HomeMy WebLinkAboutS-391005EXISTING WATER LINE
TESTING DETAIL
±8 FT
c
PLAN VIEW
WATER LINE
VERTICAL CROSS(MJxFL) FOR POLYPIGGING
ONE BLIN➢ FLANGE ON TDP WITH 27AP & 2'PLUG
ONE BLIND FLANGE ON BOTTOM
ONE <MJ) PLUG WITH 2' TAP & 2' TEMPORARY BLOW -OFF
TEMPORARY BLOCK
CUT -IN (BY CITY FORCES)
TEE (FLxFL) W/ CONC. BLOCK
3- GATE VALVES (FLxM_D
2- SOLID SLEEVES (MJ) OR RD-MAC CDUPLINGS
1- PLUG (MJ) W/2'TAP & TEMP. BLDW-OFF
TEMP. BLOCK
TER LINE
EXISTING WATER LINE
FINAL CONNECTION DETAIL
AFTER ALL TESTING, CLEANING BY POLYPIG, AND DISINFECTION,
REMOVE TEMP. BLOCK & BLOW -OFF & CONNECT
WITH SLEEVE <MJ) & D.I. SPOOLS
FINAL CONNECTION BY CITY FORCES
EXISTING WATER LINE
am Soo
+ + PUBLIC WORKS CONNECTION TO WATER MAINPLAN -'4
DEPARTMENT CUT IN -LINE TEE & THREE VALVES
MARCH 2O10
A A
PLAN VIEW f{♦1
WATER J
VALVE BOX LID WITH
EARS IN DIRECTION OF
'' SQUARE
L
WATER MAIN AND WORD
OPERATING NUT
"WATER" CAST INTO IT
112' MIN,
-
18" MAX,
4" CONCRETE COLLAR FOR
VALVES IN PAVED AREAS
4-1/4" DIA.
12,
1/8" MIN. THICKNESS
SEE DETAIL
2 PIECE CAST IRON VALVE
BOX, RICH-SEATTLE TYPE
OR OLYMPIC FOUNDRY
1" STEEL
LENGTH AS REQUIRED
�+J
1 /8" MIN. THICKNESS
//
2-1/4" INSIDE MEASUREMENT
2-1/4" DEPTH
SECTION A -A
VALVE OPERATING NUT
EXTENSION .
VALVE OPERATION NUT EXTENSION NOTE:
EXTENSIONS ARE REQUIRED WHEN VALVE NUT
IS MORE THAN THREE (3) FEET BELOW
FINISHED GRADE. EXTENSIONS ARE TO BE A
MINIMUM OF ONE (1) FOOT LONG. ONLY ONE
EXTENSION TO BE USED PER VALVE.
NOTE: ALL EXTENSIONS ARE TO BE MADE
OF STEEL, SIZED AS NOTED, AND PAINTED
WITH TWO COATS OF METAL PAINT.
VALVE MARKER NOTES:
VALVE MARKERS SHALL BE EQUAL
TO CARSONITE UTILITY MARKER
VALVE MARKER POST TO BE USED FOR ALL
MAIN LINE VALVES OUTSIDE PAVED AREAS
38"
62"
- 24„
VALVE MARKER POST
WHITE POSTI
PUBLIC WORKS VALVE BOX, MARKER &OPERATING SM. PLAN - 330.1
+ + DEPARTMENT NUT EXTENSION
MARCH 2O10
FIRE HYDRANT SHALL BE COREY-TYPE EQUAL TO IOWA F-5110 OR
COMPRESSION TYPE SUCH AS CLOW MEDALLION; M & H 929, MUELLER
SUPER CENTURION 200, AND WATEROUS PACER WITH 6" MECHANICAL
JOINT INLET WITH LUGS. 5-1/4' MAIN VALVE OPENING. TWO 2-1/2'
HOSE CONNECTIONS NATIONAL STANDARD THREADS. 4- PUMPER
CONNECTION CITY OF SEATTLE THREADS WITH A STORZ ADAPTOR,
4.875" SEATTLE THREAD X 5' STORZ, ATTACHED WITH 1/8" STAINLESS
STEEL CABLE. 1-1/4' PENTAGON OPERATING NUT. FIRE HYDRANT TO
BE PAINTED WITH TWO COATS OF PAINT. KELLY-MOORE/PRESERVATIVE
PAINT No- 5780-563 DTM ACRYLIC GLOSS, SAFETY YELLOW OR
APPROVED EQUAL PUMPER CONNECTION TO FACE ROADWAY OR AS
DIRECTED BY RENTON FIRE DEPARTMENT. FIRE HYDRANT EXTENSION TO
BE USED IF REQUIRED.
MIN, 18" TO 20" BEHIND BACK OF
CURB OR 12' BEHIND BACK OF
3' SIDEWALK THAT IS ADJACENT TO
CURB
4.875" x 5" STORZ
5'x5'x6" THICK CONCRETE PAD AROUND
HYDRANT. FINISH TO MATCH SIDEWALK.
en EXPANSION JOINT AT
BACK OF SIDEWALK
2 �CONCRETE SIDEWALK
OR PLANTING STRIP
36" MIN
COVER
13'x24' PLASTIC METER BOX EQUAL TO MID -STATES PLASTIC,
INC. BCF SERIES MSBCF 1324-18 WITH 1.75" THICK DUCTILE
IRON DIAMOND PLATE COVER EQUAL TO MID -STATES PLASTICS,
INC. NSCBC-1324-R WITH READER LID AND 2" DRILLED HOLE
FOR TOUCHREAD PIT LID (SEE DETAIL A -A)
9' MIN
12" MAX
FINISH GRADE
Z¢O
<uj
• - o
35" MIN COVER w n U
CITY
PRIVATE
PIPING
PIPING
J I
IN UNIMPROVED RIGHT OF J
✓_
WAY INSTALL METER BOX AT
� -
PROPERTY LINE NTH 12'
w•
LONG COPPER TAILPIECE. w,
a(
SIDEWALK a
I
TOUCHREAD WATER
METER TO BE
12"
SUPPLIED BY THE
a
CITY
TYPE *KSOFT
"TUBI
�>
COPPER G
1, F30
22-1/2'
TWO-PIECE CAST IRON VALVE BOX WITH LUG
TYPE COVER. EQUAL TO OLYMPIC FOUNDRY CO. NEW DUCTILE
STANDARD 8" TOP SECTION WITH REGULAR BASE IRON
SECTION LENGTH TO FIT. VALVE NUT EXTENSION ZI
WATERMAIN
AS REQUIRED. IF SERVICE LINE TO HOUSE IS 3/4- OR 1"
TO BE INSTALLED IN THE FUTURE GALVANIZED
RAISED PAVEMENT MARKER TYPE 88-A INSTALL FORD C14-33 OR 44 FIPT PLUG
STIMSONITE TWO-WAY BLUE REFLECTIVE x COMPRESSION COUPLING
LOOP DOWN TO CENTERLINE
OF WATER MAIN TO
PROVIDE SLACK IN COPPER COPPERSETTER FOR 5/8%3/4" METER: FORD
CONCRETE BLOCKING SERVICE LINE TO METER. VBH72-15W-44-33G OR McDONALD BRASS' 21-215WC0033 OR
CONCRETE is `. ".'• `,.'y,
THRUST BLOCK
MAIN LINE TEE. WITH 6" FLANGE SIDE OUTLET.
6" GATE VALVE (FL X MJ) AWWA C-509, RESILIENT SEAT
6" DUCTILE IRON PIPE, CLASS 52 CEMENT LINED, LENGTH TO FIT
2-3/4" COR-TEN STEEL TIE RODS.
16" x 8" x 4" MINIMUM 1/2 YARD OF 1-1/4" WASHED DRAIN ROCK
CONCRETE BEARING V ABOVE BOOT FLANGE. PLACE 8 MIL
BLOCK UNDER HYDRANT POLYETHYLENE FILM AROUND TOP AND SIDES OF
GRAVEL.
FIRE HYDRANT ASSEMBLY
I LEVEL ALL GROUND
LEVEL ALL GROUND
MMIN 3' RADIUS
IN 3' RADIUS
1
06
6" CONCRETE PAD
im
ONE MAN ROCK
1
6
CONCRETE PAD
CUT FI LL
HYDRANT LOCATION IN CUT OR FILL
SM
+ + PUBLIC WORKS FIRE HYDRANT ASSEMBLY• PLAN - 910.1
DEPARTMENT
MARCH 2O10
11-1/4• BEND
CAP
Y
22-1/2' BEND 45• BEND
90' BEND
THRUST BLOCK BEARINC AREA IN SQUARE FEET (SEE NOTES) FOR HORIZONTAL AND DOWNWARD VERTICAL BENDS
SOIL
FIRM SILT OR
FIRM SILTY SAND
COMPACT SAND
COMPACT SAND & GRAVEL
90'
45' BEND
11 1/4'
9D'
45-BEND
11 1/4'
90'
45- BEND
11 1/V
FITTING
BEND
TEE
CAP OR PLUG
& 22 1/2'
BEND
TEE
CAP OR PLUG
& 22 1/2'
BEND
TEE
CAP OR PLUG
& 22 1/2'
BEND
BEND
BEND
4'
7.0
4.2
4.2
1.7
2.9
2.1
2.1
1. 1)
22
1.6
1.6
1.0
6
13.3
9.4
9.4
3.8
6.7
4.7
4.7
1.9
5.0
3.5
3.5
1.4
8'
23.3
16.7
16.7
6.7
11.7
8.4
8.4
3.4
8.8
6.3
6.3
2.5
12'
53.0
37.51
37.5
15.0
26.5
10.0
18.8
7.5
211
14.0
5.6
AREAS CALCULATED ON 300 PSI TEST PRESSURE. S-O" MIN. COVER FOR WATERMAIN LESS THAN 12".
4'-0" MIN. COVER FOR WATERMAIN 12" OR GREATER.
MAX. HEIGHT OF THRUST BLOCK (FT) a 0.5 x DEPTH OF TRENCH
MIN. HEIGHT OF THRUST BLOCK (FT) = 0.0. PIPE + 1.0'
REA BLOCK BEARING
REFERS TO THE
Ila
ICE OF BLOCK MEASURED
IN SgUARE FEET
NOTES:
1. LOCATION AND SIZE OF BLOCKING FOR PIPE LARGER THAN 12"DIAMETER AND FOR SOIL TYPES
DIFFERENT THAN SHOWN SHALL BE DETERMINED BY THE ENCINEER.
2. ALL BLOCKING SHALL BE POURED IN PLACE AGAINST UNDISTURBED NATIVE GROUND.
3. ALL POURED THRUST BLOCKS SHALL BE 13ACKFILLED AFTER MIN. 1 DAY. PRESSURE TESTING
SMALL OCCUR AFTER CONCRETE HAS REACHED NOMINAL COMPRESSIVE STRENGTH.
4. ALL BLOCKING SHALL BE CONCRETE CL 5
S. BLOCKINC AGAINST FITTINCS SHALL BEAR ACAINST THE GREATEST FITTINC SURFACE AREA
POSSIBLE. BUT SHALL NOT COVER OR ENCLOSE BELL ENDS. JOINT BOLTS OR GLANDS
REASONABLE ACCESS TO BOLTS AND GLANDS SHALL BE PROVIDED.
CONCRETE BLOCKING FOR STD. PLAN - 380.2
+ + PUBLIC WORKS HORIZONTAL AND DOWNWARD
DEPARTMENT VERTICAL BENDS MARCH 2O10
QN M . HC
13 ASy�
,p 41823 0
I;0F LTE 10
"7
MUELLER: 3/4-8-2470-2 WITH ANGLE BALL VALVE ON INLET AND
SINGLE CHECK VALVE ON OUTLET
CORPORATION STOP WITH BALL VALVE. FORD COPPERSETTER FOR 1" METER: FORD VBH72-15W-44-44G, OR
TAPERED THREAD (CC). QUICK JOINT McDONALD BRASS: 21-415WC0044, OR MUELLER: 1-B-2470-2
(3/4" FB1000-3-0) OR AY MCDONALD 4701E BOTH INLET AND OUTLET WITH QUICK JOINT. PADLOCK WINGS ON
(1" F81000-4-Q) OR AY MCDONAL❑ 47018 INLET ANGLE BALL VALVE AND SINGLE CHECK VALVE ON OUTLET.
ALL FITTINGS SHALL BE WITH QUICK JOINT.
NOTE:
ALL METER BOXES INSTALLED WITHIN CONCRETE OR PAVED DRIVEWAYS SHALL BE
CAST-IRON EQUAL TO OLYMPIC FOUNDARY. EXPANSION JOINTS MUSH BE INSTALLED ON
BOTH SIDES OF METER BOX.
A- A DRILL 2" DIA. HOLE FOR AMR (AUTOMATIC
METER READ) TOUCHREAD DEVICE
L _ 2-1/2" MIN. FROM NEAREST
r AND FRONT EDGE OF PIT LID
I
TYPICAL
RIB
I
NOTE:
THE CENTER OF THE HOLE MUST BE AT LEAST 1" FROM
UNDERNEATH RIBS UNLESS THE RIB SPACING ALLOWS THE
NUT TO TICHTEN AGAINST THE OPEN SIDE OF MORE THAN
ONE RIB.
+ + PUBLIC WORKS %" AND 1" WATER SERVICE SM. PLAN - 9E0.1
DEPARTMENT
NOVEMBER 2009
WATER MAIN
2" CLOSE NIPPLE
2" 90' ELBOW -
CONCRETE BLOCKING
CITY REVIEW COMMENTS
CITY REVIEW COMMENTS
REVISION
IF ADDITIONAL ADJUSTMENT IS
REQUIRED, INSTALL 2-2" CLOSE
NIPPLE AND 2-2" 90- BEND, SCREWED
AT THIS POINT. FIELD LOCATE PLASTIC METER BOX IN
PLANTER OR CAST IRON BOX IN PAVED
OR CONCRETE AREAS.
2" CLOSE NIPPLE
�_4_�2" 90' ELBOW
2" GALVANIZED PIPE AS REQUIRED
PLAN
VALVE NUT EXTENSION AS REQUIRED
TWO PIECE CAST IRON VALVE (SEE DWG BR46 / PAGE B090)
EQUAL TO OLYMPIC FOUNDRY CO. GROUND LINE CONCRETE SIDEWALK
STANDARD 8" TOP SECTION, -+-� 6" MAX.�--
WITH REGULAR BASE SECTION
LENGTH TO FIT.
2" RESILIENT SEATED
GATE VALVE, SCREWED
2" GALVANIZED
PIPE 12" LONG
2" CLOSE NIPPLE
BETWEEN CAP OR PLUG
AND 2" 90' ELBOW
d 0 " b
��.0p o, O' _600.
INSTAL 4 MIL POLYETHYLENE
MAX. aon°o,dao° ooQo
O G' o
PLASTIC COVER OVER WASHED
GRAVEL. CUT HOLE FOR PIPE
O o�boti139
Go$OD.q-oo
10 CU. FT. WASHED GRAVEL
PASSING
1-1/2" AND RETAINED ON
1/4" MESH
FOR DRAIN
ELEVATION
+ + PUBLIC WORKS
DEPARTMENT
2" BLOW -OFF
PERMANENT ASSEMBLY
® © A
2 1/2" NST (HOSE)
AND 2 1/2" FNST
CAP WITH GASKET
2"x2%2" TEE AND 2" CAP
2" CLOSE NIPPLE BEWTEEN TEE
AND 90' ELBOW.
2" 90' ELBOW
1 0=200
ONE Pm
R FULL 90M,E
IF NOT ONE R M
SCALE ACCORDIMMY
STD. PLAN - 340.1
MARCH 2O10
NORMONGILL WO 111Y13�%1901
DATUM
j2" OPEN PATTERN, RETURN BEND - 180'
2" BEEHIVE STRAINER J 2" GALVANIZED IRON PIPE FIELD
/ LOCATE
GUT OPENING AS REQUIRED,
AFTER INSTALLATION, GROUT 17"x30" PLASTIC METER BOX EQUAL TO MID STATES
AROUND PIPE. 6" MAX. PLASTIC, BCF SERIES 1730-18 WITH 2" THICK DUCTILE
IRON DIAMOND PLATE. 18'X31" MSCBC 173OR
1" CLOSE NIPPLE
1 1" UNION 1" BRONZE GATE VALVE, SCREW EQUAL
1" NIPPLE TO RED -WHITE VALVE CORP. FIG NO.280
1" UNION
INSTALLrs. COUPLING COPPER TO MALE IRON
1" REDUCER PIPE -FORD C28-44 OR EQUAL.
2 - 2" 90' BENDS AS 2' RESILIENT SEAT GATE VALVE
SWING JOINT WITH THREADED ENDS
I.
2" BRASS NIPPLE - 6" LONG
° (MIPT X MIPT)
12" MIN. e o o° v o00paa ° �i- 2" IRON PIPE THREAD CORPORATION STOP WITH
I go o Oo c.va 90' BEND FOR COPPER. FORD TYPE F1000 PACK
JOINT CTS.
1" GALVANIZED IRON
PIPE TO FIT
1" 90' ELBOW OOUDLE STRAP SERVICE CLAMP WITH
2" IPS TAP TO FIT, EQUAL TO MEULLER CO.
1" TYPE "K' SOFT COPPER TUBING 2'.1' BRASS BUSHING
1" COMBINATION AIR RELEASE & VACUUM VALVE,
SCREWED, APCC INC, 143C OR EQUAL.
WASHED GRAVEL, PASSING 1-1/2" AND RETAINED ON
1/4" MESH FOR BRAIN
NOTE:
AIR AND VACUUM RELEASE VALVE ASSEMBLY SHALL BE
INSTALLED AT HIGHEST POINT OF LINE. IF HIGH POINT FALLS
IN A LOCATION WHERE ASSEMBLY CANNOT BE INSTALLED,
PROVIDE ADDITIONAL DEPTH OF LINE TO CREATE A HIGH
POINT AT A LOCATION WHERE ASSEMBLY CAN BE INSTALLED.
LOCATE ARE -VACUUM METER BOX OUTSIDE OF TRAFFIC
AREAS, IN PLANTING STRIPS, BEHIND CURB OR SIDEWALK.
+ ` + PUBLIC WORKS 1" AIR & VACUUM RELEASE PLAN - �
DEPARTMENT ASSEMBLY
� MARCH 2O10
Uj
� J
Q }
I �
t� LRJ
I x DIRECTION OF FLOW
CL
cD Of 3"
10� O
1 6" MIN.
�6"MIN.(TYP.) (I -UNION (TYP.)
,,,\ Zu "^ ru
TO CITY
METER STACKED METER SECTION\-6" MIN. FREE
BOXES DRAINING GRAVEL
NOTES:
1. ALL DOUBLE CHECK VALVE ASSEMBLIES (DCVA's) MUST BE LISTED ON LATEST LIST OF "BACKFLOW PREVENTION
ASSEMBLIES APPROVED FOR INSTALLATION IN WASHINGTON STATE", PUBLISHED BY STATE OF WASHINGTON
DEPARTMENT OF HEALTH.
2. THE OWNER/APPLICANT MUST OBTAIN A SEPARATE CITY OF RENTON PLUMBING PERMIT FOR THE INSPECTION
OF THE INSTALLATION OF THE DCVA AND PIPING. THE OWNER SHALL FURNISH, INSTALL AND MAINTAIN THE
DCVA AND ALL PIPING AND APPURTENANCES SHOWN ON THIS PLAN.
3. THE DCVA MUST BE TESTED BY A STATE CERTIFIED BACKFLOW ASSEMBLY TESTER AFTER ITS INITIAL
INSTALLATION, AFTER REPAIRS AND ANNUALLY THEREAFTER AT OWNER'S EXPENSE. A COPY OF THE TEST
REPORT SHALL BE SENT OR FAXED TO CITY OF RENTON WATER UTILITY ENGINEERING DEPT., ATTN: WATER
UTILITY CROSS -CONNECTION CONTROL SPECIALIST, FAX NO. 425-430-7241.
4. DCVA AND METER,BOX SHALL BE LOCATED ON PRIVATE PROPERTY AND AS NEAR AS POSSIBLE TO THE
WATER METER.
PUBLIC WORKS �/4" TO 2" DOUBLE CHECK VALVE M. PLAN - 340.8
+ + ASSEMBLY FOR IRRIGATION OR
DEPARTMENT RESIDENTIAL FIRE SPRINKLER MARCH 2O10
LO
00
00
0
LO
Q
J
S-391005/W-391005 I w
IN COMPLIANCE WITH CITY OF RENTON STANDARDS 0
O
WATER UTILITY DEVELOPMENT ENGINEERING Z
_ Abdoul Gafour 10/16/2017 malt 10/17/2017
O
w
U
Q
DIM- CITY OF GRANT PLACE TOWNHOMES 2o1s-12-2 CL
RENTON
NIN z
Planning/Building/Public Works Dept. DETAILS Q
C21 '22 (�