HomeMy WebLinkAboutCA_2021_WSEC-R_Single_Family_Work_Sheet 241204_V12021 Washington State Energy Code – Residential
Prescriptive Energy Code Compliance for All Climate Zones in Washington
Single Family – New & Additions (effective March 15, 2024)
These requirements apply to all the IRC building types, including detached one- and two-family
dwellings and multiple single-family dwellings (townhouses).
Instructions: This single-family project uses the requirements of the Prescriptive Path below to incorporate
the minimum values listed. Based on the conditioned floor area of the structure, the number of required
additional credits must be selected by the permit applicant.
Fenestration Requirements by Component, Table R406.2 - Fuel Normalization Credits and R406.3 Energy Credits.
Authorized Representative
Signature Date
Permit#
Address or Lot & Block
City Zip
All Climate Zones Table 402.1.3
R-Value a U-Factor a
a
R-values are minimums. U-factors and SHGC are maximums. When insulation is installed in a cavity which is less than the label or design
thickness of the insulation, the compressed R-value of the insulation from Appendix Table A101.4 shall not be less than the R-value specified
in the table
b The fenestration U-factor column excludes skylights.
c
"10/15/21 +5TB" means R-10 continuous insulation on the exterior of the wall, or R-15 continuous insulation on the interior of the wall, or R-
21 cavity insulation plus a thermal break between the slab and the basement wall at the interior of the basement wall. "10/15/21 +5TB" shall
be permitted to be met with R-13 cavity insulation on the interior of the basement wall plus R-5 continuous insulation on the interior or
exterior of the wall. "5TB" means R-5 thermal break between floor slab and basement wall.
d R-10 continuous insulation is required under heated slab on grade floors. See Section R402.2.9.1.
e For single rafter- or joist-vaulted ceilings, the insulation may be reduced to R-38 if the full insulation depth extends over the top plate of the
exterior wall.
f
R-7.5 continuous insulation installed over an existing slab is deemed to be equivalent to the required perimeter slab insulation when applied
to existing slabs complying with Section R503.1.1. If foam plastic is used, it shall meet the requirements for thermal barriers protecting foam
plastics.
g For log structures developed in compliance with Standard ICC 400, log walls shall meet the requirements for climate zone 5 of ICC 400.
h Int. (intermediate framing) denotes framing and insulation as described in Section A103.2.2 including standard framing 16 inches on center,
78 percent of the wall cavity insulated and headers insulated with a minimum of R-10 insulation.
i The first value is cavity insulation, the second value is continuous insulation. Therefore, as an example, “R13+10” means R-13 cavity
insulation plus R-10 continuous insulation
j
A maximum U-factor of 0.32 shall apply to vertical fenestration products installed in buildings located above 4000 feet in elevation above sea
level, or in windborne debris regions where protection of openings is required under Section R301.2.1.2 of the International Residential
Code.
Provide all information from the following tables in building permit drawings: Table R402.1.2 - Insulation and
Fenestration U-Factor b, j n/a 0.30
Ceiling e 60 0.24
Skylight U-Factor b n/a 0.50
Floor U-Factor 30 0.029
Above-Grade Wall U-Factor g,i 20+5 or 13+10 0.056
Below Grade Wall U-Factor c,h 10/15/21 int + 5TB 0.035
Slab d,f On Grade F-Factor 10, 4 ft 0.54
Prescriptive Path – Single Family WSEC-R 2021 Edition (V10/24/2024) 1
and Table R402.1.2
2021 Washington State Energy Code – Residential
Prescriptive Energy Code Compliance for All Climate Zones in Washington
Single Family – New & Additions (effective March 15, 2024)
maximum tested building air leakage, and show the qualifying ventilation system and its control sequence
of operation.
1. Small Dwelling Unit: ........................................................................................... 5.0 credits
Dwelling units less than 1500 square feet in conditioned floor area with less than 300 square feet of
fenestration area. Additions to existing building greater than 500 square feet of heated floor area but less
than 1500 square feet.
2. Medium Dwelling Unit: ...................................................................................... 8.0 credits
All dwelling units that are not included in #1, #3 or #4.
3. Large Dwelling Unit: ..........................................................................................9.0 credits
Dwelling units exceeding 5000 square feet of conditioned floor area.
4. Dwelling units serving Group R-2 occupancies: ................................................ 6.5 credits
5. Additions 150 square feet to 500 square feet: ..................................................... 2.0 credits
The drawings included with the building permit application shall identify which options have been selected and the
point value of each option, regardless of whether separate mechanical, plumbing, electrical, or other permits are
utilized for the project
Table R406.2 ENERGY EQUALIZATION CREDITS
Description of Primary Heating Source
Credits -
select ONE
1 For combustion heating equipment meeting minimum federal efficiency standards for the
equipment listed in Table C403.3.2(5) or C403.3.2(6) 0 ☐
2
For an initial heating system using a heat pump that meets federal standards for the equipment
listed in Table C403.3.2(2) and supplemental heating provided by electric resistance or a
combustion furnace meeting minimum standards listed in Table C403.3.2(5)b found in the 2021
WSEC- COMMERCIAL ENERGY CODE
1.5 ☐
3 For heating system based on electric resistance only (either forced air or Zonal) 0.5 ☐
4c
For heating system using a heat pump that meets federal standards for the equipment listed in
Table C403.3.2(2) or C403.3.2(9) or Air to water heat pump units that are configured to provide
both heating and cooling and are rated in accordance with AHRI 550/590
3.0 ☐
5
For heating system based on electric resistance with:
1. Inverter-driven ductless mini-split heat pump system installed in the largest zone in the
dwelling,
or
2. With 2kW or less total installed heating capacity per dwelling
2.0 ☐
a. See Section R401.1 and residential building in Section R202 for Group R-2 scope.
b. The gas back-up furnace will operate as fan-only when the heat pump is operating. The heat pump shall operate at
all temperatures above 38°F (3.3°C) (or lower). Below that “changeover” temperature, the heat pump would not
operate to provide space heating. The gas furnace provides heating below 38°F (3.3°C) (or lower).
c. Additional points for the HVAC system are included in Table R406.3.
System
Type type
system
Prescriptive Path – Single Family WSEC-R 2021 Edition (V10/24/2024) 2
Each dwelling unit in a residential building shall comply with sufficient options from Table R406.2 (Energy
Equalization credits) and Table 406.3 (energy credits) to achieve the minimum number of credits from the list
below. To claim credits, the building permit drawings shall specify the option selected and the
Section R401.1 and Residential Building Section R202 for Group R-2.
Before selecting your credits on this Summary table, review the option descriptions in Table R406.3 (Single Family).
2021 Washington State Energy Code – Residential
Prescriptive Energy Code Compliance for All Climate Zones in Washington
Single Family – New & Additions (effective March 15, 2024)
Summary of Table R406.3
Energy Credit Option Descriptions
Credits –
limited to one
energy option
from each
category d
Comments:
1.1 Efficient Building Envelope 0.5 ☐
1.2 Efficient Building Envelope 1.0 ☐
1.3 Efficient Building Envelope 1.5 ☐
2.1 Air Leakage Control and Efficient Ventilation 1.0 ☐
2.2 Air Leakage Control and Efficient Ventilation 1.5 ☐
2.3 Air Leakage Control and Efficient Ventilation 2.0 ☐
3.5d High Efficiency HVAC 1.5 ☐
3.7a,d,e High Efficiency HVAC 2.0 ☐
4.1 High Efficiency HVAC Distribution System 0.5 ☐
5.2 Efficient Water Heating 0.5 ☐
5.3 Efficient Water Heating 0.5 ☐
5.4 Efficient Water Heating 1.0 ☐
5.5 Efficient Water Heating 1.5 ☐
5.8 Efficient Water Heating 2.5 ☐
7.1 Appliance Package 0.5 ☐
a. An alternative heating source sized at a maximum of 0.5 Watts/ft2 (equivalent) of heated floor area or 500 Watts, whichever is bigger, may be
installed in the dwelling unit.
b. See Section R401.1 and residential building in Section R202 for Group R-2 scope.
system. Variable capacity heat pumps are ineligible from claiming this option.
e. Primary living areas include living, dining, kitchen, family rooms, and similar areas.
in Section R403.7 with increased capacity to provide a minimum of 75 percent of peak hot water demand or shall be sized in accordance with
approved manufacturer's specifications or guidance. Supplementary heat for water heating system shall be in accordance with Section R403.5.7.
Total Credits
1.4 Efficient Building Envelope 2.5 ☐
Renewable Electric Energy (4.5 credits max) 0.5-4.5
Options
6.1
5.1 Efficient Water Heating 0.5 ☐
3.6a High Efficiency HVAC 1.0 ☐
3.9 High Efficiency HVAC 1.5 ☐
5.7 Efficient Water Heating 2.5 ☐
5.6 Efficient Water Heating 2.0 ☐
3.3a,c,d High Efficiency HVAC 0.5 ☐
3.2 a High Efficiency HVAC 0.5 ☐
3.10f High Efficiency HVAC 2.5
3.4a,d High Efficiency HVAC 1.5 ☐
3.8a,d High Efficiency HVAC 1.0
3.1a High Efficiency HVAC 1.0 ☐
3.11c High Efficiency HVAC 0.5
c. Option 3.11 can only be taken with Options 3.1 and 3.3. To qualify to claim Option 3.11 with 3.3, the system shall be a 1-2 speed heat pump
f. Option 3.10 may only be taken with Efficient Water Heating Options 5.1 or 5.2. Equipment sizing for space heating shall be calculated as provided
Prescriptive Path – Single Family WSEC-R 2021 Edition (V10/24/2024) 3
d. This option may only be claimed if serving System Type 4 from Table R406.2.