CALL 48 HOURS
BEFORE YOU DIG
1-800-424-5555
SYM
ORIG I MITIGATION HANGAR
4),gBer erABAM
�
33301 9th Avenue South, Suite 300
Federal Way, Washington 98003-2600
(206) 431-2300 Fax:(206) 431-2250
REVISION
BY
C180242 1 ABAM
APPROVED DATE
SPT 10/09/18
SYM
CONSTRUCTION NOTES
TEMPORARY = PERMANENT
1 - 10" 90° BEND (RJ)
TEMPORARY = PERMANENT
1 - 10" x 8" TEE (FL)
1 - 8" GATE VALVE (FL)
1 - 8" COUPLING ADAPTER (FLxRJ)
1 - 10" COUPLING ADAPTER (FLxRJ)
1 - 10" FLUSH SECTION VALVE (FL)
1 - 10" TEMPORARY BLIND FLANGE (FL)
TEMPORARY
1 - 8" 22.5° VERTICAL BEND (RJ)
TEMPORARY = PERMANENT
1 - 10" TEE
3 - 10" GATE VALVE
1 - 10" COUPLING ADAPTER
2 - 10" COUPLING SLEEVE
1 - 10" PIPE SPOOLS AS REQUIRED
MAINTAIN CONNECTION TO ABANDONED
PIPE (NORTH) FOR THRUST RESTRAINT
TEMPORARY
1 - 8" 90° BEND WITH 22.5° VERTICAL
ROTATION (RJ)
REVISION
BY
APPROVED I DATE
GENERAL NOTES
1. SEE SHEET C501-1A FOR FIRE AND WATER SERVICE NOTES.
2. ALL FIRE LINE SHALL BE INSTALLED WITH RESTRAINED JOINTS.
3. SEE SHEET M501-1 D DETAIL 3 FOR TYPICAL UTILITY TRENCH BEDDING AND BACKFILL.
4. COORDINATE ALL DOMESTIC WATER AND FIRE WATER SHUT DOWNS REQUIRED FOR
CONNECTIONS TO EXISTING WITH BOEING SITE SERVICES AND FIRE DEPARTMENT.
5. FITTINGS SHOWN FOR CONNECTIONS TO EXISTING ARE SUGGESTED. CONTRACTOR
SHALL POTHOLE AND FIELD VERIFY PIPE TYPE, LOCATION, CONDITION AND ROUNDNESS
PRIOR TO ORDERING MATERIALS.
6. HORIZONTAL CONTROL NOTES SHOWN ON THIS SHEET REPRESENT CENTER OF
STRUCTURE, BEND OR CENTERLINE OF PIPE.
7. HORIZONTAL DATUM: WASHINGTON STATE COORDINATE SYSTEM, NORTH ZONE, NORTH
AMERICAN DATUM 1983(91). VERTICAL DATUM: NATIONAL GEODETIC VERTICAL DATUM
1929 (NGVD29). VERTICAL DATUM CONVERSION: NGVD29 TO THE NORTH AMERICAN
VERTICAL DATUM 1988 (NAVD88) = NGVD29 + 3.60 FEET.
8. THERE SHALL BE NO EXPOSED GALVANIZED MATERIALS, COATINGS OR ZINC APPLIED
SURFACE TREATMENTS ON ANY EXTERIOR OR UNDERGROUND MATERIALS OR SURFACES.
ALL GALVANIZED OR ZINC APPLIED MATERIALS OR COATINGS SHALL BE PERMANENTLY
PAINTED OR COATED TO PREVENT EXPOSURE OF THE GALVANIZED/ZINC MATERIALS
PRIOR TO INSTALLATION OR COMPLETION OF CONSTRUCTION.
9. UNLESS OTHERWISE NOTED ON THE DRAWINGS, ALL DUCTILE IRON PIPING AND FITTINGS
SHALL HAVE FLEXIBLE BOLTLESS RESTRAINED JOINTS, WITH A MECHANISM THAT
PROVIDES A POSITIVE AXIAL LOCK BETWEEN THE BELL AND THE SPIGOT TO RESTRAIN
THE JOINT. TR-FLEX BY U.S. PIPE, OR APPROVED EQUIVALENT. TR-FLEX GRIPPER RING
BY U.S. PIPE SHALL BE USED TO RESTRAIN FIELD CUT PIPE, PER MANUFACTURER'S
INSTRUCTIONS.
10. BOLLARD PROTECTION FOR ABOVE GRADE UTILITIES SHALL BE PER DETAIL 5 ON SHEET
M501-5D WITH SPACING PER DETAILS 1 AND 2 ON SHEET M501-5D.
11. FIRE SYSTEM IMPROVEMENTS SHOWN ON THIS PLAN MUST BE CONSTRUCTED PRIOR TO
BEGINNING PRELOAD CONSTRUCTION ACTIVITIES. SEE SHEETS C501-3A THROUGH
C501-3E FOR CONSTRUCTION PHASING PLANS. SEE SHEET C11E THROUGH C13E AND
SHEET M501-1 C FOR PERMANENT UTILITY IMPROVEMENT DESIGN.
KEY PLAN
SCALE : NONE
A B C D E F G H J K L
6
TEMPORARY
1 - 8" 90° BEND (RJ)
C10
C11
TEMPORARY FIRE WATER PIPE W/ HEAT
C12
EMU
TRACE AND INSULATION
C13
°
TEMPORARY
C14
8
1 - 8" 90° BEND
=
PRE -CAST CONCRETE THRUST BLOCK
C15
0
TEMPORARY
C 16
W
�®
1 - 8" 90° VERTICAL BEND (RJ)
C17
Y
10
CONNECTION TO EXISTING FIRE MAIN
C18
�
1
CONTRACTOR SHALL POTHOLE AND FIELD
C19
0
VERIFY FITTINGS REQUIRED TO MAKE
C20
O
CONNECTION PRIOR TO ORDERING PARTS
AND BEGINNING CONSTRUCTION
C21
11
CONNECT TO APRON R 10" FIRE MAIN
C22
SEE APRON R PLANS FOR CONTINUATION
C23
0
12
PROTECT EXISTING SECTION VALVE AND
RISER CONNECTION. REPLACE EXISTING
W4
—
01410
C24
C25
BOLLARDS AS REQUIRED.
C26
-�
a o
S-401410
C27
C28
C29
C30
P.
of WAsh� �f
® D
""A//V" �P �1
x
31271 w�
��ssioNaL
CIVIL PERMIT SET
V3
DESIGN BY: BERGERABAM DATE 10/22/2018
ACCEPTABILITY IHL
THIS DESIGN AND/OR CHE
SPECIFICATION IS APPROVED SPT
ENG
APPROVED BY DEPT. DATE BEE
SEPARATE FIRE PERMITS REQUIRED FROM RENTON REGIONAL FIRE AUTHORITY
20 0 20 40
scale feet
ATE SUBTITLE
10/09/18
10/09/18
10/09/18 TITLE
TEMPORARY UTILITY PLAN
MITIGATION HANGAR
RENTON SITE
SITE
R-401470
I IN COMPLIANCE WITH CITY OF RENTON STANDARDS
C180242 J'IV'UVLO R I Q v^ L 10/09/18
M501-1 A mol
JOB NO. COMP NO.
C180242
RENTON, WA DWG N0. RTN—YD—M501-1A