POLE & BRACKET CABLE, #12
AWG. SPLICES BETWEEN FUSE
HOLDER AND LUMINAIRE FIXTURE
SHALL NOT BE ALLOWED
FUSE KITS QUICK
REFER TO WSDOT LOCKING DISCONNECT 3 AMP IN LINE
LID STANDARD DUTY FUSE KITS S.E.C. OR EQUAL -
JUNCTION BOX TYPES 1 &
2 STANDARD PLAN J-40.10
GROUND LUG
SPLICE KITS CLEAR EPDXY SPLICE
KITS ON ALL THRU WIRE RUNS
CONCRETE PAD OR
SIDEWALK PER STD PLAN 120
24"(MIN) COVER #8 BARE COPPER
GROUND WIRE
1 -#8 EQUIPMENT GROUND
WIREW/GREEN INSULATION
FROM SERVICE CABINET
2 - LIGHTING SYSTEM
WIRES TO CONTACTOR
(SIZED AS REQ'D.)
NOTES:
GROUND
CLAMP
PVC CONDUI
5/8"x8' COPPER CLAD
GROUND ROD
TO LUMINAIRE
#8 GREEN INSULATED WIRE
TO FIXTURE GROUND LUG
CONCRETE FOUNDATION
THIS DETAIL DEPICTS THE BASIC LUMINAIRE ELECTRICAL WIRING SYSTEM. ADDITIONAL ELECTRICAL EQUIPMENT MAY
VARY.
2. MINIMUM GROUND WIRE SIZE SHALL BE #8, AS SHOWN ABOVE. IF CURRENT CARRYING CONDUCTORS ARE LARGER
THAN #8, THE MINIMUM GROUND WIRE SIZE SHALL MATCH THE LARGEST WIRE SIZE OF THE CURRENT CARRYING
CONDUCTORS.
3. EQUIPMENT GROUND WIRE & BARE WIRE SHALL BE SECURELY FASTENED TO THE GROUND LUG INSIDE THE POLE
HANDHOLE. ALL BONDING & GROUNDING CONNECTIONS SHALL REMAIN ACCESSIBLE FOR INSPECTION AND
MAINTENANCE.
4. IF THE FIXTURE MANUFACTURER HAS MADE PROVISIONS FOR THE ATTACHMENT OF A GROUND WIRE, A GREEN
INSULATED WIRE OF THE SAME SIZE SHALL RUN FROM THE FIXTURE TO THE GROUND LUG INSIDE THE POLE
HANDHOLE. IF THE FIXTURE MANUFACTURER HAS A GROUND LUG A #8 GREEN INSULATED WIRE SHALL BE RUN
FROM THE FIXTURE GROUND LUG TO THE POLE GROUND LUG.
G�•ty O� LUMINAIRE ELECTRICAL STD. PLAN - 119
���� PUBLIC WORKS WIRING SYSTEM AP ROVED:
�F DEPARTMENT GAZ 5/22/2019