HomeMy WebLinkAboutS-290031L
It
CRM1
120V PUMP
CALL INTERPOSE RELAY
MS1
PUMP RUN
15AN.W
name aii
REMOTE 120VDC THERMAL FAIL
(SHIELDED). CONNECT TO TELEMETRY
EM tii e;
liq I I iiiil i pp
' • • • ' ' •' ilk ' • I•.
NO SCALE
PUMP 1 SEAL & THERMAL FAIL RESET
PUMP N0. 1 MOTOR
PUMP N0: 1 STARTER
PUMP NO. 1 OVERTEMP LIGHT
(PRESS TO TEST)
OVERTEMP RELAY
PUMP /SEAL FAIL
(PRESS TO TEST)
RUNNING TIME METER
START COUNTER
PUMP RUN
CLASS 1, DIVISION 1 HAZARDOUS AREA
POWER AND SENSING J —BOX: XP AND NEMA 4
(0 RING): GUB TYPE WITH TERMINAL STRIP AND
DOME COVER. CONTROL J —BOX: NEMA 4.
CABLE —TO— CONDUCTOR CONNECTIONS MADE IN
BOXES. BOLT AND TAPE MOTOR LEAD --- --
CONNECTIONS. MAKE SENSING AND CONTROL —
CONNECTIONS ON TERMINAL STRIPS, SEE
ONE —LINE DIAGRAM FOR NUMBER OF J —BOX
REQUIRED.
2" C, (MIN), WITH
BUSHINGS OR END BELLS
FITTING WITH GLAND NUT, NEOPRENE BUSHING
AND WIRE MESH CABLE GRIP
SST MOUNTING BRACKET OR FRAMING CHANNEL
FASTEN SECURELY TO BOTH SIDES OF
HANDHOLE
CLASS 1, DIVISION 1
HAZARDOUS AREA
POWER AND SENSING J —BOX: XP AND NEMA 4
(0 RING): GUB TYPE WITH TERMINAL STRIP AND
DOME COVER. CONTROL J —BOX: NEMA 4.
CABLE —TO— CONDUCTOR CONNECTIONS MADE IN
BOXES. MAKE SENSING AND CONTROL
CONNECTIONS ON TERMINAL STRIPS. PROVIDE
SEPARATE J —BOX FOR EACH FLOAT AND SONIC
LEVEL SENSOR,
2" C, (MIN), WITH
BUSHINGS OR END BELLS
FITTING WITH GLAND NUT, NEOPRENE BUSHING
AND WIRE MESH CABLE GRIP
SST MOUNTING BRACKET OR FRAMING
CHANNEL FASTEN SECURELY TO BOTH
SIDES OF HANDHOLE
REVISED TO CON S
TO CONSTRUCTION RQRM
'CORGIS
MARK MILLER
RH2 ENGINEERING INC.
24. 2003
DATE
MANHOLE COVER MARKED "ELECTRICAL"
PROPOSED CONCRETE HANDHOLE, SEE
DWG NO. JE2 FOR SIZE AND TYPE,
1 `JO PUMP CONTROL PANEL
NOT TO SCALE
A I N ffes =Iwo , I"
COVER MARKED ELECTRICAL
NON— SHRINK GROUT
MINIMUM 12" SLAB
BEDDING MATERIAL
NATIVE MATERIAL
NOTE
PROVIDE MAXIMUM SEPARATION BETWEEN
EACH SPLICE IN. ELECTRICAL VAULT.
PROPOSED BRUSHED 4"
THICK ALUMINUM PLATE
MOUNTED TO VALVE FLANGE.
PROPOSED LIMIT SWITCH.
NOT TO SCALE
PROPOSED CONCRETE
HANDHOLE WITH GALVANIZED
DIAMOND PLATE COVER WITH
LOCKING LATCH. SEE DWG NO.
JE2 FOR SIZE AND TYPE.
TO PUMP CONTROL PANEL —
NON— SHRINK GROUT
MINIMUM 12" SLAB
BEDDING MATERIAL
NATIVE MATERIAL
NOTE
PROVIDE MAXIMUM SEPARATION BETWEEN
FLOAT SPLICE AND LEVEL TRANSMITTER
CABLE IN ELECTRICAL VAULT.
IVISION
1,.
EXPIRES 3/19/200
SIGNED: 991261( 1
�F W A SSq
Q c0
y
y" 16727
ti
EXPIRES 8/2/C
SIGNED: 11126 )1
is
roe C;,1
�i U2 Fit
ZV .a
O �.
Q al r aj
t3 s
0H ul
1 r/! `� ! b
V �
.e:.
W r °�Ir a
a ui.,l pC
Ad VAL
O
E-4 LIJ
zo
..�
m
W Ro Ana.
V IMw�
i„a
i
tl�
s.l
RH2 ENGINEERR G, INC.
BELLINGHAM OF =ICE
E30THELL OFFIC
jz.4 )(i
EAST WENATCH -_E OFFICE
PORT ORCHARC OFFICE
SCALE: SH )WN
6iiiiip9i�
0 1" 2„
DRAWING IS NOT TO SCALE
IF BAR IS NOT ?" LONG
T
DWG N0.
PLOT: 1
ENGINEER: DMB E -5
REVIEWED: MM
DATE: JAN 27, 200 SHEETo.
CLIENT: PAG 4
I
DO MM 1/24/03
JOB NO.: 10110 2
BY REVIEW I DATE
FILENAME. KCC -E5
tl�
s.l