HomeMy WebLinkAboutS-392703U)
LTJ
z_
Ld
J
Li
- -- MANHOLE FRAME AND COVER
6' SEE STD. PLAN 401
24"ADJUSTMENT RINGS (2" MIN.)
12" MAX. SEE NOTE 6
-f- I , .
MORTAR JOINT(S) (3/8" MIN.)
SEE NOTE 5
CONE (ECCENTRIC)
RUBBER GASKETED JOINTS IN
ACCORDANCE WITH ASTM C-443
STEPS - POLYPROPYLENE STEPS
6-1 �2" SHALL BE INCLUDED
7' IN.
.A,
CONCRETE RISER BY PIPE INC.,
P OR APPROVED EQUAL
12" (TYP) ; LADDER -POLYPROPYLENE
SHALL BE ATTACHED TO MANHOLE
MAX. PIPE SIZE - 'E'
CONCRETE SHELF
1%
a'
PRECAST BASE SECTION
OR CAST IN SHELF.
•NOT TO SCALE
.A, ,B, ,O, ,D, ,E,
48" MH 48 6" MIN. 5"MIN 24" MIN. 21" I.D.
54" MH 54" 8" MIN. 5.5" MIN. 24" MIN. 24" I.D.
60" MH 60" 1 8" MIN. 1 6" MIN. 42" MIN. 30" I.D.
NOTES:
1. STEPS TO BE POLYPROPYLENE SAFETY STEPS.
2. STEPS ARE To BE IN PLACE BEFORE MANHOLE SECTIONS ARE INSTALLED.
3. CASTING SHALL BE PER STD. PLAN 401.
4. MANHOLE SECTIONS TO BE OF REINFORCED PRECAST CONCRETE.
5. ALL JOINTS BETWEEN THE CONE, RISER RINGS, BRICKS AND CASTING SHALL BE GROUTED.
6. ADJUSTMENT OF THE CASTING TO GRADE SHALL BE ACCOMPLISHED WITH A COMBINATION OF
ADJUSTMENT RINGS, BRICKS AND MORTAR QJy" BRICKS SHALL BE STAGGERED TO CREATE A RUNNING
BOND OR 1/2 BOND. THE USE OF SHIMS IS PROHIBITED.
7. SANITARY SEWER MANHOLES SHALL HAVE ALL INTERIOR SURFACES, INCLUDING CHANNELING,
COATED (SEALED) WITH A HIGH SOLIDS URETHANE COATING; WASSER MC-AROSHIELD OR
APPROVED EQUAL; COLOR OF COATING SHALL BE WHITE.
8. RUBBER GASKETED JOINTS SHALL BE IN CONFORMANCE WITH ASTM C-443.
9. CHANNEL HEIGHT SHALL BE A MINIMUM OF 3/4 OF THE INSIDE DIAMETER OF THE LARGEST PIPE,
10. CONNECTIONS TO MANHOLE SHALL BE MADE USING GPK ADAPTOR, KOR-N-SEAL BOOTS OR
APPROVED EQUAL.
11. IN UNIMPROVED AREAS, MANHOLES SHALL EXTEND A MINIMUM OF 6" AND A MAXIMUM OF 12"
ABOVE FINISHED GRADE OR MUST HAVE A MINIMUM 2' DIAMETER CONCRETE RINGS POURED AT GRADE.
IN PAVED AREAS, COVER MUST SLOPE IN ALL DIRECTIONS TO MATCH PAVING.
0 o
PUBLIC WORKS
+ + STANDARD SANITARY MANHOLE BTO. PLAN -400.1
d DEPARTMENT
9 SEPTEMBER 2011
�----- EX. SEWER MAIN
PROPERTY UNE
_--SPOOL (LENGTH AS NEEDED)
8" SEWER SNBE _FUTURE _4'_SIDE SEWER
DC- -----_-_3
/ 2"x 4" STUD MARKING POST PAINTED
SEWER MAIN TEE X 8" TEE ( 8' CAP WHITE WITH THE WORD "SEWER" STENCILED
IN 3" NIGH BLACK LETTERS AND p8 WIRE
WRAPPED AROUND THE STUD AND
EXTENDED TO THE TOP OF THE STUD.
COUPLING (TYP.)
8"XONG" SURFACE CLEANOUT WITH CAST IRON RING AND COVER
I (EAST JORDAN IRON WORKS PRODUCT NO. 00387602 OR
APPROVED EQUAL, SPECIFY "SEWER' ON UD),
(SEE STD. PLAN 40.1 FOR INSTALLATION)
--- ' -
[� L -�-- - JM EAGLE THREADED CLEAN-OUT ADAPTER HUB
BEND AS PLUG (OR APPROVED EQUAL)
REQUIRED
EXISTING SANITARY _a
SEWER MAIN
FUTURE C SIDE SEWER
�8" SEWER STUB B"X8"XB' WYE FUTURE ON 4" REDUCER
SEWER MAIN SIZE X 8" TEE �
- - - 8rrrvrABi c �fiG±fi [il R�_�UR � aln SEW£R C N -.T16N¢ RO' EXIeTING-a�-,y�g ►LnLu.... A. VITRIFIED CLAY MAIN - CUT IN A NEW PVC 'TEE' USING "STRONG -BACK" FLEXIBLE COUPLINGS (FERNCO OR APPROVED EQUAL).
B. CONCRETE MAIN - CUT IN A NEW PVC "TEE" USING "STRONG -BACK" FLEXIBLE COUPLINGS (FERNCO OR APPROVED EQUAL).
C. PVC k 0900 PVC MAIN CUT IN NEW TEE USING RIGID COUPLINGS OR CORE -DRILLED WITH A ROMAC SADDLE
(OR APPROVED EQUAL):
D. DUCTILE IRON MAIN CORE -DRILLED WITH A ROMAC SADDLE (OR APPROVED EQUAL)
E. MANHOLE CONNECTION - ALL CONNECTIONS TO MANHOLES SHALL BE AT MANUFACTURED KNOCK -OUTS OR THE STRUCTURE
SHALL BE CORE -DRILLED.
3000 PSI MIXCONCR
BLOCKINGL5 �W1Xtr
� 5
8„ TIE HORIZONTAL
e" MW. MANNER ER 'SEWMAIN
CONCRETE AlOCKIN. ANGLE
OF TEE AT MAIN BETWEEN 25•.AND 45' TYPICAL SIDE SEWER
NOTE: UNLESS OTHERWISE SHOWN ON PLAN, SIDE SEWER SHALL HAVE A MINIMUM 2.5' COVER AT PROPERTY UNE OR 3-5'
LOWER THAN THE LOWEST HOUSE ELEVATION, WHICHEVER IS LOWER.
STANDARD SIDE SEWER STD. PLAN -406.1
PUBLIC WORKS Ar or
.,, ' DEPARTMENT INSTALLATION
(SEWER MAIN TO PROPERTY LINE) 1� LSA
..
Call 2 Working Days Before You Dig
811
Utilities Underground Location Center
(ID,MT,ND,OR,WA)
BOLTHOLES - 3 PLCS
bnL EQUALLY SPACED 120'
APART ON 23 1/16' (586mm)
DIA B.C. (SEE DETAIL)
reerreoo
RENT4
SEWER
r.,oE rw COVER BOTTOM VIEW
COVER & FRAME
PLAN VIEW
25' DIA,
1635mml 1r (3) BLT SOC. (ALLEN HEAD)
3/4, C25mm] 5/8'-11 X L5 SS
[19nm]r �RUBBER WASHER
8 3/4' L 2 1/2'
[222mm] [64nm]
TYP ILL
COVER SECTION VIEW
EON BOLTING DETAIL
26 1/2' DIA
[673mm]
25 1/4' DIA
I641mmI 1 1/16" 1/4'
1!41C6mm) DIA C6m
C27mm] [27mm]
NEOPRENE GASKET
1 [152nm] [3mm]
L - fi,
CR3
15 e']J 23 3/8[594 ]L OPEN GASKET GROOVE DETAIL
27 5/16' DIA
[694mml
34 1/8' DIA
1867mm3 NOTES:
FRAME SECTION VIEW 1. ALL COVERS SHALL 6E LOCKING LID PER EAST
JORDAN IRON WORKS INC. No. 3717C1 OR EQUAL.
2. USE FRAME AND COVER FOR STORM (SPECIFY
"DRAIN" ON COVER). SANITARY (SPECIFY
"SEWER"), OR WATER (SPECIFY "WATER"),
STD. PLAN - 401
PUBLIC WORKS
-(S
+ MANHOLE FRAME AND COVER
DEPARTMENT
F DECEMBER 2008
RECESSED
Not to Scale
LIFT POCKET
a 3/4" LETTERING "SEWER" 2,_0„
FRAME
DIAMETER
ALL WORK AND WORK MATERIAL SHALL BE IN CONFORMANCE WITH THE STANDARDS AND
N
SPECIFICATIONS OF THE CITY OF RENTON PLANNING/BUILDING/PUBLIC WORKS DEPARTMENT AND THE
0
SEWER
LATEST EDITION OF THE WSDOT/APWA STANDARDS AND SPECIFICATIONS, AS APPROVED AND MODIFIED
(2) BOLT SOC. (ALLEN HEAD)
11�)
BY 7HE CITY OF RENTON IN THE RENTON STANDARD PLANS & SPECIFICATIONS. A SET OF APPROVED
L= n
5/8" - 11 X 1.5 STAINLESS
STEEL
PLANS SHALL BE KEPT ON SITE AT ALL TIMES DURING CONSTRUCTION.
u
C a
REF PART �1009B1177
--•T-
1-3/18" 1
2.
THE HOURS OF WORK IN THE STREET RIGHT OF WAY SHALL BE PER CITY SPECIFICATIONS ON
0
8" CLASS "B"
WEEKDAYS UNLESS OTHERWISE APPROVED IN WRITING BY THE PLANNING/BUILDING/PUBLIC WORKS
SAND
10-1/2*ASPHALT
DEPARTMENT. AN APPROVED TRAFFIC CONTROL PLAN MUST BE OBTAINED PRIOR TO BEGINNING ANY
OR
EXPANDABLE
WORK WITHIN PUBLIC RIGHT OF WAY.
FOAM
1/4"
D
J.
ALL LOCATIONS OF EXISTING U77LITIES SHOWN ARE APPROXIMATE AND /T SHALL BE THE CONTRACTORS
7
RESPONSIBILITY TO VERIFY THE TRUE AND CORRECT LOCATION SO AS TO AVOID DAMAGE OR
2-1/4" BOLT DETAIL
DISTURBANCE.
45' (1/8) BEND
4.
A PRE -CONSTRUCTION CONFERENCE AND A 24 HOUR NOTICE SHALL BE REQUIRED PRIOR TO STARTING
14"
12-3 4
/
NEW CONSTRUCTION. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SECURE ALL NECESSARY
PERMITS PRIOR TO STARTING CONSTRUCTION. (INSPECTION WILL BE ACCOMPLISHED BY A
REPRESENTA77VE OF THE CITY OF RENTON.) IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO
NOTIFY THE PUBLIC WORKS INSPECTOR 24 HOURS IN ADVANCE OF BACKFILLING ALL CONSTRUCTION.
-1O
CONTRACTOR IS SOLELY RESPONSIBLE FOR THE MEANS, METHODS AND SEQUENCES OF CONSTRUCTION
1 t °
y\ti�
12-1/44
AND FOR THE SAFETY OF WORKERS AND OTHERS ON THE CONSTRUCTION SITE. _
OJ
CAST IRON RING AND COVER
PIPE MATERIAL As SPECIFIED
BY THE ENGINEER
��- 45• (1/8) BEND
IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO OBTAIN STREET USE AND ANY OTHER
NOTES:
1. la^ AND 6" CLEAN-OUT RINGS AND COVERS ON SEWER MAINS SHALL BE EAST JORDAN IRON WORKS, INC.
No. 3698 (PRODUCT NO. 00359803) OR APPROVED EQUAL CLEAN OUT SHALL BE A WATER TIGHT ASSEMBLY.
2. IN UNIMPROVED AREAS, POUR A 1'-0" THICK, 2`-0" SQUARE
RELATED PERMITS PRIOR TO ANY CONSTRUC77ON
CONCRETE, CLASS 3000, PAD AROUND THE RING AND COVER.
r-
...... .
STD. PLAN - 403.1
PUBUC WORKS
n LL
8 OR 6 CLEANOUT
O
DEPARTMENT
FOR SANITARY SEWER MAIN
�
a
0
8.
SANITARY SEWER NOTES AND SPECIFICATIONS:
1.
ALL WORK AND WORK MATERIAL SHALL BE IN CONFORMANCE WITH THE STANDARDS AND
N
SPECIFICATIONS OF THE CITY OF RENTON PLANNING/BUILDING/PUBLIC WORKS DEPARTMENT AND THE
0
LATEST EDITION OF THE WSDOT/APWA STANDARDS AND SPECIFICATIONS, AS APPROVED AND MODIFIED
11�)
BY 7HE CITY OF RENTON IN THE RENTON STANDARD PLANS & SPECIFICATIONS. A SET OF APPROVED
PLANS SHALL BE KEPT ON SITE AT ALL TIMES DURING CONSTRUCTION.
C)
2.
THE HOURS OF WORK IN THE STREET RIGHT OF WAY SHALL BE PER CITY SPECIFICATIONS ON
0
WEEKDAYS UNLESS OTHERWISE APPROVED IN WRITING BY THE PLANNING/BUILDING/PUBLIC WORKS
DEPARTMENT. AN APPROVED TRAFFIC CONTROL PLAN MUST BE OBTAINED PRIOR TO BEGINNING ANY
WORK WITHIN PUBLIC RIGHT OF WAY.
D
J.
ALL LOCATIONS OF EXISTING U77LITIES SHOWN ARE APPROXIMATE AND /T SHALL BE THE CONTRACTORS
RESPONSIBILITY TO VERIFY THE TRUE AND CORRECT LOCATION SO AS TO AVOID DAMAGE OR
DISTURBANCE.
4.
A PRE -CONSTRUCTION CONFERENCE AND A 24 HOUR NOTICE SHALL BE REQUIRED PRIOR TO STARTING
NEW CONSTRUCTION. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SECURE ALL NECESSARY
PERMITS PRIOR TO STARTING CONSTRUCTION. (INSPECTION WILL BE ACCOMPLISHED BY A
REPRESENTA77VE OF THE CITY OF RENTON.) IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO
NOTIFY THE PUBLIC WORKS INSPECTOR 24 HOURS IN ADVANCE OF BACKFILLING ALL CONSTRUCTION.
5.
CONTRACTOR IS SOLELY RESPONSIBLE FOR THE MEANS, METHODS AND SEQUENCES OF CONSTRUCTION
AND FOR THE SAFETY OF WORKERS AND OTHERS ON THE CONSTRUCTION SITE. _
6.
IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO OBTAIN STREET USE AND ANY OTHER
RELATED PERMITS PRIOR TO ANY CONSTRUC77ON
r-
7.
PLANS APPROVED BY THE CITY OF RENTON, PUBLIC WORKS DEPARTMENT SHALL TAKE PRECEDENCE
O
OVER ALL OTHER PLANS
0
8.
A COPY OF THESE APPROVED PLANS MUST BE ON THE JOB SITE WHENEVER CONSTRUCTION lS IN
0
PROGRESS
9.
THE CONTRACTOR SHALL PROVIDE THE CITY OF RENTON WITH AN AS -BUILT DRAWING OF THE
SANITARY SEWER SYSTEM, WHICH HAS BEEN STAMPED AND SIGNED BY A LICENSED PROFESSIONAL
A
ENGINEER OR LICENSED PROFESSIONAL SURVEYOR.
10.
BACKFILL SHALL BE PLACED EQUALLY ON BOTH SIDES OF THE PIPE IN LAYERS WITH A LOOSE
D
AVERAGE DEPTH OF 6 INCHES, MAXIMUM DEPTV OF 8 INCHES, THOROUGHLY TAMPING EACH LAYER TO
J
95 PERCENT OF MAXIMUM DENSITY. THESE COMPACTED LAYERS MUST EXTEND FOR ONE PIPE DIAMETER
ON EACH SIDE OF THE PIPE OR TO THE SIDE OF THE TRENCH. MATERIALS TO COMPLETE THE FILL
OVER PIPE SHALL BE THE SAME AS DESCRIBED.
11.
OPEN CUT ROAD CROSSINGS FOR UTILITY TRENCHES ON EXISTING TRAVELED ROADWAY SHALL BE
BACKFILLED WITH CRUSHED ROCK AND MECHANICALLY COMPACTED UNLESS OTHERWISE APPROVED BY
THE CITY OF REN TON.
12.
DATUM FOR VERTICAL CONTROL SHALL BE NORTH AMERICAN VER77CAL DATUM 1988 METERS, AND FOR
HORIZONTAL CONTROL SHALL BE NORTH AMERICAN DATUM 1983/1991 METERS UNLESS OTHERWISE
APPROVED BY THE CITY OF RENTON PUBLIC WORKS DEPARTMENT. REFERENCE BENCHMARK AND
ELEVATIONS ARE NOTED ON THE PLANS.
13. ALL DISTURBED AREAS SHALL BE SEEDED AND MULCHED OR OTHERWISE STABILIZED TO THE
SATISFACTION OF THE DEPARTMENT FOR THE PREVENTION OF ON-SITE EROSION AFTER THE
COMPLETION OF CONSTRUCTION.
14. ALL PIPE AND APPURTENANCES SHALL BE LAID ON A PROPERLY PREPARED FOUNDATION IN
ACCORDANCE WITH THE STANDARDS AND SPECIFICATIONS OF THE CITY OF RENTON
Grout adjusting rings inside, outside Manhole Frame and Cover PLANNING/BUILDING/PUBLIC WORKS DEPARTMENT AND THE LATEST ED/TION OF THE WSDOT/APWA
and between. Grout under casting. per the Standard Detail. STANDARDS AND SPECIFICATIONS, AS APPROVED AND MODIFIED BY 774E CITY OF RENTON IN THE
Locate as shown on plan: RENTON STANDARD PLANS & SPECIFICATIONS. THIS SHALL INCLUDE NECESSARY LEVEL/NG OF THE
a I cc ;.r; Minimum requirement TRENCH BOTTOM OR THE TOP OF THE FOUNDA77ON MATERIAL, AS WELL AS PLACEMENT AND
(D c c E E COMPACTION OF REQUIRED BEDDING MATERIAL, TO UNIFORM GRADE SO THAT THE ENTIRE LENGTH OF
y _ for adjustment shall be
E E " e THE PIPE WILL BE SUPPORTED ON A UNIFORMLY DENSE, UNYIELDING BASE. PIPE BEDDING SHALL BE
" a N (2) - 4 rings.
00 PEA GRAVEL 6 INCHES ABOVE AND BELOW THE PIPE.
Eccentric cone.
Mortar
15. SANITARY SEWER PIPE SHALL BE POLYVINYL CHLORIDE (PVC) RUBBER GASKETED ASTM D 3034, SDR
• N 35, OR DUCTILE IRON CLASS 50, UNLESS OTHERWISE APPROVED BY THE WASTEWATER UTILITY.
`• 16. IN UNIMPROVED AREAS, MANHOLE TO EXTEND MINIMUM 6 INCHES AND MAXIMUM 12 INCHES ABOVE
1' section below cone FIN/SHED GRADE OR MUST HAVE M1N/MUM 2' DIAMETER CONCRETE RING POURED AT GRADE. IN PAVED
''' 5"48' is required. AREA, COVER MUST SLOPE IN ALL DIREC77ONS TO MATCH PAVING
c
E Copolymer Polypropylene {# ,-
0o Plastic Steps & Ladder.
U, per the Standard Detail.
.LD Locate as shown s
g on plan view below. Confined 0 -ring rubber
gasket joints and butyl
Provide grout at knock -out. .`' sealant strips (typ.)
Provide sand collar for PVC '
Pipe a
CL
M slope 3/8"/ft Tr
� f
Poured in place Class 4000
cement concrete base. ,� t :.r�' �.Lr. L y•c :'
Kor-n-Seal boot by Pea gravel bedding per
NPC, Inc:, or approve �ELEVATION the Specifications.
equal. Foundation gravel per the
. • N Specifications, if required.
Notes:
' . 1. Marker posts may be required in
Izoweasements.
:.. -3927-03
{ APPROVED FOR CONSTRUCTION
_ .. J'�
Manhole steps.
SUBJECT TO ERRORS AND OMISSIONS
Frame and cover.
PLAN
BY: DATE:
SADDLE MANHOLE
NOT To SOME
BY: DATE: