HomeMy WebLinkAboutS-279308NEW ACCESS LADDER
NEW LIMIT SWITCH ON ,ACCESS
HATCH TO ACTIVATE LIGHT
CIRCUIT WHEN OPEN.
NEW DRY WELL VAULT
L
NEW LIMIT SWITCH ON ACCESS
HATCH TO ACTIVATE
VENTILATION SYSTEM.
NEW WET WELL LIGHT SWITCH. MOUNT IN
ACCESS HATCH FRAME AREA CLEAR OF
HATCH COMPONENTS. SWITCH SHALL
NOT INTERFERE WITH HATCH CLOSURE.
SWITCH SHALL BE ACCESSIBLE FROM
STREET LEVEL.
NEW RECEPTACLE. MOUNT IN ACCESS
HATCH FRAME AREA CLEAR OF HATCH
COMPONENTS. RECEPTACLE SHALL NOT
INTERFERE WITH HATCH CLOSURE.
RECEPTACLE SHALL BE ACCESSIBLE FROM
STREET LEVEL.
NEW ACCESS HATCH TO DRY
WELL VAULT
J
HVAIC PANEL [DRY WELL ELECTRICAL PLAN
NEW ELECTRICAL HANDHOLE
30 AMP FUSE BLOCK � ACCESS HATCH.
r SURGE SURPRESSOR -
/ A
NEW DRY WELL VAULT
NEW LEVEL TRANSMITTER
NSTALLED IN "- — 1
SEE DETAIL OP
EXHAUST FAN rJ C r� TAKE PIPE PENETRATION
I, a. 3,
�I -�
- o
d: \ DRAIN TROUGH
a -�o o a' o:Q 6 o o 0
�-
o
DRY WELL VAULT - SECTION
TE3
1" = 2' -0"
•
P,
TE3
WET WELL ELECTRICAL PLAN
1 = 2' -0"
ATS AND MOUNTING
. SEE SPECIFICATIONS
SILS.
REVISED TO CONFORM TO CONSTRUCTION RECORDS DIVE MM 0//18/00
NO. REVISION BY REVIEW" DATE
NEW LADDER ® REVISED TO CONFORM RH2 ENGINEERING. INC
TO CONSTRUCTION RECORDS L' '1Sp
1� °t WAS , ?Z�
MARK MILLER 07/18/00 ENGINEERS BOTHELL. OFFICE
RH2 ENGINEERING INC. DATE PLANNERS
SCIENTISTS EAST WENATCHEE OFFICE .g, 22780
�R�clstse6 °� SIGNED:
fonrnL �'
NEW WET WELL STRUCTURE DRAWING IS NOT TO SCALE 11112199
IF BAR IS NOT 2" LONG ExpIRES �/ s zooz
0 L, 2..
NEW CLEANING PAD R CITY Y OF RENTON -1999 SEWER
SQL • E$
*As LIFT STATION ':REPLACEMENT PROJECT
TALBOT CREST LIFT STATION
22513 ! I p p, /�
01ST-0 ` SIGNED: ELECTRICAL f AN
TONAL 11/11/99
aoe elo. rim EriclNEEa acVErho DA FE scnve vi.ur ow(; No swErr
Ex IHr s 11/3/01 199.054 TAI - -E5R MM I MM I NOV 22, 2000 1 SHOWN' 24 1 TE3 8 -112
Y
ELECTRICAL NOTES
1. ALL WIRES SHALL BE ROUTED IN RIGID GALVANIZED STEEL CONDUIT UNLESS OTHERWISE NOTED, SIZE AS
NOTED ON DRAWING. CONDUIT SHALL BE 1/2" SIZE WHEN NOT ON PLANS.
2. 480 VOLT WIRING SHALL BE ROUTED IN SEPARATE CONDUITS FROM 120 VOLT (AND OTHER VOLTAGE)
CIRCUITS.
3. ALL WIRE SHALL BE A MINIMUM SIZE # 12 UNLESS SHOWN OTHERWISE.
4.
LOCATION OF CONDUIT ENDS ARE SHOWN APPROXIMATELY. CONTRACTOR IS RESPONSIBLE FOR ENDING
CONDUITS IN LOCATION THAT WILL NOT CONFLICT WITH EQUIPMENT IN THE VAULT.
5. CONDUIT ROUTING IS SHOWN DIAGRAMMATIC. CONTRACTOR IS RESPONSIBLE TO ROUTE CONDUITS IN A
NEAT MANNER, PARALLEL OR PERPENDICULAR TO WALLS AND SECURELY ATTACHED TO WALL OR CEILING.
6. ALL
CONDUIT PENETRATIONS INTO THE CONCRETE STRUCTURES REQUIRE A LINK -SEAL FITTING AROUND THE
CONDUIT. PENETRATION SHALL BE WATERTIGHT.
ELECTRICAL EQUIPMENT LEGEND
Oq
SERVICE ENTRANCE DISCONNECT SWITCH - NEMA 3R, HEAVY DUTY BREAKER, SERVICE RATED, 100
AMP, 600 VOLT, CIRCUIT BREAKER SWITCH. SIEMENS MODEL E3RED63B10O OR EQUAL. SERVICE
ENTRANCE SWITCH SHALL INCLUDE A SURGE SUPPRESSION UNIT AS IDENTIFIED ON DWG NO. TE1.
OB
MANUAL TRANSFER SWITCH - NEMA 3R, DOUBLE THROW, NON -FUSED SAFETY SWITCH, 600 VOLT, 100
AMP, SIEMENS MODEL NFR353DTK OR EQUAL. (SIZE: 12 "Wx25 "Hx5 "D)
©
480 VOLT DISTRIBUTION BOX - NEMA 3R, SIZED PER N.E.C.
DO
240/120V LIGHTING PANELBOARD - NEMA 3R, SINGLE PHASE, 3 WIRE, SOLID NEUTRAL, 16 SPACES.
SIEMENS MODEL W1624MB1100CU OR EQUAL PROVIDE BREAKERS AS SHOWN ON ONE -LINE DIAGRAM.
(SIZE: 14.5 "Wx22 "Hx4.5 "D)
of
PUMP CONTROL PANEL - SEE SPECIFICATIONS.
OF
TRANSFORMER DISCONNECT SWITCH - NEMA 3R, HEAVY DUTY, 3 -POLE, 3 -WIRE, 30 AMP, 600 VOLT,
FUSED DISCONNECT SWITCH. SIEMENS MODEL FR351 OR EQUAL. (SIZE: 8.5 "Wx15 "Hx4.5 "D)
©
LOW VOLTAGE TRANSFORMER - OUTDOOR RATED, DRY -TYPE, 5 KVA, 240x480- 120/24OV, SINGLE
PHASE. SIEMENS MODEL lDlNO05ST OR EQUAL. (SIZE: 10 "Wx15 "Hx12 "D)
OH
ELECTRICAL CEILING HEATER - IOKW, 480 VOLT, 3 PHASE 34,100 BtuH, ELECTRICAL HEATER WITH
UNIVERSAL MOUNTING BRACKET. MOUNT PER MANUFACTURER'S RECOMMENDATION. DAYTON
HEAVY -DUTY MODEL OR APPROVED EQUAL. PROVIDE WITH WALL MOUNTED THERMOSTAT ADJUSTABLE
BETWEEN 50' TO 807. THERMOSTAT SHALL HAVE A ROOM TEMPERATURE THERMOMETER. SET
THERMOSTAT AT 557.
OJ
ELECTRICAL HEATER DISCONNECT - NEMA 3R, HEAVY DUTY, 3 -POLE, 3 -WIRE, 30 AMP, 600 VOLT,
FUSED DISCONNECT SWITCH. SIEMENS MODEL FR351 OR EQUAL. (10 "Wx15 "Hxi2 "D)
OK
UTILITY METER ENCLOSURE - AS APPROVED BY PUGET SOUND ENERGY.
©
GENERATOR CONNECTION RECEPTACLE - OUTDOOR RATED, 600 VOLT, 100A, 4 -POLE, 3 -WIRE,
THREADED CAP, WEATHERPROOF. CROIISE HINDS MODEL NO. AREA10486 OR EQUAL THAT MATCHES
CITY'S EXISTING PLUG.
OM
TELEMETRY PANEL FROM EXISTING LIFT STATION. OWNER WILL PROVIDE PANEL FOR INSTALLATION BY
CONTRACTOR. ENCLOSURE SHALL BE INSTALLED IN EXISTING NEMA 3R TELEMETRY ENCLOSURE AFTER
EXISTING PANELS IS RELOCATED.RE -USE EXISTING CONDUIT PENETRATIONS WHEN POSSIBLE. CONNECT
TO PROPOSED SENSORS, ALARMS, AND DEVICES.
0
WALL MOUNTED INCANDESCENT FIXTURE - EXPLOSION PROOF, 120 VOLT, 150 WATT RATED. FURNISH
WITH 150 WATT EXTENDED SERVICE LIGHT BULB. APPLETON PART NOS. AALB -75 (BRACKET), AAU -15N
(FIXTURE UNIT), AAGU -1 (ALUMINUM GUARD) OR EQUALS. FURNISH ALL NECESSARY CONDUIT AND
SEALS TO MEET EXPLOSION PROOF CRITERIA. MOUNT AS HIGH AS POSSIBLE ON WALL.
©
ELECTRICAL EQUIPMENT PANEL LIGHT FIXTURE - INCANDESCENT, 120 VOLT, 150 WATT RATED. FURNISH
WITH 150 WATT EXTENDED LIFE BULB. HUBBELL MODEL VX -151 OR EQUAL-
LIGHT AND HVAC LIMIT SWITCHES
®
DISCONNECT SWITCH - NEMA 3R, HEAVY DUTY BREAKER, SERVICE RATED, 100 AMP, 600 VOLT,
CIRCUIT BREAKER SWITCH. SIEMENS MODEL E3RED63B100 OR EQUAL.
OS
INTRUSION ALARM SWITCH - SQUARE D HEAVY DUTY TYPE C, CLASS 9007 OR EQUAL. USE LIQUID
TIGHT FLEXIBLE CONDUIT BETWEEN JUNCTION BOX AND LIMIT SWITCH. CONTRACTOR SHALL SELECT
ACTUATOR LEVER ALARM BEST SUITED FOR MOUNTING CONFIGURATION.
V
CHECK VALVE POSITION LIMIT SWITCH - SQUARE D HEAVY DEITY TYPE C, CLASS 9007 OR EQUAL. USE
LIQUID TIGHT FLEXIBLE CONDUIT BETWEEN JUNCTION BOX AND LIMIT SWITCH. SEE DETAIL ON DWG NO.
G2.
O
FLOOD SWITCH - OMEGA MODEL LV -10 OR EQUAL. MOUNT TO END OF 1/4" PVC PIPE AND SECURE TO
WALL WITH MINIMUM OF TWO STAINLESS STEEL PIPE CLAMPS. SWITCH SHALL TRIP AT 1/2" OF WATER
LEVEL IN VAULT.
(�
LOW TEMPERATURE DEHUMIDIFIER 7.7 AMP, 115V, 1 PHASE, 0.7 PINTS PER HOUR ® 80% RELATIVE
HUMIDITY AND 557 TEMPERATURE. EBCO OASIS MODEL OD 3800HG OR APPROVED EQUAL. PROVIDE
WITH MOUNTING FIBERGLASS SHELF MOUNTED TO WALL FOR SUPPORTING THE DEHUMIDIFIER. PROVIDE
WITH RUBBER DRAIN HOSE AND FITTINGS TO SUMP PIT.
REVISED TO CONFORM TO CONSTRUCTION RECORDS DIVE MM 0//18/00
NO. REVISION BY REVIEW" DATE
NEW LADDER ® REVISED TO CONFORM RH2 ENGINEERING. INC
TO CONSTRUCTION RECORDS L' '1Sp
1� °t WAS , ?Z�
MARK MILLER 07/18/00 ENGINEERS BOTHELL. OFFICE
RH2 ENGINEERING INC. DATE PLANNERS
SCIENTISTS EAST WENATCHEE OFFICE .g, 22780
�R�clstse6 °� SIGNED:
fonrnL �'
NEW WET WELL STRUCTURE DRAWING IS NOT TO SCALE 11112199
IF BAR IS NOT 2" LONG ExpIRES �/ s zooz
0 L, 2..
NEW CLEANING PAD R CITY Y OF RENTON -1999 SEWER
SQL • E$
*As LIFT STATION ':REPLACEMENT PROJECT
TALBOT CREST LIFT STATION
22513 ! I p p, /�
01ST-0 ` SIGNED: ELECTRICAL f AN
TONAL 11/11/99
aoe elo. rim EriclNEEa acVErho DA FE scnve vi.ur ow(; No swErr
Ex IHr s 11/3/01 199.054 TAI - -E5R MM I MM I NOV 22, 2000 1 SHOWN' 24 1 TE3 8 -112