HomeMy WebLinkAboutS-230004SANITARY SEWER NOTES & SPECIFICATIONS
7. ALL WORK MATERIALS SHALL BE IN CONFORMANCE WITH THE STANDARDS AND
SPECIFICATIONS OF THE CITY OF' RENTON UTILITY DEPARTMENT AND THE LATEST
EDITION OF THE WSDT /APWA STANDARDS AND SPECIFICATIONS.
2. THE HOURS OF WORK IN THE STREET RIGHT -OF -WAY SHALL BE LIMITED TO 8:30
A.M. TO 3:30 P.M. ON WEEKDAYS UNLESS OTHERWISE APPROVED IN WRITING BY
THE DEPARTMENT OF PUBLIC WORKS AT 235 - 2.620. ALL STREET CLOSURES,
PARTIAL, OR FULL, SHALL BE APPROVED BY THE DEPARTMENT OF PUBLIC WORKS 24
HOURS IN ADVANCE. THE POLICE DEPARTMENT, AND 911 SHALL BE NOTIFIED 24
HOURS IN ADVANCE.
3. ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH "STANDARD SPECIFICATIONS
FOR MUNICIPAL PUBLIC WORKS CONSTRUCTION" PREPARED BY WASHINGTON STATE
CHAPTER AMERICAN PUBLIC WORKS ASSOCIATION, LATEST EDITION (APWA) AND
CITY OF RENTON STANDARD SPECIFICATIONS.
4. ALL LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE AND IT SHALL
BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE TRUE AND CORRECT
LOCATION SO AS TO AVOID DAMAGE OR DISTURBANCE.
5. A PRE - CONSTRUCTION CONFERENCE AND A 24 HOURS NOTICE SHALL BE REQUIRED
PRIOR TO STARTING NEW CONSTRUCTION. IT SHALL BE THE CONTRACTOR'S
RESPONSIBILITY TO SECURE ALL NECESSARY PERMITS PRIOR TO STARTING
CONSTRUCTION. (INSPECTION WILL BE ACCOMPLISHED BY A REPRESENTATIVE OF
THE CITY OF RENTON). IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO
,NOTIFY THE UTILITY DEPARTMENT 24 HOURS IN ADVANCE OF BACKFILL ALL
CONSTRUCTION.
6. CONTRACTOR IS SOLELY RESPONSIBLE FOR THE MEANS, METHODS AND SEQUENCES OF
CONSTRUCTION AND FOR THE SAFETY OF WORKERS AND OTHERS ON THE
CONSTRUCTION SITE.
7. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO OBTAIN STREET USE
AND ANY RELATED PERMITS PRIOR TO ANY CONSTRUCTION.
B. PLANS APPROVED BY THE CITY OF RENTON, PUBLIC WORKS DEPARTMENT SHALL TAKE
PRECEDENCE OVER ALL OTHER PLANS.
9. A COPY OF THESE APPROVED PLANS MUST BE ON THE JOB SITE WHENEVER
CONSTRUCTION IS IN PROGRESS.
10. THE CONTRACTOR SHALL PROVIDE THE CITY OF RENTON WITH AN AS -BUILT
DRAWING OF THE SANITARY SEWER SYSTEM WHICH HAS BEEN STAMPED AND
SIGNED BY A LICENSED PROFESSIONAL ENGINEER OF LICENSED
PROFESSIONAL SURVEYOR.
11. BACKFILL SHALL BE PLACED EQUALLY ON BOTH SIDES OF THE PIPE IN LAYERS
WITH A LOOSE AVERAGE DEPTH OF 6 INCHES, MAXIMUM DEPTH OF B/ INCHES,
THOROUGHLY TAMPING EACH LAYER TO 95 PERCENT OF MAXIMUM DENSITY. THESE
COMPACTED LAYERS MUST EXTEND FOR ONE PIPE DIAMETER ON EACH SIDE OF THE
PIPE OR TO THE SIDE OF THE TRENCH. MATERIALS HOT MIX PATCH SHALL BE
PLACED WITHIN 10 DAYS AND SHALL BE PER CITY OF RENTON CURRENT
STANDARDS.
13 DATUM SHALL BE CITY OF RENTON, U.S.C. AND G.S.
14. ALL DISTURBED AREAS SHALL BE SEEDED MULCHED OR OTHERWISE STABILIZED TO
THE SATISFACTION OF THE DEPARTMENT FOR THE PREVENTION OF ON -SITE EROSION
AFTER THE COMPLETION OF CONSTRUCTION.
15. ALL PIPE AND APPURTENANCES SHALL BE LAID ON A PROPERLY PREPARED
FOUNDATION IN ACCORDANCE WITH SECTION 7- 02.3(1) OF THE CURRENT STATE OF
WASHINGTON STANDARD SPECIFICATIONS FOR ROAD AND BRIDGE CONSTRUCTION.
THIS SHALL INCLUDE NECESSARY LEVELING OF THE TRENCH BOTTOM OR THE TOP OF
THE FOUNDATION MATERIAL AS WELL AS PLACEMENT AND COMPACTION OF REQUIRED
BEDDING MATERIAL TO UNIFORM GRADE SO THAT THE ENTIRE LENGTH OF THE PIPE
INILL BE SUPPORTED ON A UNIFORMLY DENSE UNYIELDING BASE. PIPE BEDDING
SHALL BE PEA GRAVEL 6" ABOVE AND BELOW THE PIPE.
16. SANITARY SEWER PIPE SHALL BE POLYVINYL CHLORIDE (PVC) RUBBER GASKETED
ASTM D 3034, SDR 35, OR DUCTILE IRON CLASS 50.
17. IN UN- IMPROVED AREAS, MANHOLE TO EXTEND MINIMUM 6 INCH AND MAXIMUM 78
INCH ABOVE FINISHED GRADE, IN PAVED AREA, COVER MUST SLOPE IN ALL
DIRECTIONS TO MATCH PAVING.
I--
❑ 314" SPACES SPACED -314 "
o ° o AS INDICATED -HT. 718"
❑OO°
❑ ❑o
118" RAISE -1/2" WIDE
_ 7„
BORDER
70"
9"
FF 3/4"
75'
CAST IRON RING AND COVER
PROPERTY LINE
SIDE SEWER MAIN TO BUILDING SEWER
c < I FUTURE
6" SEWER PIPE �-- 6.0 - -� BLDG SEWER
6" SIDE OUTLET TEE 2 "X4" STUD SERVICE FuIARKER
PAINT UPPER PORTION WHITE
a AND STENCIL ON SIDE WORD
"SEWER" WITH 3" HIGH
a BLACK LETTERS.
6" SIDE SEWER & BUILDING SEWER
PLAN
6 SIDE SEWER
1:3:5 MIX
X
NOTE:
CONCRETE 60' ALLOWABLE MAX
BLOCKING FOR CAST OR
DUCTILE IRON PIPE.
SIDE SEWER SHALL HAVE A
MINIMUM 5' COVER AT PROPERTY
LINE OR 3 -5' LOWER THAN THE
6 "MIN
LOWEST HOUSE ELEVATION, WHICH -
1 25, MIN
EVER IS LOWER.
6 "MIN HORIZON I AL
6" SIDE OUTLET TEE
SEWER MAIN
CONC. BLOCKING ANGLE
OF TEE AT MAIN OVER 25°
ELEVATION
0
eo�
25'
2% MIN SLOPE
HORIZONTAL
TYPICAL SIDE SEWER
ELEVA TION
EXISTING SEWER MAIN
`6" SIDE SEWER
e`i 6 TEST TEE
TO BE INSTALLED
AT CONNECTION
NO TE:
MAKE TAP THROUGH CAST IRON
SADDLE SECURED TO 'SEWER MAIN
WITH STAINLESS STEEL BANDS
WHEN CONNECTING NEW SIDE
SEWERS TO EXISTING MAIN.
VITRIFIED CLAY, PLAIN &
REINFORCED CONCRETE, D7 &
Cl PIPE SEWER MAINS ARE TO
BE CORE DRILLED.
SIDE SEWER SERVICE DETAIL
TYP. SEE SHTS. 15 & 16
24"
ADJUSTING RINGS OR BLOCKS
AS REQUIRED.
24" x 6" FRAME AND LOCKING LID
PER DRAWING BR29.
4" MIN. TO 12" MAX. k
PRECAST VALVE ADAPTOR COLL R ro
CHAMBER CONE 8" OR 12 10 v
R.C.P. OR EQUUA RUBBER GASKET PIPE
2
i I - N 1
12 "D I- 4 314"
R JOINT
KING
7/8 BEND
PLUG TO BE SEALED IN SAME
MANNER AS MAIN SEWER JOINTS.
AS SPECFED CLEAN -OUT DETAIL
rq,
° p
6" MIN.
/ 48"
POURED IN PLACE BASE
EXTRA SHALLOW
SANITARY MANHOLE TYPE C
(BR 38)
MANHOLE FRAME & COVER
SEE DRAWING BR29
25 ADJUSTMENT 4" MIN.
RUBBER GASKETED JOINTS
ACCORDANCE WITH ASTM. C -443
4" MIN. STEPS -314" DEFORMED BAR
STEPS SHALL BE INCLUDED
Z
- 6 7/2"
i�
CONRETE RISER BY PIPE INC.
48" OR APPROVED EQUAL
MAX. PIPE SIZE -27" I.D.
LADDER -STD. ALUMINUM
OR GALVANIZED STEEL.
CONCRETE SHELF
MORTAR ZP04� PRECAST BASE SECTION
OR CAST IN SHELF
- �- 6" MIN. (TYP)
SANITARY MANHOLE TYPICAL DETAIL
(N TS)
TYP. SEE SHTS. 75 & 16
NOTES:
1. STEPS TO BE 3/4" 0 DEFORMED BAR GALVANIZED SAFTEY STEPS OR EQUAL
2. STEPS ARE TO BE IN PLACE BEFORE MANHOLE SECTIONS ARE INSTALLED
3. CASTING TO BE OLYMPIC FOUNDRY MH30 WITH MH30 D/T OR EQUAL. PER DWG. BR29
* 4. MANHOLE SECTIONS TO BE OF REINFORCED PRECAST CONCRETE
** 5. OPENING SHOULD BE ON DOWNSTREAM SIDE.
6. ALL JOINTS SHALL BE GROUTED.
7. SANITARY SEWER MANHOLES SHALL HAVE ALL INTERIOR
SURFACES, INCLUDING CHANNELING, COATED (SEALED)
WITH A HIGH SOLIDS URETHANE COATING;
WASSER MC- CONSEAL OR APPROVED EQUAL;
COLOR OF COATING SHALL BE WHITE.
8. RUBBER GASKETED JOINTS SHALL BE IN CONFORMANCE
WITH ASTM C -443.
9. CHANNEL HEIGHT SHALL BE A MINIMUM OF 3/4 THE INSIDE
DIAMETER OF THE LARGEST PIPE.
10. CONNECTIONS TO MANHOLE SHALL BE MADE USING GPK
ADAPTOR, KOR -N -SEAL BOOTS OR APPROVED EQUAL
* TYPICAL AND SHALLOW TYPE B SANITARY MANHOLES ONLY 24 "x 6" FRAME AND LIP
** SHALLOW TYPE B MANHOLES ONLY `PER DRAWING BR29.
RECOMMENDED
FOR APPROVAL
BV �n
BY-_t
c_*1znnn♦
L� 24,"
Iq,
po
MIN. TO 12"
42" MIN. T6 84" MAX.
E 2' T05'I
SHALLOW TYPE B
SANITARY MANHOLE DETAIL (BR 37)
PORTION OF SW 114 OF THE SE 114 OF SEC 19, TWN 23 N., R SE., W.M.
p p�90 CITY OF RENTON
TOUMA ENGINEERS DEPARTMENT OF PUBLIC WORKS
O��oR
-A WEST VALLEY EXECUTIVE PARK
6632 SOUTH 197ST PLACE, SUITE E -102 ° KENT, WA 98032 VALLEY VIEW ESTATES
PHONE (206) 251 -0665 FAX (206) 251 -0625 SANITARY SEWER DETAILS. & NOTES
1� 1
/ 54 wq ,W`�' l PER CITY REVIEW DT I 97 DESIGNED: D.O. DATE: SEP 7996 JOB NO. 696 -001 -951
`SIONALl DRAWN: D.O. R.D.V.
CHECKED: M.T. SCALE: NA owc -ra 6961SSDT
EXPIRES 0/22/9'!
N0. REVISION BY APPR. DATE APPROVED: SHEEP: 15 OF: 24