HomeMy WebLinkAbout119 (7/27/2022)DocuSign Envelope ID: F41B6C7D-1A89-4D3E-83C3-E2F0224FAF96 POLE & BRACKET CABLE, #12 AWG. SPLICES BETWEEN FUSE HOLDER AND LUMINAIRE FIXTURE SHALL NOT BE ALLOWED FUSE KITS QUICK REFER TO WSDOT LOCKING DISCONNECT 3 AMP IN LINE LID STANDARD DUTY FUSE KITS S.E.C. OR EQUAL - JUNCTION BOX TYPES 1 & 2 STANDARD PLAN J-40.10 GROUND LUG SPLICE KITS CLEAR EPDXY SPLICE KITS ON ALL THRU WIRE RUNS CONCRETE PAD OR SIDEWALK PER STD PLAN 120 24"(MIN) COVER #8 BARE COPPER GROUND WIRE 1 -#8 EQUIPMENT GROUND WIREW/GREEN INSULATION FROM SERVICE CABINET 2 - LIGHTING SYSTEM WIRES TO CONTACTOR (SIZED AS REQ'D.) NOTES: GROUND CLAMP PVC CONDUI 5/8"x8' COPPER CLAD GROUND ROD TO LUMINAIRE #8 GREEN INSULATED WIRE TO FIXTURE GROUND LUG CONCRETE FOUNDATION THIS DETAIL DEPICTS THE BASIC LUMINAIRE ELECTRICAL WIRING SYSTEM. ADDITIONAL ELECTRICAL EQUIPMENT MAY VARY. 2. MINIMUM GROUND WIRE SIZE SHALL BE #8, AS SHOWN ABOVE. IF CURRENT CARRYING CONDUCTORS ARE LARGER THAN #8, THE MINIMUM GROUND WIRE SIZE SHALL MATCH THE LARGEST WIRE SIZE OF THE CURRENT CARRYING CONDUCTORS. 3. EQUIPMENT GROUND WIRE & BARE WIRE SHALL BE SECURELY FASTENED TO THE GROUND LUG INSIDE THE POLE HANDHOLE. ALL BONDING & GROUNDING CONNECTIONS SHALL REMAIN ACCESSIBLE FOR INSPECTION AND MAINTENANCE. 4. IF THE FIXTURE MANUFACTURER HAS MADE PROVISIONS FOR THE ATTACHMENT OF A GROUND WIRE, A GREEN INSULATED WIRE OF THE SAME SIZE SHALL RUN FROM THE FIXTURE TO THE GROUND LUG INSIDE THE POLE HANDHOLE. IF THE FIXTURE MANUFACTURER HAS A GROUND LUG A #8 GREEN INSULATED WIRE SHALL BE RUN FROM THE FIXTURE GROUND LUG TO THE POLE GROUND LUG. G�•ty O� LUMINAIRE ELECTRICAL STD. PLAN - 119 ���� PUBLIC WORKS WIRING SYSTEM AP ROVED: �F DEPARTMENT GAZ 5/22/2019 DATE