Major Franchise Permit: MFP26001535
IVR Number: 26001535
Permit Information
Permit Name: Puget Sound Energy - Electric
101183997Address/Location:03/27/2026Application Date:3340404265Parcel Number: 519 SW 12TH ST
Permit Type:05/14/2026Issue Date:Franchise
Permit Work Class:05/14/2027Expiration Date:Major Utility
Job Number: 101183997Franchise Type:Electric
Description: Puget Sound Energy Electric Crew to install new 65 ft pole with UG termination for new 3 phase line extension for
Subaru Dealership. Pole work in ROW at intersection of SW 13th St & Seneca Ave SW. UG work on Private Property.
Tree trimming required. All restoration to be completed to city standards.
Contacts
Name Address PhoneTypeBilling
Permits Central 355 110th Ave NE
Bellevue, WA 98004
B: (425) 620-6742
H: (425) 620-6742
C: (425) 620-6742
Applicant
Katie Zimmerman
Puget Sound Energy
1660 Park Lane
Burlington, WA 98233
B: (425) 620-6742
C: (425) 620-6742
ApplicantX
Vicki Henson
Potelco Inc
8001 212th St S
Kent, WA 98032
B: (253) 863-0484Contractor
Business License Number: 5109Electrical Contractor: POTELI*344O4
Construction Contractor: POTELI*227PL
Puget Sound Energy Inc 10885 NE 4th Street, PSE08-N08
Bellevue, WA 98009
B: (888) 225-5773Emergency
Contact
CITY OF RENTON ROW 1055 S Grady Way
Renton, WA 98057-3232
Owner
Katie Zimmerman
Puget Sound Energy
1660 Park Lane
Burlington, WA 98233
B: (425) 620-6742
C: (425) 620-6742
Specialized
Billing
General Conditions & Signature
Permission is hereby given for the work described on this permit according to the conditions hereon and according to the
approved plans and specifications pertaining thereto, subject to compliance with the Ordinance of the City of Renton.
Ÿ
This permit and plans must be posted at the job site at all times.Ÿ
I hereby certify that no work is to be done except as described above and in approved plans, and that work is to conform to
Renton codes and ordinances. Renton Trench Restoration and Street Overlay Requirements.
Ÿ
Call 425.430.7203 or go to: https://permitting.rentonwa.gov one working day in advance to schedule an inspections and for
ANY work in the Right of Way.
Ÿ
Call 8 1 1 to locate underground utilities at least two full business days prior to any excavation.Ÿ
In accordance with RCW 19.122.033(4) the permit holder is required to contact (Williams Northwest Pipeline at 425.868.1010)
(Olympic Pipeline at 425.235.7736) (Puget Sound Energy at 425.375.3397) to request a consultation with the transmission
pipeline company prior to performing any construction or excavation activities. This requirement to consult with the
transmission pipeline company is in addition to the requirement to Call before You Dig as required in RCW 19.122.
Ÿ
(Date)(Signature)
Page 1 of 1THIS PERMIT AND PLANS MUST BE POSTED AT THE JOB SITE AT ALL TIMES
Note: The Applicant is responsible for compliance with all codes and regulations, whether or not described in this document.
PUBLIC WORKS DEPARTMENT
Page 1 of 6 | Published: 2/25/2025
Transportation Systems Division | 1055 South Grady Way, 5th Floor | Renton, WA 98057 | 425-430-7380
Website: rentonwa.gov
TRAFFIC CONTROL PLAN APPLICATION
Published: 2/25/2025
TRAFFIC CONTROL PLAN (TCP) MUST BE SUBMITTED TO PUBLIC WORKS TRANSPORTATION DIVISION
FOR REVIEW/APPROVAL AT LEAST FIVE (5) WORKING DAYS BEFORE THE DATE OF WORK AND FOR TRAFFIC SIGNAL
WORK WITHIN 150 FEET OF THE INTERSECTION AT LEAST FIFTEEN (15) WORKING DAYS BEFORE THE DATE OF WORK.
FOR PURPOSES OF THIS APPLICATION, WORKING DAYS ARE DEFINED AS MONDAY THRU FRIDAY, AND EXCLUDING
CITY HOLIDAYS.
The City of Renton requires any contractor, firm, corporation, or other public/private agency to prepare a Traffic
Control Plan (TCP) and obtain City's approval of that plan when construction, repair, or maintenance work is to be
conducted within the City's right-of-way.
1.Fill out the Traffic Control Plan (TCP) Application form and prepare required submittal documents.
2.All TCPs must conform to all attached requirements. Failure to do so may be subject to resubmittal.
3.Submit Application via email to TCP@rentonwa.gov with the subject line “TCP Application – [Project Name].”
4.Resubmittal may be required for TCPs that are incomplete and do not display proper requirements as
described in the guidelines. Additional review time may be needed.
By signing, I certify that the information on this application and within the submittal documents are accurate to the
best of my knowledge and I acknowledge and have read all the requirements and guidelines on this application.
Applicant’s Signature Date
Applicant’s Name (Print)
Project Name: Permit #:
Site Address:
Work Date: From _____________ To _____________ Work Time: Start ______________ End ______________
Construction Company:
Contact Name: Phone/Cell: _________________________
Business Address: City/State: Zip: ___________
Description of Work:
24 Hour Emergency
Contact Name & Phone:
Approval By: ______________________________________________ Date:____________________
PW/Transportation or CED/Development Engineering Division
Potelco, Inc
6905 S 228th St Kent, WA 98466
Please See Attached
Katie Zimmerman
3/27/2026
101183997
519 SW 12TH ST
Jordan Velasco (360) 296-3127
MFP26001535
Scott Warlick CED 5/14/2026
Monday Friday 8:00am 3:00pm
Page 2 of 6 | Published: 2/25/2025
This Page Intentionally Left Blank
Page 3 of 6 | Published: 2/25/2025
APPLICANT AGREES TO ALL THE FOLLOWING REQUIREMENTS:
GENERAL
•Applicant is responsible for compliance with all traffic regulations of the City of Renton (City) and the State
of Washington, including codes and regulations not described in this application.
•Work Zone Traffic Control shall be in accordance with Manual on Uniform Traffic Control Devices (MUTCD)
and shown by a traffic control plan layout or reference to Washington State Department of Transportation
(WSDOT) traffic control plans.
•Any lane or street closures not in conformance with the approved Traffic Control Plan (TCP) and/or without
notification of emergency services may result in receiving a citation for violation of R.C.W. 47.36.200 Signs
or Flaggers at thoroughfare work sites and R.C.W. 9A.36.050 Reckless Endangerment, and other applicable
State and City codes.
•Indemnify and hold harmless the City from any and all claims, actions, and judgments, including all costs of
defense and attorney’s fees incurred in defending against same, arising from and related to
implementation of the approved TCPs including claims arising from towing of private vehicles and the acts
of Applicant’s agents and employees.
•Applicant must comply with all conditions of the application.
•The City shall be entitled, in its reasonable discretion, to settle claims prior to suit or judgment, and in such
event shall indemnify and hold harmless the City for any such claims paid, including the City’s reasonable
attorney’s fees and litigation costs incurred resulting from such claim.
•In the event any claim or suit is brought against City within the scope of this application, Applicant is
responsible to pay for legal counsel chosen by the City to defend against same.
•No more than one TCP shall be in use at any given time for a single project. If multiple TCPs are submitted
for review and approval at the same time, the TCPs shall be clearly labeled as separate plans and include
construction phasing and sequencing.
•Previously approved TCPs cannot be combined into a new TCP without review and approval by the City.
•Expired TCP is not valid and shall not be used. Applicant shall resubmit the expired TCP for approval with
the updated date and time and/or any changes to TCP.
•Applicant must have the approved TCP prior to commencing the work.
•Approved TCP must be at the work site during work hours.
•Signage shall be used to warn motorcyclists/bicyclists of the potential hazards on any uneven surfaced or
slippery road conditions during work and non-work hours.
•Any vehicle, equipment, barricade, or portable tow-away sign used within the work area must display a
company logo or any legally acceptable sign showing the company name, address, and telephone number
at a conspicuous place on the vehicle or equipment.
•At signalized intersections, vehicle detection shall always remain operational, unless approved in this TCP
and notified Transportation Signal Maintenance prior to commencing work. If damage occurs to existing
vehicle detection that is to remain, it is Applicant’s responsibility to replace with video vehicle detection
equipment that meets current City’s standards at Applicant’s expense.
•When not in use, temporary traffic control devices shall be removed or covered immediately. It is the
Applicant’s responsible to cover any temporary traffic control devices when not applicable for the
construction activities. Similarly, when work is suspended for short periods of time, traffic control devices
that are no longer necessary shall be removed or covered. If deemed abandoned, City crews will remove
and may store them at the City’s maintenance shop (3555 NE 2nd Street) for up to sixty (60) days. The City
is not responsible for any private property from City assets and identifying the property owner.
•Applicant is responsible to maintain existing pedestrian accessible routes during work and non-work hours.
At intersections, the work on pedestrian facilities shall be limited to one (1) corner at a time, with the least
possible inconvenience or delay to pedestrians. Pedestrian pushbuttons shall remain accessible at all times,
unless approved pedestrian accessible detour(s) are provided. Accessibility to existing or temporary
Page 4 of 6 | Published: 2/25/2025
pedestrian pushbuttons shall not be impaired. Deficiencies caused by Applicant’s operations shall be
repaired at Applicant’s expense.
•Applicant shall provide complete assistance and accommodation from a dedicated pedestrian escort to all
kinds of pedestrian traffic when sidewalk or walkway is impeded to safely redirect pedestrians around a
work zone.
•Driveway and alley access shall be maintained at all times, also see RMC Chapters 9 and 10 for Street
Closure and Street Excavation for details. Applicant is responsible for coordinating with the property
owners and/or residents prior to commencement of the work.
•Pavement excavation shall be limited to a maximum of one travel lane at a time unless otherwise
approved.
•Accessibility for emergency vehicles shall be maintained at all times.
PUBLIC OUTREACH
•Applicant must notify Transportation Signal Maintenance (425-430-7423) and City inspector (425-430-
7203) at least twenty-four (24) hours before commencing work (lane shift/closure or near a signal)
affecting the vehicle detection.
•Applicant shall notify emergency services (253-852-2121) twenty-four (24) hours before any street closures
or lane closures.
•Applicant shall call Renton School District (425-204-4455) or any public/private agency, including public
transit, to be affected by a temporary lane or road closure a minimum of five (5) working days (excluding
weekends and holidays) prior to starting any work.
•Applicant shall coordinate with King County Metro Transit Construction Information Center (206-477-1140
or construction.coord@kingcounty.gov) for any construction or installation activities affecting transit
operations or facilities. Notification information and guidelines can be found at:
https://kingcounty.gov/en/dept/metro/about/contractor-resources/transit-system-impacts.
WORKING DAYS AND TIMES
•Normal working days are Monday through Friday. Work on holidays, weekends or at night shall not occur
without City’s approval. For work times between 10:00 p.m. and 7:00 a.m., see Night Work section below
for details.
•Work time begins when any street or travel lane is fully or partially closed. This includes set up and removal
within the traveled way.
•If the City determines the closure hours adversely affect traffic during the work, the City may require to
adjust or reduce the working hours accordingly. Reduced work hours may be required by the City to
minimize traffic impacts for any work located near a school during pick-up and drop-off times or on an
arterial street. (See WSDOT Functional Classification Map:
https://www.wsdot.wa.gov/data/tools/geoportal/?config=FunctionalClass)
•Applicant may request the City for consideration of extended or modified working hours. Such request
must be approved by the City before changing hours of work.
CLOSURES
•All closure hours and days are subject to local permit and ordinance conditions (such as noise ordinances).
More information can be found on https://www.rentonwa.gov/City-Services/Permit-Center. Total street
closure lasting more than twenty-four (24) hours is subject to City Council authorization per Section 9-9 of
the Renton Municipal Code (RMC).
•Road closure notice – Applicant must install Portable Changeable Message Sign (PCMS) boards no less than
five (5) working days in advance of effective date and time, not including holidays, at location(s) as
identified in the TCP. Other methods of displaying the messages shall be approved by the City.
Page 5 of 6 | Published: 2/25/2025
•Road closure notice messages must include at least the following:
ROAD WILL BE CLOSED
MONTH/DAY – MONTH/DAY
_AM - _PM
•Road and/or sidewalk closure must be evaluated by the City with respect to both the necessity as well as
the impact of the closure to the public. Applicant shall submit detour plans for road closures to
accommodate both motorized and non-motorized users, including accessible pedestrian route(s). Road
closures shall require additional temporary traffic control including advance notification, approach and
detour signage.
•Applicant is responsible to temporarily remove the flags and install bags over the flag holders for any work
requiring the temporary closure of a crosswalk equipped with pedestrian flags. Applicant shall ensure the
bags remain intact and shall replace damaged bags as needed or determined necessary by the City of
Renton inspector. For any misplaced or lost flags, Applicant is responsible to replace at Applicant’s own
expense. Upon restoration of the crosswalk, Applicant shall remove the bags and return all flags to the
holders. Inventory of pedestrian flags must be submitted to the City inspector and reported to City of
Renton Transportation Signal Maintenance (425-430-7423) prior to removal.
UNIFORMED POLICE OFFICERS (UPO) / FLAGGERS
•Any construction activities within one hundred and fifty (150) feet of a signalized intersection shall require
Uniformed Police Officer(s) (UPO) at the traffic signal, unless otherwise approved in this TCP and evaluated
by City Transportation for the impacts of traffic signal operations and safety.
•Flagger and sign placement are subject to revision by the City Inspector on site, if needed to address traffic
or pedestrian safety or travel.
•For TCPs that require the presence of UPO to manage vehicular traffic and pedestrians at signalized
intersections, Applicant shall coordinate with Transportation Signal Maintenance (425-430-7423) at least
twenty-four (24) hours in advance for any signal that will be placed in red flashing mode. Applicant shall
notify Transportation Signal Maintenance when the intersection is back to the normal traffic signal
operations.
TEMPORARY TRAFFIC SIGNALS OR TRAFFIC SIGNAL MODIFICATION
•Temporary traffic signal programming or modification requires a minimum fifteen (15) working days for
each traffic signal controller to be programmed and tested by City Transportation staff before starting the
work. The Start Date on this TCP shall reflect the time for temporary traffic signal programming or
modification.
TEMPORARY NO-PARKING
•Applicant must post notice of date(s) and time(s) of Temporary No Parking Zone with signs at every
hundred (100) feet at least seventy-two (72) hours in advance of effective date and time.
•Applicant is responsible to show on the TCP the limits of Temporary No Parking Zone, identifying barricade
locations for vacate parking or curb lane usage. The cover sheet of this approved TCP form must be
attached to each Temporary No Parking Sign on the project site.
•Two travel lanes (one for each approach) must be open at all times on arterial streets unless approved in
this TCP.
NIGHT WORK
•Between the hours of 10 p.m. and 7 a.m., approved Noise Variance shall be required (See Section RMC 8-7-
8)for night work. Process may take up to twelve (12) weeks. More information can be found at
https://www.rentonwa.gov/City-Services/Permit-Center/Land-Use-Development/Noise-Variance.
•City may require night work for TCPs that have severe traffic impacts on arterial streets.
Page 6 of 6 | Published: 2/25/2025
•Night work shall always be required if two lanes of traffic (One for each approach) cannot be maintained
on an arterial street.
•Night work shall be required if an evaluation of existing traffic volumes and patterns finds that any TCP will
functionally reduce an arterial or high-volume collector street to only one lane of traffic.
•The following configurations may require night work:
Work at traffic signals that requires shifting one direction of traffic into a left turn pocket where a high
volume of left turns occur.
Work at traffic signals that requires shifting two directions of traffic into left turn pockets.
Work at traffic signals that requires shifting high-volume left-turn movement into a through lane on a
single approach to the intersection.
Work at signals that requires shifting left-turning traffic into a through lane on multiple approaches to
the intersection.
•If City’s initial TCP review finds that night work is required, a pre-construction meeting is mandatory to
confirm the extents of the work required, the duration of work, anticipated noise levels, and any potential
alternatives to mitigate the impact of night work to adjacent residents prior to review and approval of the
TCP.
TRAFFIC CONTROL PLAN (TCP) FORMAT
•TCP must be site and project specific. The TCP shall clearly indicate all existing transportation facilities
impacted by work including roads, bike lanes, sidewalks, transit stops, and driveways. Typical drawings,
taper tables and MUTCD illustrations, by themselves, are insufficient.
•Each construction phase shall be provided with appropriate work zone traffic control. The impacts of utility
relocation, traffic delays, detours and capacity restrictions must be considered and addressed. A suitable
sequence of construction activities must be discussed with City Staff prior to fully developing TCPs based on
the complexity of a project.
•TCPs shall be clearly labeled as separate plans to identify the construction sequencing during each phase
when more than one TCP layout is submitted.
•TCP must be submitted with an electronic copy of TCP layout(s), on 11” X 17” paper size PDF format, which
consist of:
Map(s) showing the location of the project and work area.
All fonts shall be legible and a minimum 10-point font size.
All symbols of viewing or printing shall be clear and contrasting.
All streets shall be labeled, and layout must include a north arrow and scale.
Must show channelizing devices, signing, flagger locations, barricades, PCMS boards, etc.
Show locations where the standard traffic control plans are applied.
519 SW 12th St
Renton
WA 98057
USA
1
1
1
1
13 13
PV2
STOP
STOP
FR
O
M
TO
TO
W
A
W
A
Y
A
R
E
A
PH
O
N
E
8
8
8
-
9
9
9
9
INF
R
A
S
O
U
R
C
E
L
L
C
0
0
0
0
0
0
0
0
0
0
NO
P
A
R
K
I
N
G
NO-PARK
FR
O
M
TO
TO
W
A
W
A
Y
A
R
E
A
PH
O
N
E
8
8
8
-
9
9
9
9
INF
R
A
S
O
U
R
C
E
L
L
C
0
0
0
0
0
0
0
0
0
0
NO
P
A
R
K
I
N
G
NO-PARK
FROMTO
TOW AWAY AREA
PHONE 888-9999
INFRASOURCE LLC 000 0000000
NO PARKING
NO-PARK
FROM TO
TOW AWAY AREA
PHONE 888-9999
INFRASOURCE LLC 000 0000000
NO PARKING
NO-PARK
SE
N
E
C
A
A
V
E
S
W
SW 13TH ST
SW 12TH S
T
W2
0
-
1
ROAD
WORK
AHEAD
W2
0
-
4
ONE LANE
ROADAHEAD X'
≥
X'
≥
X'≥
W2
0
-
7
A
W20-1
RO
A
D
W
O
R
K
AH
E
A
D
W20-4
ON
E
L
A
N
E
RO
A
D
AH
E
A
D
X'≥X'≥X'≥
W20-7A
17
17
10
1
0
W20-1
RO
A
D
WO
R
K
AH
E
A
D
X'≥
W20-1
RO
A
D
WO
R
K
AH
E
A
D
X'≥
W20-7A
STOP
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
jaber Tofan
425-424-7701
Jaber.tofan@pse.com
1 OF 1519 SW 12TH ST ,Renton ,98057
0
515507484
03/27/2026
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated,
if indicated use ADA compliant channelization.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. All signs shall be sized as outlined in sections 6G and 6H
of the MUTCD unless otherwise specified.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place during approved work hours as
per jurisdictional requirements. (Generally between 9
a.m. and 4 p.m. on non-arterials and from 9 a.m. to 3
p.m. on arterials. If night time work is approved,
signaling and flaggers shall conform to WAC
296-155-305. Night time work to take place between
_____________and ______________.)
8. All Flagger and Downstream tapers shall be 50'-100'.
LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
WORK AREA
CHEVRONARROW BOARD
FLAGGER
UNIFORMED
POLICE OFFICERPOLICE
STOP
POLE
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
TEMPORARY TRAFFIC CONTROL PLAN
Puget Sound EnergyTraffic Control Supervisor:Jaber Tofan
Card No. ES2 000434
Card Exp. 02/18/2028
Jaber.Tofan@pse.com
(425)424-7701
MFP26001535
EAR
13
N
Vicinity Map
47.4681, -122.2238
10
1
1
8
3
9
9
7
FOREMAN (CHECK BOX WHEN COMPLETED)
PSE Equipment LOCKED/SECURED & Work Area left in CLEAN/SAFE Condition.
Grid, Cable, and Switch numbers INSTALLED & VERIFIED.
Field Changes RED-LINED on As-built.
Indicate correct FUSE SIZE on As-built & VERIFY proper PHASE.
Foreman's Signature _______________________________________________
Print Name ___________________________________ Date ______________
Material VERIFIED and CHANGES noted on Paperwork.
Total PRIMARY Cable noted on As-built.
Company ID#'s RECORDED in correct location on As-built.
Deviations noted on the As-built and their reason.
I certify that the work performed meets PSE's standards and procedures
and that all quality requirements are met.
No
No
No
Yes
Yes
Yes
"Flagging Required"
"Outages Required"
"Locates Required"
WALKER'S RENTON SUBARU
OH-UG FEEDER DISTRIBUTION
CONVERSION
101183997
Owner / Developer Contact Info
officeATTN:
Walker Renton Subaru
519 SW 12th St
Renton, WA 98057
Gar Hansen 253-380-3801PHONE
CABLE TV
515507484 101183997
N/A
583083738N/A
108162437
PROJECT PHASE
PWR
NOTIF#ORDER#
Superior
OH Wire & Pole RM
OH XFMR
E-Mail:
Cell Phone:
Project Manager Contact Information:
Manager:JORDAN VELASCO
(360) 296-3127
JORDAN.VELASCO@PSE.COM
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
J. VELASCO (360) 296-3127 3/23/26
J. VELASCO (360) 296-3127 3/23/26
N/A N/A N/A
T. MYER .3/23/26
RW-141033 RENTON
WALKER'S RENTON SUBARU
OH-UG FEEDER DISTRIBUTION CONVERSION
519 SW 12TH ST, RENTON, WA 98057
N/A N/A
N/A 101183997
AS NOTED 1 / 12
KING N/A N/A CSPSKEPM
NW 19-23N-05E N/A N/A
2305E074 2305E076 2305E074SW EAR-13
COMCAST
TODD ZIMNY
360-507-0598
ZIPLY
WA.structure.Access@ziply.com
888-688-0013
.
.
.
N/A
N/A
N/A
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL 811 TWO BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
LEGEND
CONDUIT RISER
OVERHEAD TRANSFORMER
JUNCTION VAULT/JUNCTION BOX
NEW CONDUCTOR AND OR TRENCH LINE
DISCONNECT - FUSED
PULL VAULT OR SPLICE VAULT
EXISTING POLE
DOWN GUY
DISCONNECT - UNFUSED
NEW POLE
PADMOUNT TRANSFORMER
SECONDARY HANDHOLE
EXISTING CONDUCTOR TO BE REMOVED
OR ABANDONED
STREET LIGHT
TOTAL UNDERGROUND TRANSFORMER
ENERGY CUSTOMER DEMAND POINT
OR
OR
OR
OVERHEAD JUMPER CONNECTION
JOB
SITE
PSE GENERAL SPECIFICATIONS
Scope of Work
OH-UG FEEDER DISTRIBUTION CONVERSION
- REMOVE 425' OF OH WIRE & CONVERT TO UG FEEDER
General
-All work is to be completed per PSE Standards & Practices. Copies of all PSE Standards
are available upon request.
-Work sites shall be kept clear of debris and all construction materials; equipment and
packing shall be removed daily.
-Return all unused and removed poles, transformers and hardware to PSE, storeroom. All
copper shall be coiled and returned the day it is removed from the poles. Remove all
unused pins and insulators.
-Return all streetlights, area lights and floodlights to Sumner yard.
Pre-Construction
-Notify appropriate city, County or DOT authorities 48 to 72 hours, or as required by
permitting agency, in advance of starting work in Right-of-way involving a Permit.
-All system switching shall be approved by System Operations (425-882-4652) a minimum
of 48 hours in advance.
-Notify customers of all outages 48 hours in advance.
Work Drawings & Documents
-PSE Project Manager or Engineer shall approve field design changes.
-Mark all field changes, equipment ID numbers and Underground cable information in red on
Foreman's copy of work sketch.
-Return one Foreman's copy of work sketch to Project Manger at completion of job.
-When permits are required, a copy of the permits shall be available on work site at all times.
Safety
- efer to PSE standards 6275.3000 for requirements on System Grounding
-Refer to PSE standards 6275.9210, 6275.9230 and 6275.9250 for personal protective
grounding requirements.
-Refer to PSE standards 6275.9150 for vehicle grounding and barricading requirements.
-Proper line clearances shall be taken at the beginning, and released at the end, of each
workday, or as otherwise instructed by the System Operator.
-Provide signs, barricades, and traffic control in conformance with permit regulations.
-Utilize flagging and other vehicle traffic control as necessary and in conformance with local
traffic regulations.
-Maintain traffic flow as required by permitting agency.
Joint Facilities
-Coordinate with Communication Companies for transfers.
OVERHEAD CONSTRUCTION
Poles & Structures
-Poles are to be installed or relocated as staked. Unless otherwise noted, all pole location
measurements are from the center of the pole.
-All new poles set shall be the class indicated on the sketch, or better. Do not set a lower
class pole than specified.
-Install ground plate assembly on all new poles. Install Switch Ground Assembly per
standard specification 6014.1000 at new gang operated switch locations.
-Install grid numbers on all new and existing poles as shown on sketch.
-Straighten existing poles as indicated or as necessary.
-Treat all field-drilled poles with copper napthenate wood preservative.
-Remove old poles after communication companies have transferred off and return to PSE
storeroom. Fill and crown pole holes and restore the area similar to adjacent landscaping.
Conductors & Equipment
-Transfer all overhead and underground primary, secondary and service conductors and
guys to new poles set, unless otherwise indicated on this sketch.
-Transfer existing transformers to new poles unless otherwise indicated on this sketch.
-Use stirrups to connect all overhead and underground primary taps, and all transformers.
Install at all sites being worked within the scope of the project where they are currently
missing.
- For 12vK construction, install avian protection with #4 CU-covered jumpers (MID#9998076)
and #4 SD Aluminum covered tie-wire (MID#8309760). For 34vK construction use bare
wire primary jumpers with pre-formed helical-grip ties and avian protection devices when
required per Std. 6015.2000. Jumpers for poles that are double dead ended with tree wire
can be either the same size tree wire conductor or covered CU.
-Apply grit inhibitor on all Ampact, stirrup, and dead-end connections.
-Connect primary taps and transformers to same phase as existing unless otherwise shown
on the drawing.
-All neutral connections to be made with solid compression connectors. Connect all pole
grounds to common neutral.
-Use Load-interrupter cutouts (with arc shields) on all primary overheads and underground
taps with fused protection above 40T.
-Install Wildlife Protectors on all transformers.
-If four or more six inch conduits are installed in a trench, fluidized thermal backfill (FTB)
shall be installed around the conduits to a depth of six inches above and to the sides of the
conduit, and two inches underneath, per PSE Standard 6790.0140.
Materials
-The City will provide a schedule of when vault excavation will be ready. All vaults will be
delivered by the manufacture to the job site as follows:
--575 and smaller with a minimum 3 days advanced notice to PSE storeroom.
--5106 and larger with a minimum 5 days advanced notice to PSE storeroom.
-If vault excavation is not ready when vaults are delivered, city will provide necessary
equipment to install vaults.
UNDERGROUND CONSTRUCTION
Vault Installation
-Vaults shall be installed in accordance with PSE standards 6775.0035 and 6775.0040.
-All PSE vaults shall be clean and clear of construction debris with all knockouts and cover
adjustments grouted to PSE satisfaction prior to PSE accepting delivery of bare conduit &
vault system.
Conduit Installation
-All PSE conduit installations shall conform to PSE standards 6800.6000, 6800.6050,
6800.8050, and 6825.6505.
-All conduits shall be routed and installed per conduit tables, installation diagrams, and
details in this work sketch.
-A plug shall be installed in all spare conduits.
-All conduits entering PSE vaults shall be through the appropriate knockouts to ensure
proper cable lay. Vault entries shall not cause cables to cross each other in the vault, or lay
in the vault unevenly.
-All conduits entries into PSE vault shall be straight and level with a minimum of 6' straight
section outside the vault wall and 2” on conduit extending into the vault with bell ends
installed.
-PSE conduits shall be placed in the trench maintaining a minimum of 1-1/2” of separation.
Use conduit spacers (provided by PSE) every10'.
-PSE conduit runs shall be placed straight and level. If it becomes necessary to alter
conduit alignments, in order to avoid other utilities, the maximum bend radius allowed is
22-1/2 degrees. Bend radius greater than 22-1/2 degrees require prior approval from PSE
engineering representatives.
-All PSE conduits shall be placed with the minimum separation between other utility facilities
as specified in PSE standard 6790.0130. Refer to the typical utility trench cross section
detail in this work sketch.
-All PSE conduits shall have a minimum of 36” of cover. Cover of less than 36” is
permissible on a case by case basis provided that such installations adhere to PSE
standard 6790.0130 figure 2. Pre-approved by PSE engineering representatives is
required.
Cable Tags and Pulling
-Primary Underground Cable Identification Tag installation shall conform to PSE standards
6825.6050.
-Cable Pulling shall conform to PSE standards 6825.6100 and 6825.6150
RESPONSIBILITIES OF THE CITY
Documentation
-The city and their contractor shall attend a pre-construction meeting specifically for
installation of bare duct and vault system.
-Field changes shall be pre-approved by PSE or designated representative prior to
construction with proof of acceptance required prior to PSE acceptance of completed duct
and vault system.
Safety
-The city contractor shall not access energized power vaults without the assistance of PSE
line workers.
-The city contractor shall not expose energized power conductors (direct buried or in
conduit) without the assistance of PSE line workers.
Trench and Excavation
-The city shall provide all trench excavation and backfill for the installation of new or
modified PSE underground distribution system within the construction area.
-All trench excavation shall conform to PSE standards 6790.0075, 6790.0130, 6790.0140,
6790.0250, and 6790.3050.
-PSE plans show general trench alignment. They do not show specific cross sections with
existing or proposed other utilities. It is the City's responsibility to install PSE facilities at
necessary depths to avoid and provide required clearances to other existing or proposed
utilities.
-Construct the shared utility trench where the various utilities can transition in and out of the
trench line in an orderly fashion without altering duct bank alignments of other utility.
Separation of crossing utilities sharing the common utility trench is 6”.
-Placement of other utility vaults within the trench line alignment encumbering access to
PSE facilities is not allowed.
- After the new underground system is installed and energized, additional excavation may be
necessary to re-train existing underground cables into the new vaults. This excavation will
be provided by the city with 48 hours notice.
-City shall provide all surveying necessary to assure all PSE vaults are installed in the
alignment location specified in this document. The city shall be responsible for establishing
grade elevation for PSE vaults. Adjustment of vault lids to final grade will be the
responsibility of the City.
-Vault hole excavation shall be prepared level and free of debris with a minimum 6” base of
crushed rock to prevent vault settling.
-PSE Vaults in planter areas shall be set 2” above final grade.
-PSE Conductors and equipment are energized.
-PSE line Note: The city contractor will not be allowed to make vault adjustments after PSE
conductors and equipment are energized. PSE line crew will perform the adjustments on a
change order basis.
N/AUG XFMR
N/AOH Maintenance
N/AUG Maintenance
584052681
593270756
594171047
OVERHEAD CIRCUIT MAP
SCALE: NONE
SITE
JOB
N. SZEMER 3/23/26
FABIAN GOMEZ 3/26/26
MFP26001535
This permit is for Major construction work in the ROW and will be billed at an additional
$158/HR for inspections. After hours and weekend work will be billed at $175/HR
RESTORATION PER CITY OF RENTON STANDARDS
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
J. VELASCO (360) 296-3127 3/23/26
J. VELASCO (360) 296-3127 3/23/26
N/A N/A N/A
T. MYER .3/23/26
RW-141033 RENTON
WALKER'S RENTON SUBARU
OH-UG FEEDER DISTRIBUTION CONVERSION
519 SW 12TH ST, RENTON, WA 98057
N/A N/A
N/A 101183997
AS NOTED 2 / 12
KING N/A N/A CSPSKEPM
NW 19-23N-05E N/A N/A
2305E074 2305E076 2305E074SW EAR-13
COMCAST
TODD ZIMNY
360-507-0598
ZIPLY
WA.structure.Access@ziply.com
888-688-0013
.
.
.
N/A
N/A
N/A
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL 811 TWO BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
10
1
1
8
3
9
9
7
OVERHEAD CIRCUIT MAP (########) BEFORE
SCALE: NTS
OVERHEAD CIRCUIT MAP (########) AFTER
SCALE: NTS
SITE
JOB
SITE
JOB
P07
X97494
X97495U97497
SITE
JOB
SITE
JOB
P06
X97496
(100T)
SW1
MFP26001535
EAR
13
SITE
JOB
EAR
13
SITE
JOB
U97497
AØEJS472
BØEJS473
CØEJS474
AØEJS475
BØEJS476
CØEJS477
AØEJS496
BØEJS497
CØEJS498
AØEJS515
BØEJS516
CØEJS517
AØEJS493
BØEJS494
CØEJS495
AØEJS478
BØEJS479
CØEJS480
AØEJS475
BØEJS476
CØEJS477
AØEJS490
BØEJS491
CØEJS492
AØEJS464
CØEJS508
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
J. VELASCO (360) 296-3127 3/23/26
J. VELASCO (360) 296-3127 3/23/26
N/A N/A N/A
T. MYER .3/23/26
RW-141033 RENTON
WALKER'S RENTON SUBARU
OH-UG FEEDER DISTRIBUTION CONVERSION
519 SW 12TH ST, RENTON, WA 98057
N/A N/A
N/A 101183997
AS NOTED 3 / 12
KING N/A N/A CSPSKEPM
NW 19-23N-05E N/A N/A
2305E074 2305E076 2305E074SW EAR-13
COMCAST
TODD ZIMNY
360-507-0598
ZIPLY
WA.structure.Access@ziply.com
888-688-0013
.
.
.
N/A
N/A
N/A
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL 811 TWO BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
10
1
1
8
3
9
9
7
SCALE: NONE
UNDERGROUND CIRCUIT MAP (BEFORE)
SCALE: NONE
UNDERGROUND CIRCUIT MAP (AFTER)
MFP26001535
D
D
D
D
D
D
D
D
D
D
D
D
D
P
P
P
P
P
P
P
PP
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P P P P P P P
P
P
P P P P
P
P
P
P
P
P
P P P P P P P P P P P P P P P P P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
PP
P
P
P
P
P
P
P
P
P
P FDC
397 MCMA
A
CC
B
A
#2ACSRC
B
A
#2ACSR
AB
C
600
39
7
M
C
M
A
A
C
39
7
M
C
M
A
A
C
39
7
M
C
M
A
A
C
ABCN
SD
SD
SD
SD
SD
SD
SD
SD
SD
S
D
S
D
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
S
D
S
D
S
D
S
D
S
D
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS SS
SS SS
SS
SS
SS SS
SS
SS
SS SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
EAR
13
PROPOSED
DRIVE
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
J. VELASCO (360) 296-3127 3/23/26
J. VELASCO (360) 296-3127 3/23/26
N/A N/A N/A
T. MYER .3/23/26
RW-141033 RENTON
WALKER'S RENTON SUBARU
OH-UG FEEDER DISTRIBUTION CONVERSION
519 SW 12TH ST, RENTON, WA 98057
N/A N/A
N/A 101183997
1" = 20'4 / 12
KING N/A N/A CSPSKEPM
NW 19-23N-05E N/A N/A
2305E074 2305E076 2305E074SW EAR-13
COMCAST
TODD ZIMNY
360-507-0598
ZIPLY
WA.structure.Access@ziply.com
888-688-0013
.
.
.
N/A
N/A
N/A
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL 811 TWO BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
10
1
1
8
3
9
9
7
REMOVAL SITE PLAN
SCALE: 1" = 20'
00 1"2"
00 20'40'
MA
T
C
H
L
I
N
E
SE
E
P
A
G
E
5
/
1
2
A
A
SITE SPECIFIC NOTES
P01: EXISTING 65’ CL 1 2009 GRID # 317385-165613
EXISTING POLE TO REMAIN
P02: EXISTING 45’ CL 4 2004 GRID # 317389-165630
EXISTING POLE TO BE REMOVED
WO# 108162437
REMOVE EXISTING 45' CL 4 2004 POLE
REMOVE POLE STUB AFTER COMMUNICATION TRANSFERS HAVE BEEN COMPLETED
NOTE: POTELCO TO TIE UP COMMS WHEN POSSIBLE, ATTACHED UTILITIES: COMCAST
REMOVE EXISTING STLT (SLAP0375)
WO# 593270756
[TRANSFER CAPACITOR BANK 900kVAr 12kV #X8719 TO NEW POLE P08 - SEE SHEEET 7]
SPAN NOTES
P01-P02
WO# 108162437
REMOVE EXISTING 3Ø PRIMARY #2ACSR & NEUT L = 160', (ACTUAL________)
P02-P03
WO# 108162437
REMOVE EXISTING 3Ø 397AAC PRIMARY & 4/0ACSR NEUT L = 120', (ACTUAL________)
MFP26001535
S
S
S
S
S
D
D
D
D
D
D
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P P P P P P P
P
P
397 MCMA
A
C
C
B
A
397 MCMA
A
C
C
B
A
X1819
SD
SDS
D
S
D
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SS
SS
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
J. VELASCO (360) 296-3127 3/23/26
J. VELASCO (360) 296-3127 3/23/26
N/A N/A N/A
T. MYER .3/23/26
RW-141033 RENTON
WALKER'S RENTON SUBARU
OH-UG FEEDER DISTRIBUTION CONVERSION
519 SW 12TH ST, RENTON, WA 98057
N/A N/A
N/A 101183997
1" = 20'5 / 12
KING N/A N/A CSPSKEPM
NW 19-23N-05E N/A N/A
2305E074 2305E076 2305E074SW EAR-13
COMCAST
TODD ZIMNY
360-507-0598
ZIPLY
WA.structure.Access@ziply.com
888-688-0013
.
.
.
N/A
N/A
N/A
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL 811 TWO BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
10
1
1
8
3
9
9
7
REMOVAL SITE PLAN
SCALE: 1" = 20'
00 1"2"
00 20'40'
MA
T
C
H
L
I
N
E
SE
E
P
A
G
E
4
/
1
2
A
A
SITE SPECIFIC NOTES
P03: EXISTING 50’ CL 3 1970 GRID # 317391-165641
EXISTING POLE TO BE REMOVED
WO# 108162437
REMOVE EXISTING 50' CL 3 1970 POLE
REMOVE EXISTING STLT (SLAP0376)
REMOVE POLE STUB AFTER COMMUNICATION TRANSFERS HAVE BEEN COMPLETED
NOTE: POTELCO TO TIE UP COMMS WHEN POSSIBLE, ATTACHED UTILITIES: COMCAST, CENTURY LINK
P04: EXISTING 40’ CL UNK 1963 GRID # 317394-165654
EXISTING POLE TO BE REMOVED
WO# 108162437
REMOVE EXISTING 40' CL UNK 1963 POLE
REMOVE EXISTING STLT (SLAP0377)
P05: EXISTING 60’ CL UNK 1996 GRID # 317398-165673
EXISTING POLE TO REMAIN
SPAN NOTES
P03-P04
WO# 108162437
REMOVE EXISTING 3Ø 397AAC PRIMARY & #2ACSR NEUT L = 135', (ACTUAL________)
MFP26001535
D
D
D
D
D
D
D
D
D
D
D
D
D
P
P
P
P
P
P
P
PP
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P P P P P P P
P
P
P P P P
P
P
P
P
P
P
P P P P P P P P P P P P P P P P P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
PP
P
P
P
P
P
P
P
P
P
P FDC
#2ACSR
AB
C
600
39
7
M
C
M
A
A
C
39
7
M
C
M
A
A
C
39
7
M
C
M
A
A
C
ABCN
NO
SD
SD
SD
SD
SD
SD
SD
SD
SD
S
D
S
D
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
S
D
S
D
S
D
S
D
S
D
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS SS
SS SS
SS
SS
SS SS
SS
SS
SS SS
SS
SS
SS
SS
SS
SS
SS SS
SS
SS
SS
EAR
13
PROPOSED
DRIVE
SEE PARTIAL PLAN DETAIL 'A'
2.5'
10'
NO
2'
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
J. VELASCO (360) 296-3127 3/23/26
J. VELASCO (360) 296-3127 3/23/26
N/A N/A N/A
T. MYER .3/23/26
RW-141033 RENTON
WALKER'S RENTON SUBARU
OH-UG FEEDER DISTRIBUTION CONVERSION
519 SW 12TH ST, RENTON, WA 98057
N/A N/A
N/A 101183997
1" = 20'6 / 11
KING N/A N/A CSPSKEPM
NW 19-23N-05E N/A N/A
2305E074 2305E076 2305E074SW EAR-13
COMCAST
TODD ZIMNY
360-507-0598
ZIPLY
WA.structure.Access@ziply.com
888-688-0013
.
.
.
N/A
N/A
N/A
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL 811 TWO BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
10
1
1
8
3
9
9
7
INSTALL SITE PLAN
SCALE: 1" = 20'
00 1"2"
00 20'40'
MA
T
C
H
L
I
N
E
SE
E
P
A
G
E
7
/
1
2
B
B
SITE SPECIFIC NOTES
P01: EXISTING 65’ CL 1 2009 GRID # 317385-165613
WO# 101183997
EXISTING POLE TO REMAIN
INSTALL TRIPLE HELIX ANCHOR 10”-12”-14” (ANDH3) AS PER STD 6012.1000
NOTE: INSTALL LEAD 10' EAST
INSTALL DBL GUY 7/16” ANC w/AUTO GRIP (GYDD7SA) AS PER STD 6013.0100
INSTALL GUY 3/8” ANC w/AUTO GRIP, NEUTRAL (GYD3SAN) AS PER STD 6013.0100
P06: 317384-165601
WO# 101183997
INTERSET NEW POLE
INSTALL 65FT CL2 POLE (PD652) AS PER STD 6010.1000
INSTALL 12kV 3-PHASE, #2ACSR (TAN312) AS PER STD 6033.1010
INSTALL #2ACSR "H" CONNECTOR (MID: 2167000) AS PER STD 6099.9999, TBL 4
INSTALL 12kV FEEDER TERM (TSU3DF1) AS PER STD 6043.1020
INSTALL NEW SW # X97494
INSTALL RISER, 6" COND SYS STANDOFF (RIS6CSS) AS PER STD 6042.1000
INSTALL NEW GRID #
J01: 317382-165603
WO# 101183997
INSTALL 12kV 5' X 7' X 5' 4-POS J-BOX (JBOX15L) AS PER STD 6055.1030
INSTALL (6) 12kV ELBOW KIT (ELB10J) AS PER STD 6041.1000
INSTALL (6) CABLE TAG # (MID: 3861000)
INSTALL GRID #
J02: 317380-165603
WO# 101183997
INSTALL 12kV 5' X 7' X 5' 4-POS J-BOX (JBOX15L) AS PER STD 6055.1030
INSTALL (6) 12kV ELBOW KIT (ELB10J) AS PER STD 6041.1000
INSTALL (6) CABLE TAG # (MID: 3861000)
INSTALL GRID #
SW1: 317381-165603
WO# 101183997
INSTALL 12kV PME-9 W/ VAULT (PME0915) AS PER STD 6056.1010
INSTALL (6) 12kV 1/0 ELBOW KIT (ELB10J) AS PER STD 6041.1000
INSTALL (6) 12kV 750 ELBOW KIT (ELB750) AS PER STD 6041.1000
FUSE @ 150E (MID: 3285200)
UG SW # U97497
INSTALL GRID #
3
2
1
3
2
1 1
2
3
3
2
1
AØ - EJS472
BØ - EJS473
CØ - EJS474
CØ - EJS475
BØ - EJS476
AØ - EJS477
AØ - EJS496
BØ - EJS497
CØ - EJS498
CØ - EJS515
BØ - EJS516
AØ - EJS517
PME-9 CONNECTION DIAGRAM
PME PADMOUNT SWITCH
NOT TO SCALE 6056.1010
TO PV1
TO P06 TO J01
TO J02
PARTIAL PLAN DETAIL 'A'
SCALE: 1" = 5'
U97497
SPAN NOTES
P06-SW1
WO# 101183997
INSTALL NEW 1-6" SCH80 CONDUIT, APPROX. 60' (ACTUAL = ______)
INSTALL NEW SPARE 1-6" CONDUIT DB-120 APPROX. 60' (ACTUAL = ______)
INSTALL NEW 12kV 3Ø 750 AL STR CABLE APPROX. 100' (ACTUAL = _______)
NOTE: INSTALL ON CABLES #'S AØEJS472, BØEJS473, CØEJS474
SW1-PV1
WO# 101183997
INSTALL NEW 1-6" SCH80 CONDUIT, APPROX. 310' (ACTUAL = ______)
INSTALL NEW SPARE 1-6" CONDUIT DB-120 APPROX. 310' (ACTUAL = ______)
INSTALL NEW 12kV 3Ø 750 AL STR CABLE APPROX. 330' (ACTUAL = _______)
NOTE: INSTALL ON CABLES #'S AØEJS475, BØEJS476, CØEJS477
SW1-J01
WO# 101183997
INSTALL NEW 1-4" SCH80 CONDUIT, APPROX. 15' (ACTUAL=______)
INSTALL NEW 12kV 3Ø 1/0 SOL JKT CABLE APPROX. 25' (ACTUAL = _______)
NOTE: INSTALL ON CABLES #'S AØEJS496, BØEJS497, CØEJS498
SW1-J02
WO# 101183997
INSTALL NEW 1-4" SCH80 CONDUIT, APPROX. 15' (ACTUAL = ______)
INSTALL NEW 12kV 3Ø 1/0 SOL JKT CABLE APPROX. 25' (ACTUAL = _______)
NOTE: INSTALL ON CABLES #'S AØEJS515, BØEJS516, CØEJS517
J01-J02
WO# 101183997
INSTALL NEW 1-4" SCH80 CONDUIT, APPROX. 20' (ACTUAL = ______)
INSTALL NEW 12kV 3Ø 1/0 SOL JKT CABLE APPROX. 40' (ACTUAL = _______)
NOTE: INSTALL ON CABLES #'S AØEJS493, BØEJS494, CØEJS495
AND PARK ELBOWS FOR NORMAL OPEN IN J02
J02-J03
WO# 101183997
INSTALL NEW 1-4" SCH80 CONDUIT, APPROX. 330' (ACTUAL = ______)
INSTALL NEW SPARE 1-4" CONDUIT DB-120 APPROX. 330' (ACTUAL = ______)
INSTALL NEW 12kV 3Ø 1/0 SOL JKT CABLE APPROX. 350' (ACTUAL = _______)
NOTE: INSTALL ON CABLES #'S AØEJS478, BØEJS479, CØEJS480
SW1
MFP26001535
S
S
S
S
S
D
D
D
D
D
D
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P P P P P P P
P
P
397 MCMA
A
C
C
B
A
X1819
SD
SDS
D
S
D
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SS
SS
NO
TREE TRIMMING
REQUIRED
SEE PARTIAL PLAN DETAIL 'B'
P
P
P
P
P
P
P
P
P
P P P P P
SD
SD
SD
SD
SD
SD
SD
SD
SD
SDS
S
S
S
S
S
NO
4'
6'
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
J. VELASCO (360) 296-3127 3/23/26
J. VELASCO (360) 296-3127 3/23/26
N/A N/A N/A
T. MYER .3/23/26
RW-141033 RENTON
WALKER'S RENTON SUBARU
OH-UG FEEDER DISTRIBUTION CONVERSION
519 SW 12TH ST, RENTON, WA 98057
N/A N/A
N/A 101183997
1" = 20'7 / 12
KING N/A N/A CSPSKEPM
NW 19-23N-05E N/A N/A
2305E074 2305E076 2305E074SW EAR-13
COMCAST
TODD ZIMNY
360-507-0598
ZIPLY
WA.structure.Access@ziply.com
888-688-0013
.
.
.
N/A
N/A
N/A
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL 811 TWO BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
10
1
1
8
3
9
9
7
INSTALL SITE PLAN
SCALE: 1" = 20'
00 1"2"
00 20'40'
MA
T
C
H
L
I
N
E
SE
E
P
A
G
E
6
/
1
2
B
B
SITE SPECIFIC NOTES
P05: EXISTING 60’ CL UNK 1996 GRID # 317398-165673
EXISTING POLE TO REMAIN
P07: 317394-165644
NEW POLE, TREE TRIMMING REQUIRED
WO# 101183997
INSTALL 65FT CL2 POLE (PD652) AS PER STD 6010.1000
INSTALL 12kV 3-PHASE, 397 AAC DE (DE3315) AS PER STD 6033.1042
INSTALL 336 AAC "H" CONNECTOR (MID: 2168000) AS PER STD 6099.9999, TBL 4
INSTALL (3) STIRRUP (MID: 2254100) AS PER STD 6099.9999, TBL 2
INSTALL (3) WEDGE CONNECTOR (MID: 2368200) AS PER STD 6099.999, TBL 13
INSTALL 12kV FEEDER & 1/0 TERM (TSU6D31) AS PER STD 6043.1022
INSTALL NEW SW # T97495 (600A)
INSTALL NEW SW # T97496 (200A)
INSTALL 100T FUSE (MID: 3412700)
INSTALL RISER, 6" COND SYS STANDOFF (RIS6CSS) AS PER STD 6042.1000
INSTALL RISER, 4" COND SYS STANDOFF (RIS6CSS) AS PER STD 6042.1000
INSTALL TRIPLE HELIX ANCHOR 10”-12”-14” (ANDH3) AS PER STD 6012.1000
NOTE: INSTALL LEAD 25' WEST
INSTALL GUY DBL 7/16” ANC w/AUTO GRIP (GYDD7SA) AS PER STD 6013.0100
INSTALL GUY 7/16” ANC w/AUTO GRIP, NEUTRAL (GYD7SAN) AS PER STD 6013.0100
INSTALL NEW GRID #
P08: 317394-165645
INTERSET NEW POLE, TREE TRIMMING REQUIRED
WO# 101183997
INSTALL 65FT CL2 POLE (PD652) AS PER STD 6010.1000
INSTALL 12kV 3-PHASE, 397 AAC PTP (TAN313) AS PER STD 6033.1012
INSTALL 336 AAC "H" CONNECTOR (MID: 2168000) AS PER STD 6099.9999, TBL 4
INSTALL NEW GRID #
WO# 593270756
[TRANSFER CAPACITOR BANK 900kVAr 12kV #X8719 (40T) FROM POLE P02 -SEE SHEET 4]
V01: 317390-165629
NEW VAULT
WO# 101183997
INSTALL 36" X 42" X 38" MINI-PAD UNISTRUT HH W/ GROUNDS (MINU1SR) AS PER STD 6045.1010
INSTALL 37.5KVA PADMOUNT XFMR (MID: 6247050)
INSTALL (3) #6-350 KCMIL SECONDARY CONNECTION BLOCKS (MID: 4842002)
INSTALL CABLE TAG # (MID: 3861000)
INSTALL GRID #
V02: 317389-165629
NEW VAULT
WO# 101183997
INSTALL 36" X 42" X 38" MINI-PAD UNISTRUT HH W/ GROUNDS (MINU1SR) AS PER STD 6045.1010
INSTALL 25KVA PADMOUNT XFMR (MID: 6247000)
INSTALL (3) #6-350 KCMIL SECONDARY CONNECTION BLOCKS (MID: 4842002)
INSTALL CABLE TAG # (MID: 3861000)
INSTALL GRID #
J03: 317389-165630
NEW J-BOX
WO# 101183997
INSTALL 12kV 5' X 7' X 5' 4-POS J-BOX (JBOX15L) AS PER STD 6055.1030
INSTALL (8) 12kV ELBOW KIT (ELB10J) AS PER STD 6041.1000
INSTALL (9) CABLE TAG # (MID: 3861000)
INSTALL GRID #
PV1: 317384-165630
NEW PULL BOX
WO# 101183997
INSTALL 5' X 11' X 5' w/3' SQ ADJ PC H20 (SVT5ADJ) AS PER STD 6051.2000
INSTALL COPPER "C" CONNECTOR (MID: 2162500)
INSTALL (3) 12kV 750 SPLICE (SPL750)
INSTALL (3) CABLE TAG # (MID: 3861000)
INSTALL GRID #
PARTIAL PLAN DETAIL 'B'
SCALE: 1" = 10'
SPAN NOTES
PV1-P07
WO# 101183997
INSTALL NEW 1-6" SCH80 CONDUIT, APPROX. 205' (ACTUAL = ______)
INSTALL NEW SPARE 1-6" CONDUIT DB-120 APPROX. 205' (ACTUAL = ______)
INSTALL NEW 12kV 3Ø 750 AL STR CABLE APPROX. 225' (ACTUAL = _______)
NOTE: INSTALL ON CABLES #'S AØEJS475, BØEJS476, CØEJS477
P07-J03
WO# 101183997
INSTALL NEW 1-6" SCH80 CONDUIT, APPROX. 155' (ACTUAL = ______)
INSTALL NEW SPARE 1-6" CONDUIT DB-120 APPROX. 155' (ACTUAL = ______)
INSTALL NEW 12kV 3Ø 1/0 SOL JKT CABLE APPROX. 195' (ACTUAL = _______)
NOTE: INSTALL ON CABLES #'S AØEJS490, BØEJS491, CØEJS492 AND PARK
ELBOWS FOR NORMAL OPEN IN J03
J03-V01
WO# 101183997
INSTALL NEW 1-6" SCH80 CONDUIT, APPROX. 35' (ACTUAL = ______)
INSTALL NEW 12kV 1Ø 1/0 SOL JKT CABLE APPROX. 55' (ACTUAL = _______)
NOTE: INSTALL ON CABLE # CØEJS508
J03-V02
WO# 101183997
INSTALL NEW 1-6" SCH80 CONDUIT, APPROX. 20' (ACTUAL = ______)
INSTALL NEW 12kV 1Ø 1/0 SOL JKT CABLE APPROX. 40' (ACTUAL = _______)
NOTE: INSTALL ON CABLE # AØEJS464
V01-H01
WO# 101183997
INSTALL NEW 1-3" SCH80 CONDUIT, APPROX. 10' (ACTUAL = ______)
INSTALL NEW SEC 350 CABLE APPROX. 70' (ACTUAL = _______)
MFP26001535
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
J. VELASCO (360) 296-3127 3/23/26
J. VELASCO (360) 296-3127 3/23/26
N/A N/A N/A
T. MYER .3/23/26
RW-141033 RENTON
WALKER'S RENTON SUBARU
OH-UG FEEDER DISTRIBUTION CONVERSION
519 SW 12TH ST, RENTON, WA 98057
N/A N/A
N/A 101183997
N/A 8 / 12
KING N/A N/A CSPSKEPM
NW 19-23N-05E N/A N/A
2305E074 2305E076 2305E074SW EAR-13
COMCAST
TODD ZIMNY
360-507-0598
ZIPLY
WA.structure.Access@ziply.com
888-688-0013
.
.
.
N/A
N/A
N/A
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL 811 TWO BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
10
1
1
8
3
9
9
7
PRIMARY CABLE & CONDUIT TABLE
LOCATION
CONDUIT PRIMARY CABLE ASBUILT INFORMATION
SIZE
Qty
LENGTH
Design
(ft)
BENDS PULL PULL Cable LENGTH
Design
(ft)
Cable Numbers Please Record Foreman - Complete
FROM TO (in)90°45°22°11°(lbs)Rev
(lbs)Size A B C Manufacturer Compound Year Actual Amount Installed (Conduit & Cable)
P06 SW1 6 1 60 1 68 787 750 FEEDER 130 EJS472 EJS473 EJS474
P06 SW1 6 1 60 1 CONDUIT ONLY
SW1 PV1 6 1 310 1 1 2 1179 1151 750 FEEDER 340 EJS475 EJS476 EJS477
SW1 PV1 6 1 310 1 1 2 CONDUIT ONLY
SW1 J01 4 1 15 1 153 153 3Ø 1/0 JKT 45 EJS496 EJS497 EJS498
SW1 J02 4 1 15 1 153 153 3Ø 1/0 JKT 45 EJS515 EJS516 EJS517
J01 J02 (NO)4 1 20 104 104 3Ø 1/0 JKT 50 EJS493 EJS494 EJS495
J02 J03 4 1 330 1 1 4 534 512 3Ø 1/0 JKT 360 EJS478 EJS479 EJS480
J02 J03 4 1 330 1 1 4 CONDUIT ONLY
PV1 P07 6 1 205 2 1 1086 815 750 FEEDER 250 EJS475 EJS476 EJS477
PV1 P07 6 1 205 2 1 CONDUIT ONLY
P07 J03 (NO)4 1 155 1 128 362 3Ø 1/0 JKT 200 EJS490 EJS491 EJS492
P07 J03 4 1 155 1 CONDUIT ONLY
J03 V01 2 1 35 1 2 80 74 1Ø 1/0 JKT 45 EJS508
J03 V02 2 1 20 1 65 61 1Ø 1/0 JKT 30 EJS464
2" PVC (FT) & BENDS =55'2 2 1Ø 1/0 AL JKT TOTAL (FT) =95'
4" PVC (FT) & BENDS =1020'4 4 8 3Ø 1/0 AL JKT TOTAL (FT) =635'
6" PVC (FT) & BENDS =1150'2 8 6 3Ø 750 AL JKT TOTAL (FT) =655'
WIRE REMOVAL TABLE
Location
Pri Sec Wire Size & Type Quantity
Length
(ft per
conductor)Remarks UnitsFromTo
P01 P02 X #2ACSR PRI & NEUT 4 160'
P02 P03 X 397 AAC PRI 3 120'
P02 P03 X 4/0 ACSR NEUT 1 120'
P03 P04 X 397 AAC PRI 3 135'
P03 P04 X 4/0 ACSR NEUT 1 135'
Total Feet (397AAC) Removed 765'
Total Feet (4/0 ACSR NEUT) Removed 255'
Total Feet (#2ACSR & NEUT) Removed 640'
POLE RETIREMENT TABLE TEMP TRANSFERS ST. LIGHT TRANSFERS
Wk
Loc
Pole Data Pole
TEL TV FIBER TRAN RMVD ID NUMBER
Grid #Length Class Year TOPPED RMVD
P02 317389-165630 45 4 2004 X SLAP0375
P03 317391-165641 50 3 1970 X SLAP0376
P04 317394-165654 40 UNK 1963 X SLAP0377
Removed at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER REMOVAL
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
P03
317391-165641
45kVA
VAULT & EQUIPMENT TABLE
SITE #GRID #
VAULT SIZE &
COVER
TYPE & SIZE
EQUIPMENT IN
VAULT
PRIMARY
BUSHINGS
TRANSFORMER ID NUMBERS
(COMPANY ID)
ENGINEERING
INFORMATION
AS-BUILT INFORMATION
LB DC FOREMAN: INCLUDE PHASE TAPPED
SW1 317381
165603
HH 5106 w/3-3'
SQ, 58"x66" HOLE
Matid: 9996351
SW PM DIST PME-9 12 -
PME0915 6056.1010 ABCØ
ELB10J 6041.1000 x 6
ELB750 6041.1000 x 6
J01 317382
165603
4'8"x7'x5'
w/2-3' Sq Doors
Matid: 7663200
J-Box Below Grade
w/4-Pos J-Bus x3
Matid: 7625900
6 6 JBOX15L 6055.1030 ABCØ
ELB10J 6041.1000
J02 317380
165603
4'8"x7'x5'
w/2-3' Sq Doors
Matid: 7663200
J-Box Below Grade
w/4-Pos J-Bus x3
Matid: 7625900
6 6 JBOX15L 6055.1030 ABCØ
ELB10J 6041.1000
J03 317389
165630
4'8"x7'x5'
w/2-3' Sq Doors
Matid: 7663200
J-Box Below Grade
w/4-Pos J-Bus x3
Matid: 7625900
8 4 JBOX15L 6055.1030 ABCØ
ELB10J 6041.1000
V01 317390
165629
42"x48"x38"
Unistrut HH
Matid: 7663001
37.5KVA MP TRF
120/240
Matid: 6247500
1 1
MINU1SR 6045.1010 _Ø
V02 317389
165629
42"x48"x38"
Unistrut HH
Matid: 7663001
25KVA MP TRF
120/240
Matid: 6247000
1 1
MINU1SR 6045.1010 _Ø
PV1 317384
165630
5' X 11' X 5' w/3'
SQ ADJ PC H20
FEEDER PULL
VAULT --SVT5ADJ 6051.2000
SPL750 6041.2000 ABCØ
Installed at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER INSTALLATION
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
Material ID#:
V01
317390-165629
37.5kVA
6247500
Installed at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER INSTALLATION
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
Material ID#:
V02
317389-165629
25kVA
6247000
SECONDARY CABLE & CONDUIT TABLE
LOCATION
CABLE CONDUIT ASBUILT INFORMATION
SIZE LENGTH
Design
(ft)
SIZE LENGTH
Design
(ft)
BENDS Foreman - Complete
FROM TO (1/0,4/0,350)(in)90°45°22°11°Actual Amount Installed (Conduit & Cable)
V01 H01 350 TPX 70 CABLE ONLY
V01 IP1 CONDUIT ONLY 3 10
POLE TABLE (NEW)
SITE POLE DATA
GRID #HEIGHT CLASS YEAR REMARKS / LOCATION REF
P06 317384-165601 65 2
P07 317394-165644 65 2
P08 317394-165645 65 2
Installed at site:
Grid Number:
kVAr Rating:
Foreman to redline the following information
CAPACITOR BANK TRANSFER
Company ID#:
Primary phase connected to:
P08
317394-165645
900 kVAr
MFP26001535
397 MCM
A
A
C
C
B
A
397 MCMA
A
CC
B
A
397 MCM
A
A
CCB
A
#2ACSRCB
A
#2ACSR
AB
C
39
7
M
C
M
A
A
C
39
7
M
C
M
A
A
C
39
7
M
C
M
A
A
C
ABCN
X1819
NO
X97494
U97497
EAR
13
NO
T97496
T97495
NEW 3Ø 750AL CABLE, ±225'
AØEJS475
BØEJS476
CØEJS477
NEW 3Ø 750AL CABLE, ±100'
AØEJS472
BØEJS473
CØEJS474
NEW 3Ø 1/OAL CABLE, ±25'
AØEJS496
BØEJS497
CØEJS498
NEW 3Ø 750AL CABLE, ±330'
AØEJS475
BØEJS476
CØEJS477
NEW 3Ø 1/OAL CABLE, ±25'
AØEJS515
BØEJS516
CØEJS517
NEW 3Ø 1/OAL CABLE, ±40'
AØEJS493
BØEJS494
CØEJS495
NEW 3Ø 1/OAL CABLE, ±350'
AØEJS478
BØEJS479
CØEJS480
NEW 3Ø 1/OAL CABLE, ±195'
AØEJS490
BØEJS491
CØEJS492
NEW 1Ø 1/OAL CABLE, ±55'
CØEJS508
NEW 1Ø 1/OAL CABLE, ±40'
AØEJS464
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
J. VELASCO (360) 296-3127 3/23/26
J. VELASCO (360) 296-3127 3/23/26
N/A N/A N/A
T. MYER .3/23/26
RW-141033 RENTON
WALKER'S RENTON SUBARU
OH-UG FEEDER DISTRIBUTION CONVERSION
519 SW 12TH ST, RENTON, WA 98057
N/A N/A
N/A 101183997
N/A 9 / 12
KING N/A N/A CSPSKEPM
NW 19-23N-05E N/A N/A
2305E074 2305E076 2305E074SW EAR-13
COMCAST
TODD ZIMNY
360-507-0598
ZIPLY
WA.structure.Access@ziply.com
888-688-0013
.
.
.
N/A
N/A
N/A
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL 811 TWO BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
10
1
1
8
3
9
9
7
PRE & POST CONSTRUCTION ONE-LINE
NOT TO SCALE
MFP26001535
397 MCMA
A
CCB
A
#2ACSR
A
B
C
39
7
M
C
M
A
A
C
39
7
M
C
M
A
A
C
39
7
M
C
M
A
A
C
ABCN
X1819
NO
X97494
U97497
EAR
13
NO
T97496
T97495
NEW 3Ø 750AL CABLE, ±225'
AØEJS475
BØEJS476
CØEJS477
NEW 3Ø 750AL CABLE, ±100'
AØEJS472
BØEJS473
CØEJS474
NEW 3Ø 1/OAL CABLE, ±25'
AØEJS496
BØEJS497
CØEJS498
NEW 3Ø 750AL CABLE, ±330'
AØEJS475
BØEJS476
CØEJS477
NEW 3Ø 1/OAL CABLE, ±25'
AØEJS515
BØEJS516
CØEJS517
NEW 3Ø 1/OAL CABLE, ±40'
AØEJS493
BØEJS494
CØEJS495
NEW 3Ø 1/OAL CABLE, ±350'
AØEJS478
BØEJS479
CØEJS480
NEW 3Ø 1/OAL CABLE, ±195'
AØEJS490
BØEJS491
CØEJS492
NEW 1Ø 1/OAL CABLE, ±55'
CØEJS508
NEW 1Ø 1/OAL CABLE, ±40'
AØEJS464
90°
(2) NEW 6" SCH 80
L=310'
(2) NEW 4" SCH 80
L=330'
(2) NEW 6" SCH 80
L=205'
(1) NEW 4" SCH 80
L=20'
22.5°
22.5°90°
22.5°
(2) NEW 6" SCH 80
L=60'
90°
22.5°
45°45°
90°
22.5°
22.5°45°
45°
45°
(1) NEW 4" SCH 80
L=15'
(1) NEW 4" SCH 80
L=15'
(2) NEW 4" SCH 80
L=155'
(1) NEW 2" SCH80
L=20'
(1) NEW 2" SCH80
L=35'
(1) NEW 3" SCH80
L=10'
T97496
T97495
X97494
U97497
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
J. VELASCO (360) 296-3127 3/23/26
J. VELASCO (360) 296-3127 3/23/26
N/A N/A N/A
T. MYER .3/23/26
RW-141033 RENTON
WALKER'S RENTON SUBARU
OH-UG FEEDER DISTRIBUTION CONVERSION
519 SW 12TH ST, RENTON, WA 98057
N/A N/A
N/A 101183997
N/A 10 / 12
KING N/A N/A CSPSKEPM
NW 19-23N-05E N/A N/A
2305E074 2305E076 2305E074SW EAR-13
COMCAST
TODD ZIMNY
360-507-0598
ZIPLY
WA.structure.Access@ziply.com
888-688-0013
.
.
.
N/A
N/A
N/A
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL 811 TWO BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
10
1
1
8
3
9
9
7
PROPOSED ONE-LINE DIAGRAM
NOT TO SCALE
PROPOSED CONDUIT DIAGRAM
NOT TO SCALE
CONDUIT LEGEND
SECONDARY 3"
PRIMARY 2"
FEEDER 6"
PRIMARY 4"
MFP26001535
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
J. VELASCO (360) 296-3127 3/23/26
J. VELASCO (360) 296-3127 3/23/26
N/A N/A N/A
T. MYER .3/23/26
RW-141033 RENTON
WALKER'S RENTON SUBARU
OH-UG FEEDER DISTRIBUTION CONVERSION
519 SW 12TH ST, RENTON, WA 98057
N/A N/A
N/A 101183997
AS NOTED 11 / 12
KING N/A N/A CSPSKEPM
NW 19-23N-05E N/A N/A
2305E074 2305E076 2305E074SW EAR-13
COMCAST
TODD ZIMNY
360-507-0598
ZIPLY
WA.structure.Access@ziply.com
888-688-0013
.
.
.
N/A
N/A
N/A
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL 811 TWO BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
10
1
1
8
3
9
9
7
J-BOX B-FLY DETAIL (J01)
SCALE: NONE
Prop 4" (SW1)
Prop 4" (J02)
NORMAL OPEN
J-BOX B-FLY DETAIL (J02)
SCALE: NONE
Prop 4" (SW1)
Prop 4" (J01)
NORMAL OPEN
PM SWITCH VAULT B-FLY DETAIL (SW1)
SCALE: NONE
Prop 6" (P06)
SPARE
Prop 4" (J02)
Prop 6" (PV1)
Prop 4" (J01)
J-BOX B-FLY DETAIL (J03)
SCALE: NONE
Prop 2" (V02)
Prop 4" (J02)
SPARE
Prop 2" (V01)
Prop 4" (P07)
NORMAL OPEN
PULL VAULT B-FLY DETAIL (PV1)
SCALE: NONE
PM XFMR VAULT B-FLY DETAIL (V01)
SCALE: NONE
Prop 2" (J03)
Fr
o
n
t
o
f
V
a
u
l
t
Prop 3" (IP1)
PM XFMR VAULT B-FLY DETAIL (V02)
SCALE: NONE
Prop 2" (J03)
Fr
o
n
t
o
f
V
a
u
l
t
PREFFERED SECONDARY ENTRY
Preferred Customer Owned Services.
Deep vault entry for straight shot to connector bars
on front right side of vault.
*Cant enter services from primary entry
Prop 6" (P07)
SPARE
Prop 6" (SW1)
Prop 4" (J03)
Prop 4" (J03)
SPARE
Prop 4" (J02)
Prop 6" (PV1)
SPARE
Prop 4" (J02)
SPARE
Prop 6" (P06)
Prop 6" (P07)
Prop 6" (SW1)
SPARE
Prop 4" (P07)
SPARE
MFP26001535
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
J. VELASCO (360) 296-3127 3/23/26
J. VELASCO (360) 296-3127 3/23/26
N/A N/A N/A
T. MYER .3/23/26
RW-141033 RENTON
WALKER'S RENTON SUBARU
OH-UG FEEDER DISTRIBUTION CONVERSION
519 SW 12TH ST, RENTON, WA 98057
N/A N/A
N/A 101183997
AS NOTED 12/12
KING N/A N/A CSPSKEPM
NW 19-23N-05E N/A N/A
2305E074 2305E076 2305E074SW EAR-13
COMCAST
TODD ZIMNY
360-507-0598
ZIPLY
WA.structure.Access@ziply.com
888-688-0013
.
.
.
N/A
N/A
N/A
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL 811 TWO BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
10
1
1
8
3
9
9
7
2"
Excavation - 19-1/2 cubic yards
SIDE VIEW
5'-4"Crushed
6"
Rock
TOP VIEW
9'
11'
7'-0"
4'-0"
1'
4'-8"
4,750 lbs
2,490 lbs
VAULT & EXCAVATION DETAIL @ J01-J03
Not to scale 6051.1500
6'-5"
11'-4" Min
11'-10" Max
7'-6"
overall
overall
5'-10" Min
6'-4" Max
8"
58"
66"
2"
6"
CRUSHED
ROCK
16'-0"
10'-0"
8'-6"
EXCAVATION - 50-1/2 CUBIC YARDS
PME-9 VAULT & EXCAVATION DETAIL @ SW1
Not to scale 6056.1010
11,600 lbs
8,430 lbs
3,930 lbs
SIDE VIEW
TOP VIEW
Cover11'-2"
3' x 3' Diamond Plate
Top
Section
8'-2"
Base TOP VIEW
SIDE VIEW
EXCAVATION: 4-2/3 CUBIC YARDS
Rock
Crushed
6"
3'-6"
2"
6'
6'
48"42"
36"
38"
42"
Struts
VAULT & EXCAVATION DETAIL @ V01 & V02
Not to scale 6045.1000
1950 lbs
2"
Rock
Crushed
6"
8'-6"
10'-0"
16'-0"
11'-4" Min
11'-10" Max
7'-6"
8"
8'-2"
6'-4" Max
5'-10" Min
Excavation - 50-1/2 cubic yards
SIDE VIEW
TOP VIEW
VAULT & EXCAVATION DETAIL @ PV1
Not to scale 6051.2000
11,000 lbs
8,430 lbs
6,600 lbs
Height adjustable bolts Three 3' sq std plate doors, or
Three 3' sq Anti-Skid doors.
11'-2"
5'
3'-6" x 9'-6"
Min Clear Opening
CLEAR WORKING SPACE FOR VAULTS
NOT TO SCALE
FIELD SIDE (PREFERRED)
ROAD SIDE (PREFERRED)
6' MIN
3'
MIN
3'
MIN
3' MIN
Cables should enter the vault so that all of
the cables will lay in the same direction.
TOP VIEW
J- BOX CABLE ENTRY DETAIL
Not to scale
21" Min. bend radius
LSG317
on 750 cable
Mark each cable withcable numbers
Nylon cable tie
PULL VAULT CABLE ENTRY DETAIL
NOT TO SCALE 5'x7' VAULT DETAIL
Cables must enter the vault so that
they will lay in the opposite direction.
TOP VIEW
COOLING
5' MIN
5' MIN
10' MIN
5'
MIN
FINS
ACCESS
CONCRETE PAD
MINIMUM CLEARANCES FOR PADMOUNT TRANSFORMER AND VAULT
CURB OR EDGE OF PAVEMENT
CURB OR EDGE OF PAVEMENT
5' MIN
ROAD OR
PARKING AREA
TYP. PAD
& TRANS-
FORMER
1.5' MIN
DOOR
ACCESS
DOOR
REQUIRED
WORK SPACE
AREA
Not to scale
1.5' MIN
3'
MIN
3' MIN
3' MIN
10' MIN
3'
MIN
MFP26001535