HomeMy WebLinkAbout04-21-2026 - Addendum 2 - PlansPUMP CONTROL PANEL, "PCP", 480V, 3Ø, 4W, NEMA 4X, 42 KAIC WITHSTAND GND BUS NEUTRAL SPD "L" 240/120V 480V 10 kVA 1Ø, 3W, 240/120V 3% REACTORS 3% REACTORS ONE-LINE DIAGRAM 200/3 TM DIGITAL METER GND BUS S/N GROUNDING MAIN SERVICE DISCONNECT SWITCH AUTOMATIC TRANSFER SWITCH, "ATS" STANDBY GENERATOR GROUND PER N.E.C. M HARMONIC FILTER HARMONIC FILTER PUMP 1 (15 HP)21.0 A X 1.25 =26.3 AMPS PUMP 2 (15 HP)21.0 A X 1.00 =21.0 AMPS PUMP STATION HEATER (5 KW)6.7 A X 1.00 =6.7 AMPS LIGHTING TRANSFORMER (10 kVA)12.1A X 1.00 =12.1 AMPS TOTAL 66.1 AMPS 100/3 TM 200/3 TM, SE 30/3 TM 30/3 TM 30/2 TM 50KW EXISTING SECONDARY POWER EXISTING SECONDARY POWER HAND HOLE 4 MAIN SERVICE DISCONNECT SWITCH LIGHTING TRANSFORMER 2 3 PEDESTAL REBAR MAT UFER CONNECTION #6 MIN. #4 MIN. ATS WET WELL VAULT CLASS I DIVISION 2 AREA PROVIDE PLASTIC BUSHING AT END OF CONDUIT, TYP. EXISTING WET WELL PROPOSED SEAL-OFF, TYP. NEMA 4X SS INSTRUMENTATION AND CONTROL JUNCTION BOX MOUNTED INSIDE EXTERIOR ENCLOSURE. NEMA 4X SS POWER JUNCTION BOX MOUNTED INSIDE EXTERIOR ENCLOSURE. 1 OUTSIDE AP B KM S Ap r 1 7 , 2 0 2 6 Ap r 1 7 , 2 0 2 6 RE N 11 9 - 2 1 5 OA K R A I - D - E 0 2 . D W G SHOWN E02 14 24 EL E C T R I C A L O N E - L I N E CI T Y O F R E N T O N RA I N I E R S T O R M W A T E R P U M P S T A T I O N U P G R A D E S CI T Y O F R E N T O N RA I N I E R S T O R M W A T E R P U M P S T A T I O N U P G R A D E S DWG NO.: DA T E DE S C R I P T I O N RE V I S I O N S BY RE V I E W EN G I N E E R : SA V E D A T E : RE V I E W E D : PL O T D A T E : CL I E N T : FI L E N A M E : SHEET NO.: JO B N O . : NO . 0"1"2" DRAWING IS FULL SCALE WHEN BAR MEASURES 2" SCALE: 0 01 / 2 3 / 2 6 IS S U E D F O R B I D D I N G CJ B MR J F INSIDE UTILITY METER 1. UTILITY METERING. METER BASE AND ENCLOSURE BY CONTRACTOR PER SERVING UTILITY REQUIREMENTS. METER BY PUGET SOUND ENERGY. 2. FUSING OR CIRCUIT BREAKER PER SURGE PROTECTION DEVICE MANUFACTURER'S RECOMMENDATION. 3. SEE GROUNDING DETAIL, THIS SHEET. 4. GROUND ROD PER N.E.C. (TYPICAL). SEE DWG NO. E11 FOR DETAIL. 5. SEE DWG NO. E12 FOR CONDUIT AND CONDUCTOR SCHEDULE. 6. SEE DWG NO. E12 FOR ELECTRICAL EQUIPMENT SCHEDULE. ELECTRICAL NOTES STATION LOAD CALCULATIONS #4 MIN. BOND TO EQUIPMENT PEDESTAL STRUCTURAL STEEL 15/3 TM PUMP STATION HEATER PUMP 1 PUMP 2 PROPOSED EXTERIOR JUNCTION BOX ENCLOSURE 480/277 VOLT 3 INSTALL SEAL-OFF PER PLAN 15/3 N7 2 04 / 1 7 / 2 6 AD D E N D U M 2 AB M KM S AP B KM S Ap r 1 7 , 2 0 2 6 Ap r 1 7 , 2 0 2 6 RE N 11 9 - 2 1 5 OA K R A I - D - E 0 4 . D W G SHOWN E04 16 24 EL E C T R I C A L P L A N 1 CI T Y O F R E N T O N RA I N I E R S T O R M W A T E R P U M P S T A T I O N U P G R A D E S CI T Y O F R E N T O N RA I N I E R S T O R M W A T E R P U M P S T A T I O N U P G R A D E S DWG NO.: DA T E DE S C R I P T I O N RE V I S I O N S BY RE V I E W EN G I N E E R : SA V E D A T E : RE V I E W E D : PL O T D A T E : CL I E N T : FI L E N A M E : SHEET NO.: JO B N O . : NO . 0"1"2" DRAWING IS FULL SCALE WHEN BAR MEASURES 2" SCALE: 0 01 / 2 3 / 2 6 IS S U E D F O R B I D D I N G CJ B MR J F PUMP STATION INTERIORPUMP STATION EXTERIOR PUMP STATION EXTERIOR PUMP STATION INTERIOR 1. ALL EXISTING CONDUIT IN PUMP STATION INTERIOR TO BE REMOVED. 2. FOLLOWING CONDUIT REMOVAL, CONTRACTOR TO SEAL EXISTING UNUSED CONDUIT BUILDING PENETRATIONS AND MAKE WEATHERTIGHT. ELECTRICAL NOTES EXISTING METER AND MAIN SERVICE DISCONNECT, TO BE REMOVED. EXISTING GENERATOR RECEPTACLE, TO BE REMOVED. EXISTING RADIO ANTENNA AND MAST TO REMAIN IN PLACE. EXISTING COMBINATION LIGHT SWITCH/RECEPTACLE TO BE REMOVED. EXISTING BUILDING INTRUSION SWITCH TO BE REMOVED. PROPOSED EXPLOSION-PROOF INTRUSION SWITCH TO BE INSTALLED IN SAME LOCATION. EXISTING INTRUSION DISABLE SWITCH TO BE REMOVED. PROPOSED EXPLOSION-PROOF INTRUSION DISABLE SWITCH TO BE INSTALLED IN SAME LOCATION. EXISTING ELECTRICAL EQUIPMENT, TO BE REMOVED EXISTING HEATER TO BE REMOVED. PROPOSED EXPLOSION-PROOF HEATER AND DISCONNECT TO BE INSTALLED IN SAME LOCATION. EXISTING LIGHT FIXTURES, TO BE REMOVED, TYP. EXISTING MOTOR STARTERS, TO BE REMOVED EXISTING PUMPS TO BE REMOVED EXISTING SMOKE DETECTOR TO BE REMOVED EXISTING TELEMETRY PANEL, "RTU", TO BE RELOCATED TO PROPOSED ELECTRICAL SHELTER. INSTALL PROPOSED LEVEL TRANSMITTER JUNCTION BOX IN SAME LOCATION AND SPLICE EXISTING LEVEL TRANSMITTER CABLE TO FIELD WIRING AT TERMINAL BLOCKS INSIDE JUNCTION BOX. RECONNECT EXISTING LEVEL TRANSMITTER CABLE TO TERMINAL BLOCKS. EXTEND EXISTING CONDUIT WITH PROPOSED CONDUIT AS NECESSARY. EXISTING POWER DISTRIBUTION PANEL, TO BE REMOVED EXISTING MANUAL TRANSFER SWITCH, TO BE REMOVED EXISTING FLOOD SWITCH TO BE REMOVED EXISTING PRESSURE SWITCHES, TO BE REMOVED. TYP. 2 04 / 1 7 / 2 6 AD D E N D U M 2 AB M KM S AP B KM S Ap r 1 7 , 2 0 2 6 Ap r 1 7 , 2 0 2 6 RE N 11 9 - 2 1 5 OA K R A I - D - E 0 4 . D W G SHOWN E07 19 24 PU M P C O N T R O L P A N E L D E T A I L S 2 CI T Y O F R E N T O N RA I N I E R S T O R M W A T E R P U M P S T A T I O N U P G R A D E S CI T Y O F R E N T O N RA I N I E R S T O R M W A T E R P U M P S T A T I O N U P G R A D E S DWG NO.: DA T E DE S C R I P T I O N RE V I S I O N S BY RE V I E W EN G I N E E R : SA V E D A T E : RE V I E W E D : PL O T D A T E : CL I E N T : FI L E N A M E : SHEET NO.: JO B N O . : NO . 0"1"2" DRAWING IS FULL SCALE WHEN BAR MEASURES 2" SCALE: 0 01 / 2 3 / 2 6 IS S U E D F O R B I D D I N G CJ B MR J F PUMP CONTROL PANEL INTERIOR SWING DOOR LAYOUT PUMP CONTROL PANEL DISCONNECT SWITCH PUMP START COUNT METER, TYP. PUMP 1 HOURS 0 0 0 0 0 0 START 0 0 0 0 0 0 PUMP 2 HOURS 0 0 0 0 0 0 START 0 0 0 0 0 0 VFD FAULT LIGHT, TYP. VFD DISABLE LIGHT, TYP. VFD DISABLE PUSHBUTTON, TYP. PUMP RUN TIME METER, TYP. VFD KEYPAD MODULE, TYP. MOUNT INTRUSION SWITCH TO INSIDE OF ENCLOSURE PUMP RUNNING LIGHT, TYP. PUMP SEAL FAIL LIGHT, TYP. PUMP OVERTEMPERATURE LIGHT, TYP. ALARM RESET PUSHBUTTON, TYP. POWER MONITOR 2 04 / 1 7 / 2 6 AD D E N D U M 2 AB M KM S 1. SEE ELECTRICAL SITE PLAN, DWG NO. E03 FOR CONTINUATION 1. SEE DWG NO. E12 FOR CONDUIT AND CONDUCTOR SCHEDULE. 2. SEE DWG NO. E12 FOR ELECTRICAL EQUIPMENT SCHEDULE. ELECTRICAL NOTES AP B KM S Ap r 1 7 , 2 0 2 6 Ap r 1 7 , 2 0 2 6 RE N 11 9 - 2 1 5 OA K R A I - D - E 0 5 . D W G SHOWN E09 21 24 EL E C T R I C A L E Q U I P M E N T P E D E S T A L DE T A I L S CI T Y O F R E N T O N RA I N I E R S T O R M W A T E R P U M P S T A T I O N U P G R A D E S CI T Y O F R E N T O N RA I N I E R S T O R M W A T E R P U M P S T A T I O N U P G R A D E S DWG NO.: DA T E DE S C R I P T I O N RE V I S I O N S BY RE V I E W EN G I N E E R : SA V E D A T E : RE V I E W E D : PL O T D A T E : CL I E N T : FI L E N A M E : SHEET NO.: JO B N O . : NO . 0"1"2" DRAWING IS FULL SCALE WHEN BAR MEASURES 2" SCALE: 0 01 / 2 3 / 2 6 IS S U E D F O R B I D D I N G CJ B MR J F 5'-0" 1'-1" CLCL CL 7'-9" POST CONNECTION ELECTRICAL EQUIPMENT PEDESTAL PLAN VIEW UNISTRUT FRAMING. SPACING AS NEEDED FOR PANEL ATTACHMENTS HSS 4 1/2" x 4 1/2" x 5/16" POSTS, TYP. OF 2, HOT DIP GALVANIZE POST AND RAFTER PL 9" X 9" X 1/2" HSS 4.5X4.5X5/16 HILTI HIT-RE 500 V3 + HAS-V-36 1/2" W/ MIN 4" EMBEDMENT, OR APPROVED EQUAL BASE PLATE DETAIL 1601 UTILITY METER MAIN SERVICE DISCONNECT AUTOMATIC TRANSFER SWITCH, "ATS" PUMP CONTROL PANEL, "PCP" TELEMETRY PANEL, "RTU". INSTALL EXISTING TELEMETRY PANEL IN PROPOSED NEMA 4X SS 48" W, 72" H, 24" D ENCLOSURE. ELECTRICAL EQUIPMENT PEDESTAL FRONT ELEVATION VIEW 5'-0" UTILITY METER MAIN SERVICE DISCONNECT SWITCHAUTOMATIC TRANSFER SWITCH, "ATS"PUMP CONTROL PANEL, "PCP" (CONTAINS LIGHTING PANEL, "L") TELEMETRY PANEL, "RTU" P6P13 C4 J5 P4 P5 P3 P2P11 P1 C5 C3 C7 C8 C6 J6J4J2 J1 1601 WALL C1 P12C12 C2 P7 P8 C14 C13 "RTU" FRONT EDGE OF CONCRETE SLAB INSTALL INTRINSICALLY SAFE JUNCTION BOX INSIDE OUTER TELEMETRY PANEL ENCLOSURE CONTAINING INTRINSICALLY SAFE BARRIERS FOR THE FOLLOWING DEVICES: LEVEL TRANSMITTER, INTRUSION DISABLE KEY SWITCH, "ICJB" INTRUSION SWITCH, AND (3) WET WELL FLOATS. SOURCE 24VDC POWER FOR BARRIERS FROM SPARE CIRCUIT BREAKER IN "RTU". 2 04 / 1 7 / 2 6 AD D E N D U M 2 AB M KM S 04 / 1 7 / 2 6 AD D E N D U M 2 AB M KM S 2 AP B KM S Ap r 1 7 , 2 0 2 6 Ap r 1 7 , 2 0 2 6 RE N 11 9 - 2 1 5 OA K R A I - D - E 0 7 . D W G SHOWN E12 24 24 EL E C T R I C A L S C H E D U L E S CI T Y O F R E N T O N RA I N I E R S T O R M W A T E R P U M P S T A T I O N U P G R A D E S CI T Y O F R E N T O N RA I N I E R S T O R M W A T E R P U M P S T A T I O N U P G R A D E S DWG NO.: DA T E DE S C R I P T I O N RE V I S I O N S BY RE V I E W EN G I N E E R : SA V E D A T E : RE V I E W E D : PL O T D A T E : CL I E N T : FI L E N A M E : SHEET NO.: JO B N O . : NO . 0"1"2" DRAWING IS FULL SCALE WHEN BAR MEASURES 2" SCALE: 0 01 / 2 3 / 2 6 IS S U E D F O R B I D D I N G CJ B MR J F ɸ ɸ ELECTRICAL EQUIPMENT AND INSTRUMENTATION SCHEDULE HEATER SCHEDULE LIGHTING FIXTURE SCHEDULE PANEL SCHEDULE L ɸ INSTRUMENTATION CONDUIT AND CONDUCTOR SCHEDULE CONTROL CONDUIT AND CONDUCTOR SCHEDULE POWER CONDUIT AND CONDUCTOR SCHEDULE 2 04 / 1 7 / 2 6 AD D E N D U M 2 AB M KM S