PROVIDE NEW STREET LUMINARIES AS REQUIRED BY THE CITY OF RENTON LAND USE ADVISORY NOTES DATED DECEMBER 29,2017. THE NEW
LUMINARIES WILL BE INSTALLED ON THE EAST FRONTAGE OF THE NEW MERRILL GARDENS BUILDING ALONG WILLIAMS AVE S. THE LUMINARIES
SELECTION AND PLACEMENTS SHALL MEET THE CITY OF RENTON ZONE STANDARDS FOR DOWNTOWN STREETSCAPE INCLUDING MINIMUM LIGHT
LEVELS AND UNIFORMITY RATIO REQUIREMENTS.
GENERAL NOTES
1, ALL WORK SHALL BE COMPLETED IN THE ACCORDANCE WITH THE CITY GUIDELINES AND STANDARDS, STANDARD SPECIFICATIONS, SPECIAL
PROVISIONS AND THESE PLANS.
2. THE LOCATION OF ALL LUMINAIRES, JUNCTION BOXES AND CONDUIT SHOWN ON THIS PLAN ARE FOR GRAPHIC PRESENTATION ONLY AND
FINAL LOCATIONS SHALL BE DETERMINED BY THE ENGINEER IN THE FIELD. ALL NEW CONDUIT SHALL BE PLACED WITHIN CITY OF RENTON
RIGHT—OF—WAY. ALL NEW POLE FOUNDATION LOCATIONS SHALL BE APPROVED BY THE ENGINEER PRIOR TO EXCAVATION. AFTER EXCAVATION,
VERIFY WITH ENGINEER THAT FIELD CONDITIONS ALLOW FOR ASSIGNED SPECIAL FOUNDATION.
3. NUMBER OF CONDUIT BENDS BETWEEN PULL POINTS SHALL NOT BE MORE THAN THE EQUIVALENT OF FOUR QUARTER BENDS (360 DEGREES
TOTAL). IF NUMBER OF BENDS EXCEEDS 360 DEGREES, THE CONTRACTOR SHALL INSTALL ADDITIONAL JUNCTION BOXES, AS REQUIRED.
4. ALL NEW JUNCTION BOXES INSTALLED IN SIDEWALKS SHALL HAVE LOCKING AND SKID RESISTANT LIDS.
5. EXISTING OR HIGHER ILLUMINATIONS LEVELS SHALL BE MAINTAINED BY USING EXISTING OR TEMPORARY ILLUMINATION UNTIL THE NEW SYSTEM
IS OPERATIONAL. THE CONTRACTOR IS ALSO RESPONSIBLE FOR MAINTAINING A CLEARANCE ZONE OF 15' AROUND EXISTING AERIAL POWER
LINES DURING CONSTRUCTION. COORDINATE WORK WITH THE POWER COMPANY.
6. JUNCTION BOXES FOR LUMINAIRES SHALL BE LOCATED PER POLE/JUNCTION BOX LAYOUT DETAILS OUTLINED ON SHEET E3.0 AND E3.1.
7. MAINTAIN A MINIMUM OF 4' CLEARANCE BETWEEN PROPOSED CONDUITS AND TREE CENTERLINES. FOR TRENCHING DETAILS.
8. CONTRACTOR SHALL CONTACT CITY OF RENTON MANAGER ERIC CUTSHALL (425) 430-7423 PRIOR TO DISCONNECTION OF POWER TO
EXISTING LUMINARIES. CONTRACTOR SHALL COORDINATE WITH CITY PUBLIC WORKS TO PROVIDE POWER TO NEW LUMINARIES.
9• CONTRACTOR SHALL INCLUDE POLE ID NUMBER AND GPS COORDINATES ON AS—BULT DRAWINGS.
10. ALL WORK SHALL BE CONSISTENT WITH UTILITY AGENCY REQUIREMENTS. THE CONTRACTOR SHALL CONTACT ALL PERTINENT UTILITY AGENCIES
48 HOURS BEFORE COMMENCING WORK AND SHALL COORDINATE WITH AFFECTED UTILITY AGENCIES THROUGHOUT THE PROJECT.
11. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGE TO EXISTING UTILITIES. THE CONTRACTOR AHALL NOTIFY THE AFFECTED UTILITY
COMPANY AND THE CITY IMMEDIATELY UPON DAMAGE.
INSTRUCTION TO BIDDERS
1. IT IS MANDATORY FOR THE CONTRACTOR TO VISIT THE SITE AND REVIEW
THE EXISTING SYSTEM AND CONDITIONS IN ORDER TO BID THIS PROJECT.
2. DESIGN DRAWINGS ARE SCHEMATIC. THIS CONTRACTOR SHALL VISIT THE
SITE PRIOR TO BIDDING OR AWARD OF CONTRACT TO INSPECT EXISTING
FIELD CONDITIONS. THIS CONTRACTOR SHALL INCLUDE ALL LABOR AND
MATERIALS NECESSARY FOR FIELD MODIFICATIONS DUE TO EXISTING
CONDITIONS.
3. THE CONTRACTOR SHALL CONTACT THE ARCHITECT, ENGINEER OR OWNER
PRIOR TO BIDDING FOR INTERPRETATIONS AND CLARIFICATIONS OF THE
DESIGN AND INCLUDE IN HIS BID ALL COSTS TO MEET THE DESIGN
INTENT. CLARIFICATIONS MADE BY THE ARCHITECT, ENGINEER OR OWNER
AFTER BIDDING WILL BE FINAL AND SHALL BE IMPLEMENTED AT
CONTRACTOR'S COST.
4. BIDDING CONTRACTORS SHALL HAVE A WORKING KNOWLEDGE OF LOCAL
CODES AND ORDINANCES AND SHALL INCLUDE IN THEIR BIDS THE COSTS
FOR ALL WORK INSTALLED IN STRICT ACCORDANCE WITH GOVERNING
CODES, THE PLANS AND SPECIFICATIONS NOT WITHSTANDING. THE
CONTRACTOR SHALL ALERT ARCHITECT, ENGINEER OR OWNER OF ANY
APPARENT DISCREPANCIES BETWEEN GOVERNING CODES AND DESIGN
INTENT.
REVISIONS:
DRAWING INDEX:
E1.0 STREET LIGHTING GENERAL NOTES & SHEET INDEX
E2.0 STREET LIGHTING — POWER & PHOTOMETRICS
E3.0 STREET LIGHTING DETAILS
E3.1 STREET LIGHTING DETAILS
E4.0 SPECIFICATIONS
CONSTRUCTION RECORD DRAWING:
THIS SHEET CONTAINS AS —BUILT INFORMATION
MINOR REVISIONS ARE SHOWN BY STRIKING
THROUGH THE ORIGINAL TEXT ADN DENOTING THE
AS —BUILT INFORMATION ADJACENT. OTHER
REVISIONS ARE DENOTED BY REVISION CLOUDS.
AS —BUILT INFORMATION WAS SURVEYED BY D.R.
STRONG AND SUPPORTING PHOTOS AND
DOCUMENTATION WAS PROVIDED BY SRM
(CONTRACTOR) ABOSSEIN ENGINEERING IS
RESPONSIBLE FOR NOTATING THE AS —BUILT
INFORMATION ON THE DRAWINGS BUT IS NOT
RESPONSIBLE FOR THE ORIGINAL AS —BUILT DATA P
ROVIDED TO ABOSSEIN ENGINEERING.
LUMINAIRE SCHEDULE
SYMBOL
CALLOUT
MODEL
DETAILS
DESCRIPTION
LAMP
BALLAST
MOUNTING
INPUT
VOLTS
NOTE I
POLE# AND CPS
QUANTITY
VOLTS
INPUT
DEFAULT
TOTAL
IES FILE
ARM
WATTS
INFO
WATTS
ELEVATION
LUMENS
LENGTH
ST1
Cyclone Lighting,
umentra, Inc.160
CYCLONE LIGHTING BELL SHAPED
(1) 80W 40 White LEDs
ELECTRONIC
POLE
90
120V 1 P 2W
15' POLE, TYPE PM4
NORTH POLE POINT
120
90
15'
9714
DOMIA—CY55P1 A—FGC-3-80W-4K
2
CY55P1 A—FGC-3-80W-4K —
Frobisher Drive, Unit
PENDANT LED FIXTUREWITH INDIVIDUAL
WITH M222 ARM AN
#23036.
(K617CM)
BK
SWaterloo,
LED LENS OPTICS AND CLEAR FLAT LENS
BM11 BASE, BLACK
POLE #51221380
OntarioNVLAP LAB
N=178941.0j
CODE 500084-0
E=1300836.1
04-29-2016
PHILIPS ADVANCE
SOUTH POLE
XITANIUM 120-277V
#23098
LED DRIVER MODEL
POLE #5121
LEDINTA070OC21 ODO
N=178880.2LED
E=13008334
70
4000
Outdoor, Area, Parking,
Parks, Pathway,
3
Pedestrian, Roadway,
Sidewalk, Site, Street,
Walkway, Decorative
Arm, Pendant, Pole,
Wall
Abossein
Engineering,
L.L.C.
MECHANICAL - ELECTRICAL
CIVIL - LEED
FIRE PROTECTION
18465 NE 68TH ST
REDMOIND, WA. 98052
PH: (425) 462-9441
FAX: (425) 462-9451
E-Mail: cservice@abossein.com
www.abossein.com
BASE MAP/TOPOGRAPHY PROVIDED BY
OTHERS. DCG CANNOT BE HELD LIABLE
WA
FOR ACCURACY. CONTRACTOR SHALL
z
FIELD VERIFY GRADES, UTILITIES AND
ALL OTHER EX FEATURES &
9�0 ���
CONDITIONS. IF CONDITIONS ARE NOT
SsioNA
AS SHOWN &/OR PLANS CANNOT BE
CONSTRUCTED AS SHOWN, CONTACT
DCG PRIOR TO CONSTRUCTION.
R-401201
IN COMPLIANCE WITH CITY OF RENTON STANDARDS
N
N
O
O
Cfl
AN
u
N
0
O
O
T
a
J
00
co
Q0
O
O
O
T
TJ
CALL 811 (2) BUSINESS DAYS
BEFORE YOU DIG
W
LU
(UNDERGROUND UTILITY
6�
LOCATIONS ARE APPROXIMATE)
<
SURVEYED:
SCALE:
AS NOTED
VERTICAL: NAVD 1988
HORIZONTAL: NAD 1983/1991
DATUM
RCITY 0
RENT 0 N
•
MERRILL
GARDENS AT RENTON CENTER- ADDITION
104 BURNETT AVE S, RENTON, WA 98057
STREET LIGHTING GENERAL NOTES,
DATE:
1 /21 /20
J
DESIGNED: JW
3
CONSTRUCTION RECORD DRAWINGS
CT
01/21/20
PAGE:FIELDB
PAGE:
2
CIVIL C❑NSTRUCTI❑N PERMIT REVIEW #2
CT
09/18/18
DRAWN:
JW
ONE INCH
DRAWING NO:
1
CIVIL C❑NSTRUCTI❑N PERMIT REVIEW #1
CT
07/26/18
CHECKED:
AA
AT FULL SCALE
IF NOT ONE INCH
Planning/Building/Public Works Dept.
E1 .�
W
N
REVISION
BY
DATE
1APPRIAA
SCALE ACCORDINGLY
SHEET INDEX