MEMORANDUM
DATE: April 3, 2026
TO: City of Renton
FROM: Stella Oh, P.E.
TENW
SUBJECT: Proposed Streetlight Clearances to Existing Aerial Utilities
Project Name: Wang Short Plat
TENW Project No. 2026-064
Overview
This memorandum has been prepared in response to the City of Renton’s request to verify that the
existing aerial transmission and fiber communication line clearances are acceptable relative to the
proposed streetlight poles along 116th Ave SE associated with the Wang Short Plat.
WAC and NESC Guidelines
Aerial Transmission Line Clearance:
TENW has confirmed with Puget Sound Energy (PSE) that the required clearance between existing aerial
transmission lines and structures along 116th Ave SE is up to 20 ft, with a minimum working clearance of
15 ft. Applicable minimum clearance requirements are outlined in Washington Administrative Code (WAC)
Sections 296-155-53408 and 296-155-428.
Fiber Communication Line Clearance:
Although fiber communication lines do not carry electrical current and are not subject to the same
clearance requirements as energized conductors, the National Electrical Safety Code (NESC) provides
guidance for comparable configurations:
Description Required Clearance NESC Rule
Comm to grounded luminaire bracket/span wire 4 inches min. 238C
Comm to street light drip loops 12 inches min. 238D
Proposed Clearances
The following table summarizes the measured clearances between existing aerial utilities and the
proposed streetlight poles:
Pole Description Transmission Clearance Fiber Clearance
Pole 1: 40-ft Dual Standard 23.4-ft 3.7-ft
Pole F: 18-ft Pedestrian Standard 45.6-ft 4.0-ft
Pole 2: 40-ft Dual Standard 27.0-ft 8.5-ft
Overhead Clearance Memorandum
Wang Short Plat (Renton)
April 3, 2026
Refer to Exhibit C for graphical representations of the proposed streetlight poles and associated aerial
utility clearances.
Conclusion
As shown in Exhibit C, the clearances between the existing aerial transmission and fiber communication
lines and the three proposed streetlight poles along 116th Ave SE meet or exceed the requirements
established by PSE, WAC, and NESC.
Please feel free to contact me at stella@tenw.com or (206) 412-6743 if there are any questions related to
this memorandum.
Attachments:
Exhibit A: Email from Matt Maynard (PSE)
Exhibit B: WAC Section 296-155-53408, Table 4 - Minimum Clearance Distances
Exhibit C: Overhead Clearance Figures (3 total)
Overhead Clearance Memorandum
Wang Short Plat (Renton)
April 3, 2026
Exhibit A
Email from Matt Maynard (PSE)
1
Glen DuBreuil
From:Maynard, James <Matt.Maynard@pse.com>
Sent:Thursday, April 2, 2026 2:03 PM
To:WILLYNEWHART
Cc:Glen DuBreuil; Stella Oh; Daniel Bernik; Elyse Stemmler; Hammons, Michael
Subject:RE: RE: Wang Short Plat | Overhead Transmission Voltage (116th Ave SE)
All,
I hope this information helps. Sorry for the delay on getting back to you. I will be on vacation this Friday
thru next week. I got my co-worker Mike on this email. He may be able to assist you while I’m gone if you
need anything.
~15’ working clearance, 15’-20’ structure.
There are different variables but refer to WAC-
Working near high-voltage power lines in Washington state requires adherence to strict safety
clearances established by the Washington Administrative Code (WAC) to prevent electrocution, with a
general minimum clearance of 10 feet for voltages up to 50 kV. For higher voltages, the clearance must
be increased by 0.4 inches for each 1 kV over 50 kV, or as specified by federal regulations. Key
requirements for working near overhead lines, particularly for crane and construction operations (WAC
296-155-428 and WAC 296-155-53408)
Thanks!
Matt Maynard
Account Manager
Pole Services
Puget Sound Energy
BOTO20
PO Box 97034
Bellevue, WA 98009
Phone Number: 425-628-7701
matt.maynard@pse.com
From: WILLYNEWHART <WILLYNEWHART@comcast.net>
Sent: Wednesday, April 1, 2026 6:38 PM
To: Maynard, James <Matt.Maynard@pse.com>
Cc: Glen DuBreuil <dubreuil@tenw.com>; Stella Oh <stella@tenw.com>; Daniel Bernik <bernik@tenw.com>; Elyse
Stemmler <elyse@tenw.com>
Subject: FW: RE: Wang Short Plat | Overhead Transmission Voltage (116th Ave SE)
CAUTION - EXTERNAL EMAIL
Phishing? Click the PhishAlarm "Report Phish" button.
Matt,
Overhead Clearance Memorandum
Wang Short Plat (Renton)
April 3, 2026
Exhibit A
Washington Administrative Code
Section 296-155-53408 – Table 4
Minimum Clearance Distances
(6) For power lines over 1000 kV, the minimum clearance distance must be established by the(6) For power lines over 1000 kV, the minimum clearance distance must be established by the
utility owner/operator or a RPE who is a qualified person with respect to power transmission andutility owner/operator or a RPE who is a qualified person with respect to power transmission and
distribution.distribution.
Table 4: Minimum Clearance DistancesTable 4: Minimum Clearance Distances
VoltageVoltage
(nominal, kV)(nominal, kV)
Minimum clearanceMinimum clearance
distance (feet)distance (feet)
up to 50up to 50 . . . . . . . . . . . . . . . . . . . . . . . . . 10. . . . . . . . . . . . . . . . . . . . . . . . . 10
over 50 to 200over 50 to 200 . . . . . . . . . . . . . . . . . . . . . . . . . 15. . . . . . . . . . . . . . . . . . . . . . . . . 15
over 200 to 350over 200 to 350 . . . . . . . . . . . . . . . . . . . . . . . . . 20. . . . . . . . . . . . . . . . . . . . . . . . . 20
over 350 to 500over 350 to 500 . . . . . . . . . . . . . . . . . . . . . . . . . 25. . . . . . . . . . . . . . . . . . . . . . . . . 25
over 500 to 750over 500 to 750 . . . . . . . . . . . . . . . . . . . . . . . . . 35. . . . . . . . . . . . . . . . . . . . . . . . . 35
over 750 to 1,000over 750 to 1,000 . . . . . . . . . . . . . . . . . . . . . . . . . 45. . . . . . . . . . . . . . . . . . . . . . . . . 45
over 1,000over 1,000 . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . .
(as established by the utility owner/(as established by the utility owner/
operator or RPE who is a qualified personoperator or RPE who is a qualified person
with respect to electrical powerwith respect to electrical power
transmission and distribution).transmission and distribution).
Note:Note:The value that follows "to" is up to and includes thatThe value that follows "to" is up to and includes that
value.value.
Table 5: Minimum Clearance Distances While Traveling With No Load and Boom/Mast LoweredTable 5: Minimum Clearance Distances While Traveling With No Load and Boom/Mast Lowered
Voltage (nominal,Voltage (nominal,
kV)kV)
While traveling—While traveling—
Minimum clearanceMinimum clearance
distance (feet)distance (feet)
up to 0.75up to 0.75 . . . . . . . . . . . . . . . . . . . . . . . . . 4. . . . . . . . . . . . . . . . . . . . . . . . . 4
(while traveling/boom lowered)(while traveling/boom lowered)
over 0.75 to 50over 0.75 to 50 . . . . . . . . . . . . . . . . . . . . . . . . . 6. . . . . . . . . . . . . . . . . . . . . . . . . 6
(while traveling/boom lowered)(while traveling/boom lowered)
over 50 to 350over 50 to 350 . . . . . . . . . . . . . . . . . . . . . . . . . 10. . . . . . . . . . . . . . . . . . . . . . . . . 10
(while traveling/boom lowered)(while traveling/boom lowered)
over 350 to 750over 350 to 750 . . . . . . . . . . . . . . . . . . . . . . . . . 16. . . . . . . . . . . . . . . . . . . . . . . . . 16
(while traveling/boom lowered)(while traveling/boom lowered)
over 750 to 1,000over 750 to 1,000 . . . . . . . . . . . . . . . . . . . . . . . . . 20. . . . . . . . . . . . . . . . . . . . . . . . . 20
(while traveling/boom lowered)(while traveling/boom lowered)
over 1,000over 1,000 . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . .
(as established by the utility owner/(as established by the utility owner/
operator or RPE who is a qualifiedoperator or RPE who is a qualified
person with respect to electrical powerperson with respect to electrical power
transmission and distribution).transmission and distribution).
[Statutory Authority: RCW [Statutory Authority: RCW 49.17.01049.17.010, , 49.17.04049.17.040, , 49.17.05049.17.050, , 49.17.06049.17.060, and chapter , and chapter 49.1749.17 RCW. WSR RCW. WSR
25-16-089, s 296-155-53408, filed 8/5/25, effective 9/5/25. Statutory Authority: RCW 25-16-089, s 296-155-53408, filed 8/5/25, effective 9/5/25. Statutory Authority: RCW 49.17.01049.17.010,,
49.17.04049.17.040, , 49.17.05049.17.050, , 49.17.06049.17.060. WSR 16-09-085, § 296-155-53408, filed 4/19/16, effective 5/20/16.. WSR 16-09-085, § 296-155-53408, filed 4/19/16, effective 5/20/16.
Statutory Authority: RCW Statutory Authority: RCW 49.17.01049.17.010, , 49.17.04049.17.040, , 49.17.05049.17.050, , 49.17.06049.17.060 and chapter and chapter 49.1749.17 RCW, and 29 RCW, and 29
C.F.R. 1926, Subpart CC. WSR 13-02-068, § 296-155-53408, filed 12/31/12, effective 2/1/13. StatutoryC.F.R. 1926, Subpart CC. WSR 13-02-068, § 296-155-53408, filed 12/31/12, effective 2/1/13. Statutory
Authority: RCW Authority: RCW 49.17.01049.17.010, , 49.17.04049.17.040, , 49.17.05049.17.050, , 49.17.44049.17.440, , 49.17.06049.17.060, and 29 C.F.R. 1926, Subpart CC., and 29 C.F.R. 1926, Subpart CC.
WSR 12-01-086, § 296-155-53408, filed 12/20/11, effective 2/1/12.]WSR 12-01-086, § 296-155-53408, filed 12/20/11, effective 2/1/12.]
WAC 296-155-53408: https://app.leg.wa.gov/wac/default.aspx?cite=296-155-53408
8 of 8 3/12/2026, 4:03 PM
Overhead Clearance Memorandum
Wang Short Plat (Renton)
April 3, 2026
Exhibit C
Overhead Clearance Figures (3 Total)
CM
CM
CM
CM
CM
CM
OH
P
OH
P
OH
P
OH
P
OH
P
OH
P
OH
P
OH
P
OH
P
OH
P
OH
P
OH
P
OVERHEAD POWER CLEARANCES
LIGHT POLE '1'
DATE:SHEET
OF
1
3
04/03/2026 WANG SHORT PLAT
RENTON, WASHINGTON
20.,5./A1D:A<68,TE00.,5./A1D:A033
PRELIMINARY - FOR DISCUSSION ONLY
0 10
VERTICAL SCALE IN FEET
HORIZONTAL SCALE IN FEET
0 10
OH
P
OH
P
OH
P
OH
P
OH
P
OH
P
OH
P
CM
CM
CM
CM
CM
CMOH
P
OH
P
OH
P
OH
P
OH
P
0 10
VERTICAL SCALE IN FEET
HORIZONTAL SCALE IN FEET
OVERHEAD POWER CLEARANCES
LIGHT POLE 'F'
DATE:SHEET
OF
2
3
04/03/2026 WANG SHORT PLAT
RENTON, WASHINGTON
20.,5./A1D:A<68,TE00.,5./A1D:A033
PRELIMINARY - FOR DISCUSSION ONLY
0 10
OH
P
OH
P
OH
P
OH
P
OH
P
OH
P
OH
P
OH
P
OH
P
OH
P
OH
P
OH
P
CM
CM
CM
CM
CM
CM
0 10
VERTICAL SCALE IN FEET
HORIZONTAL SCALE IN FEET
OVERHEAD POWER CLEARANCES
LIGHT POLE '2'
DATE:SHEET
OF
3
3
04/03/2026 WANG SHORT PLAT
RENTON, WASHINGTON
20.,5./A1D:A<68,TE00.,5./A1D:A033
PRELIMINARY - FOR DISCUSSION ONLY
0 10