4". 3. WHEN THE "SAWCUT AFTER BACKFILL" ENCROACHES INTO AN ADJACENT LANE, CURB & GUTTER OR SHOULDER, THE AFFECTED LANE SHALL BE PLANED AND OVERLAID WITH HMA FULL WIDTH, THE CURB & GUTTER SHALL BE REMOVED AND REPLACED, OR THE SHOULDER SHALL BE PLANED OR REMOVED AND OVERLAID WITH HMA. 4. IF TRENCH UNDERMINES EXISTING SIDEWALK AND/OR CURBS, THEN THE SIDEWALK AND/OR CURB SHALL BE REPLACED FROM EXPANSION JOINT TO EXPANSION JOINT. 5, IF TRENCHING THROUGH EXISTING DRIVEWAY OR SIDEWALK RAMP, THE DRIVEWAY OR SIDEWALK RAMP SHALT. BE REPLACED TO MEET ADA STANDARDS. STDTYPICAL LONGITUDINAL PATCH' PLAN - 110.1 PUBLIC WORKS FOR FLEXIBLE PAVEMENT OR DEPARTMENT RLAY )0 14S RIGID PAVEMENT WITH OVE/ t" R CITY OF ML RENTON Planning/Building/Public Works Dept. SOUTH _132ND_STREET SEWER_ LINE_ EXTENSION 8681BASE As-Builts O O (D O CD 0 00 IZ Z O Z W I__ X LU W Z_ J I IZ W S- 404602 LU �I DATE: 3/27/19 QI FIELDBOOK: BOOK CU PAGE` PAGE co T DRAWING NO: 8681 SHEET: OF: 3 4 U) AHNNNINAA