HomeMy WebLinkAboutD-337505ti
M
M
ti
N
a
� F-
Z U
W
w O
0
o! �
a.
a
W
2
W
0
a
W
F-
U)
2
O
Lu
Z
Z
J
a
i
j
ca
I
c
WATER UTILITY NOTES AND SPECIFICATIONS:
1. ALL WORK MATERIAL SHALL BE IN CONFORMANCE WITH THE STANDARDS AND SPECIFICATIONS
OF THE CITY OF RENTON PLANNING /BUILDING /PUBLIC WORKS DEPARTMENT AND THE LATEST
EDITION OF THE WSDOT /APWA STANDARDS AND SPECIFICATIONS, AS APPROVED AND MODIFIED
BY THE CITY OF RENTON IN THE RENTON STANDARD PLANS & SPECIFICATIONS. A SET OF
APPROVED PLANS SHALL BE KEPT ON SITE AT ALL TIMES DURING CONSTRUCTION.
2. THE HOURS OF WORK IN THE STREET RIGHT OF WAY SHALL BE LIMITED TO 8:30 AM TO 3:30
PM ON WEEKDAYS UNLESS OTHERWISE APPROVED IN WRITING BY THE PUBLIC WORKS
DEPARTMENT AT (425) 430 -7301. THE POLICE DEPARTMENT, FIRE DEPARTMENT, AND 911
SHALL BE NOTIFIED 24 HOURS IN ADVANCE OF ANY WORK IN THE RIGHT OF WAY.
3. ALL LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE AND IT SHALL BE THE
CONTRACTOR'S RESPONSIBILITY TO VERIFY THE TRUE AND CORRECT LOCATION SO AS TO AVOID
DAMAGE OR DISTURBANCE. FOR UTILITY LOCATES CALL 48 -HOUR LOCATORS 800 -424 -5555.
w n• nnnnnvrn rrn nnmmRn n n REQUIRED TO BE n ,nE,mrrn AT :HIE
4. AN nr PROYED TRAF
5. ALL WATERMAIN PIPE IS TO BE CEMENT LINED DUCTILE IRON PIPE CONFORMING TO AWWA
C110 AND C111 OR LATEST REVISION, THICKNESS CLASS 52. CEMENT MORTAR LINING AND
SEAL COATING SHALL CONFORM TO AWWA C104 OR LATEST REVISION. PIPE JOINTS TO BE
PUSH -ON OR MECHANICAL JOINT. BEDDING TO BE CLASS C. ALL DUCTILE IRON PIPE AND
FITTINGS SHALL BE POLYETHYLENE WRAPPED PER ANSI /AWWA C105/A21.5 -93 STANDARDS.
6. CAST IRON AND DUCTILE IRON FITTINGS SHALL BE CEMENT LINED, PRESSURE RATED AS NOTED
ON PLANS, AND IN ACCORDANCE WITH ANSI /AWWA C110/A21.10 -87. CEMENT LINING SHALL
BE IN ACCORDANCE WITH ANSI /AWWA C104/421/4 -90. IF FITTINGS ARE 3 TO 12 INCHES IN
DIAMETER AND HAVE MECHANICAL JOINTS, THE FITTINGS SHALL IN ACCORDANCE WITH EITHER
ANSI /AWWA C110- A21.10 -87 OR ANSI /AWWA C153/A21.53 -94. THREE (3) INCH TO 12 INCH
DIAMETER FITTINGS, WHICH HAVE MECHANICAL JOINTS AND /OR FLANGED JOINTS, SHALL BE IN
ACCORDANCE WITH ANSI /AWWA C110/A21.10.87 OR A COMBINATION OF ANSI /AWWA
C110/A21.10.87 AND ANSI AWWA C153/A21.53 -94 SUCH THAT THE PORTION OF THE FITTING
WITH A MECHANICAL JOINT(S) MAY BE WITH ANSI /AWWA C153/A21.53 -94 AND THAT PORTION
OF THE FITTING WITH FLANGED JOINT(S) SHALL BE IN ACCORDANCE WITH AWWA
C110/A21.10 -87. ACCEPTANCE TESTING IN ACCORDANCE WITH SECTION 53.53 OF ANSI /AWWA
SECTION 10 -4.3 OF ANSI /AWWA C110/A21.10 -87 SHALL BE OBTAINED BY THE CONTRACTOR.
AND TRANSMITTED TO THE OWNER.
7. GATE VALVES SHALL BE IRON BODY, BRONZED - MOUNTED, DOUBLE DISC WITH BRONZE
WEDGING DEVICE AND 0 -RING STUFFING BOX (AWWA C500) OR OF RESILIENT SEATED TYPE
(AWWA C509). VALVES SHALL BE DESIGNED FOR A MINIMUM WATER OPERATING PRESSURE OF
200 PSI. GATE VALVES SHALL BE CLOW LIST 14, MUELLER COMPANY NO. A2380 OR M & H.
8. FIRE HYDRANTS SHALL BE COREY TYPE (OPENING WITH THE PRESSURE) OR COMPRESSION
TYPE (OPENING AGAINST PRESSURE) CONFORMING TO AWWA C- 502 -85 WITH A 6 INCH
MECHANICAL JOINT INLET AND A MAIN VALVE OPENING (M.V.O.) OF 5 -1/4 INCH, TWO 2 -1/2
INCH HOSE NOZZLES WITH NATIONAL STANDARD THREADS 7 -1/2 THREADS PER INCH AND ONE
4 INCH PUMPER NOZZLE WITH THE NEW SEATTLE PATTERN 6 THREADS PER INCH, 60
DEGREES V. THREADS: OUTSIDE DIAMETER OF MALE THREAD 4.875 AND ROOT DIAMETER
4.6263. HYDRANTS SHALL HAVE A 1 -1/4 INCH PENTAGON OPERATING NUT OPENED BY
TURNING COUNTER CLOCKWISE (LEFT).
9. THE TWO 2 -1/2 INCH HOSE NOZZLES SHALL BE FITTED WITH CAST IRON THREADED CAPS
WITH OPERATING NUT OF THE SAME DESIGN AND PROPORTIONS AS THE HYDRANT STEM NUT.
CAPS SHALL BE FITTED WITH SUITABLE NEOPRENE GASKETS FOR POSITIVE WATER TIGHTNESS
UNDER TEST PRESSURES.
10. THE 4 INCH PUMPER NOZZLE SHALL BE FITTED WITH A STORZ ADAPTER, 4 INCH SEATTLE
THREAD X 5 INCH STORZ. STORZ ADAPTER SHALL BE FORGED AND /OR EXTRUDED 6061 -T6
ALUMINUM ALLOY, HARDCOAT ANODIZED. THREADED END PORTION SHALL HAVE NO LUGS AND
TWO SET SCREWS 180 DEGREES APART. STORZ FACE TO BE METAL, NO GASKET TO WEATHER.
STORZ CAP TO HAVE SYNTHETIC MOLDED RUBBER GASKET, AND SHALL BE ATTACHED TO
HYDRANT ADAPTER WITH 1/8 INCH, COATED, STAINLESS STEEL, AIRCRAFT CABLE.
11. FIRE HYDRANTS SHALL BE PAINTED WITH TWO COATS OF PAINT. PRESERVATIVE PAINT NUMBER
43 -655 SAFETY YELLOW OR APPROVED EQUAL.
12. PUMPER CONNECTION TO FACE ROADWAY ASSEMBLY.
13. FIRE HYDRANTS SHALL BE INSTALLED PER CITY OF RENTON STANDARD DETAIL FOR FIRE
HYDRANTS, LATEST REVISION.
14. ALL WATERMAINS 12 INCHES AND SMALLER TO MAINTAIN A MINIMUM COVER OF 36 INCHES
BELOW FINISH GRADE. INeHES AND b1RGER SHALL nr MINIMUM OF
A° INGIIES BELOW r, n, GRAB E. WHERE UTILITY CONFLICTS OCCUR, WATERMAINS ARE TO BE
LOWERED TO CLEAR. '
1231FRYARAWENUE
SUMNER, WASHINGTON 90390
T. 253.863.5120 R 253.063.ON.
Nvw.Dermm�tr#.mm
RECOMMENDU
EQ APPROVAL
BYI- ----- --- ------
Date '--------
By, ----------------
Date, --------
DYl----------------
Datet_- __m_ --
BYI----------------
Dat ----------
WATER UTILITY NOTES AND SPECIFICATIONS (CONTINUED):
15. ALL WATERMAINS 6 INCHES AND LARGER IN DIAMETER SHALL BE CLEANED WITH PIPE CLEANING
"PIGS" PRIOR TO DISINFECTION. THE "POLY PIGS" SHALL BE GIRARD INDUSTRIES AQUA
SWAB -AS OR APPROVED EQUAL, 2 LB /CU. FT. DENSITY FOAM WITH 90A DUROMETER
URETHANE RUBBER COATING ON THE REAR OF "PIG" ONLY.
16. "PIGS" SHALL BE CYLINDER SHAPED WITH BULLET NOSE OR SQUARE END. THE CONTRACTOR
WILL PERFORM THE CLEANING OPERATION.
17. ALL WATERMAINS AND SERVICES SHALL BE PRESSURE TESTED TO A MINIMUM OF 200 PSI OR
150 PSI OVER OPERATING PRESSURE, IN ACCORDANCE WITH THE SPECIFICATIONS OF THE CITY
OF RENTON AND THE WASHINGTON STATE HEALTH DEPARTMENT. ALL PRESSURE TESTING SHALL
BE DONE IN THE PRESENCE OF A REPRESENTATIVE OF THE CITY OF RENTON. THE QUANTITY
OF WATER LOST FROM THE MAIN SHALL NOT EXCEED THE NUMBER OF GALLONS PER HOUR
AS LISTED IN CITY OF RENTON STANDARD PLANS & SPECIFICATIONS 7- 11.3(11). THE LOSS IN
PRESSURE SHALL NOT EXCEED 5 PSI DURING 'rHE 2 HOUR TEST PERIOD.
18. ALL WATERMAINS AND SERVICES SHALL BE DISINFECTED BY THE INJECTION OF A 50 PPM
(MINIMUM CONCENTRATION) CHLORINE /WATER SOLUTION. DRY CALCIUM HYPOCHLORITE SHALL
NOT BE PLACED IN THE PIPE AS LAID. CHLORINE SHALL BE METERED /INJECTED IN
ACCORDANCE WITH SECTION 7- 11.3(12)E OR 7- 11.3(12)F OF THE STANDARD SPECIFICATIONS
REFERENCED ABOVE.
19. A PRE - CONSTRUCTION CONFERENCE IS REQUIRED PRIOR TO ANY CONSTRUCTION. A MINIMUM
OF FIVE (5) WORKING DAYS NOTICE IS REQUIRED FOR SCHEDULING.
20. TWENTY -FOUR (24) HOURS NOTICE WILL BE REQUIRED PRIOR TO STARTING NEW
CONSTRUCTION.
21. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SECURE ALL NECESSARY PERMITS PRIOR
TO STARTING CONSTRUCTION.
23. ALL CONNECTION TO EXISTING MAINS IS TO BE ACCOMPLISHED BY THE CITY OF RENTON,
EXCEPT WET TAPS, WHICH MAY BE MADE BY APPROVED WET TAP CONTRACTORS WITH PRIOR
APPROVAL FROM THE PUBLIC WORKS DEPARTMENT. ALL NECESSARY EXCAVATION AND
MATERIALS ARE TO BE SUPPLIED BY THE CONTRACTOR AND BE ON -SITE PRIOR TO CITY
NOTIFICATIONS.
24. INSPECTION WILL BE ACCOMPLISHED BY A REPRESENTATIVE OF THE CITY OF RENTON. IT SHALL
BE THE CONTRACTOR'S RESPONSIBILITY TO NOTIFY DEVELOPMENT SERVICES TWENTY FOUR (24)
HOURS IN ADVANCE OF BACKFILLING ALL CONSTRUCTION. THE CONTRACTOR, AS WELL AS THE
ENGINEERS, SHALL KEEP AS -BUILT DRAWINGS.
25. CONTRACTOR TO PROVIDE PLUGS AND TEMPORARY BLOW -OFF ASSEMBLIES FOR TESTING AND
PURITY ACCEPTANCE PRIOR TO FINAL TIE -IN.
26. ALL JOINT RESTRAINT SYSTEMS (SHACKLE RODS, NUTS, BOLTS, ETC.) SHALL BE AS
MANUFACTURED BY THE STAR MANUFACTURING COMPANY OF COLUMBUS OHIO, OR EQUAL,
APPROVED IN WRITING BY THE PUBLIC WORKS DEPARTMENT.
27. ASPHALT AND CONCRETE STREET PAVING SHALL BE SAWCUT TO A MINIMUM DEPTH OF TWO (2)
INCHES. OIL MAT STREETS MAY BE SPADE CUT. ALL SURFACE CONCRETE, PAVEMENT,
SIDEWALKS, CURB, GUTTERS, AND DRIVEWAY APPROACHES SHALL BE SAWCUT TO A MINIMUM
DEPTH OF TWO (2) INCHES OR REMOVED TO AN EXISTING EXPANSION JOINT.
28. A TEMPORARY COLD MIX ASPHALT PATCH SHALL BE PLACED ON THE DAY OF INITIAL
EXCAVATION WITH A PERMANENT, SEALED PATCH TO BE PLACED, TO CITY OF RENTON POLICY,
WITHIN 10 DAYS. CALL FOR SUBGRADE INSPECTION PRIOR TO PLACEMENT OF FINAL PATCH. *
SANITARY SEWER NOTES AND SPECIFICATIONS:
1. ALL WORK AND WORK MATERIAL SHALL BE IN CONFORMANCE WITH THE STANDARDS AND
SPECIFICATIONS OF THE CITY OF RENTON PLANNING /BUILDING /PUBLIC WORKS DEPARTMENT
AND THE LATEST EDITION OF THE WSDOT /APWA STANDARDS AND SPECIFICATIONS, AS
APPROVED AND MODIFIED BY THE CITY OF RENTON IN THE RENTON STANDARD PLANS &
SPECIFICATIONS. A SET OF APPROVED PLANS SHALL BE KEPT ON SITE AT ALL TIMES DURING
CONSTRUCTION.
2. THE HOURS OF WORK IN THE STREET RIGHT OF WAY SHALL BE PER CITY SPECIFICATIONS ON
WEEKDAYS UNLESS OTHERWISE APPROVED IN WRITING BY THE PLANNING /BUILDING /PUBLIC
WORKS DEPARTMENT. AN APPROVED TRAFFIC CONTROL PLAN MUST BE OBTAINED PRIOR TO
BEGINNING ANY WORK WITHIN PUBLIC RIGHT OF WAY.
3. ALL LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE AND IT SHALL BE THE
CONTRACTOR'S RESPONSIBILITY TO VERIFY THE TRUE AND CORRECT LOCATION SO AS TO AVOID
DAMAGE OR DISTURBANCE.
4. A PRE - CONSTRUCTION CONFERENCE AND A 24 HOUR NOTICE SHALL BE REQUIRED PRIOR TO
STARTING NEW CONSTRUCTION. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SECURE
ALL NECESSARY PERMITS PRIOR TO STARTING CONSTRUCTION. (INSPECTION WILL BE
ACCOMPLISHED BY A REPRESENTATIVE OF THE CITY OF RENTON.) IT SHALL BE THE
CONTRACTOR'S RESPONSIBILITY TO NOTIFY THE PUBLIC WORKS INSPECTOR 24 HOURS IN
ADVANCE OF BACKFILLING ALL CONSTRUCTION.
5. CONTRACTOR IS SOLELY RESPONSIBLE FOR THE MEANS, METHODS AND SEQUENCES OF
CONSTRUCTION AND FOR THE SAFETY OF WORKERS AND OTHERS ON THE CONSTRUCTION SITE,
6. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO OBTAIN STREET USE AND ANY
OTHER RELATED PERMITS PRIOR TO ANY CONSTRUCTION.
7. PLANS APPROVED BY THE CITY OF RENTON, PUBLIC WORKS DEPARTMENT SHALL TAKE
PRECEDENCE OVER ALL OTHER PLANS.
8. A COPY OF THESE APPROVED PLANS MUST BE ON THE JOB SITE WHENEVER CONSTRUCTION IS
IN PROGRESS.
9. THE CONTRACTOR SHALL PROVIDE THE CITY OF RENTON WITH AN AS -BUILT DRAWING OF THE
SANITARY SEWER SYSTEM, WHICH HAS BEEN STAMPED AND SIGNED BY A' LICENSED
PROFESSIONAL ENGINEER OR LICENSED PROFESSIONAL SURVEYOR.
10. BACKFILL SHALL BE PLACED EQUALLY ON BOTH SIDES OF THE PIPE IN LAYERS WITH A LOOSE
AVERAGE DEPTH OF 6 INCHES, MAXIMUM DEPTH OF 8 INCHES, THOROUGHLY TAMPING EACH
LAYER TO 95 PERCENT OF MAXIMUM DENSITY, THESE COMPACTED LAYERS MUST EXTEND FOR
ONE PIPE DIAMETER ON EACH SIDE OF THE PIPE OR TO THE SIDE OF THE TRENCH.
MATERIALS TO COMPLETE THE FILL OVER PIPE SHALL BE THE SAME AS DESCRIBED.
11. OPEN CUT ROAD CROSSINGS FOR UTILITY TRENCHES ON EXISTING TRAVELED ROADWAY SHALL
BE BACKFILLED WITH CRUSHED ROCK AND MECHANICALLY COMPACTED UNLESS OTHERWISE
APPROVED BY THE PUBLIC WORKS INSPECTOR. CUTS INTO THE EXISTING ASPHALT SHALL BE
NEATLINE CUT WITH SAW IN A CONTINUOUS LINE. A TEMPORARY MIX PATCH MUST BE PLACED
IMMEDIATELY AFTER BACKFILL AND COMPACTION. A PERMANENT HOT MIX PATCH SHALL BE
PLACED WITHIN 10 DAYS AND SHALL BE PER CITY OF RENTON CURRENT', STANDARDS.
12. DATUM SHALL BE CITY OF RENTON, 1988 NAVD.
13. ALL DISTURBED AREAS SHALL BE SEEDED AND I
SATISFACTION OF THE DEPARTMENT FOR THE PR
COMPLETION OF CONSTRUCTION.
14. ALL PIPE AND APPURTENANCES SHALL BE LAID ON
ACCORDANCE WITH THE STANDARDS AND SPECIFICAI
PLANNING /BUILDING /PUBLIC WORKS DEPARTMENT At
WSDOT /APWA STANDARDS AND SPECIFICATIONS, AS
RENTON IN THE RENTON STANDARD PLANS & SPEC
NECESSARY LEVELING OF THE TRENCH BOTTOM OR
AS WELL AS PLACEMENT AND COMPACTION OF REQ
GRADE SO THAT THE ENTIRE LENGTH OF THE PIPE
DENSE, UNYIELDING BASE. PIPE BEDDING SHALL BE
THE PIPE.
15. SANITARY SEWER PIPE SHALL BE POLYVINYL
3034, SDR 35, OR DUCTILE IRON CLASS 50,
WASTEWATER UTILITY.
OR OTHERWISE STABILIZED TO THE
OF ON -SITE EROSION AFTER THE
PROPERLY PREPARED FOUNDATION IN
IS OF THE CITY OF RENTON
THE LATEST EDITION OF THE
'ROVED AND MODIFIED BY THE CITY OF
ATIONS. THIS SHALL INCLUDE
E TOP OF THE FOUNDATION MATERIAL,
ED BEDDING MATERIAL, TO UNIFORM
.L BE SUPPORTED ON A UNIFORMLY
:A GRAVEL 6 INCHES ABOVE AND BELOW
(PVC) RUBBER GASKETED ASTM D
OTHERWISE APPROVED BY THE
16. IN UNIMPROVED AREAS, MANHOLE TO EXTEND MINIMUM 6 INCHES AND MAXIMUM 12 INCHES
ABOVE FINISHED GRADE OR MUST HAVE MINIMUM 2' DIAMETER CONCRETE RING POURED AT
GRADE. IN PAVED AREA, COVER MUST SLOPE IN ALL ;DIRECTIONS TO MATCH PAVING.
D- 331505
N. STORM SYSTEM IMPROVEMENT
WATER UTILITY
AND SANITARY SEWER
NOTES AND SPECIFICATIONS
3/21/08
G4
OF
-• --'-
AS SHOWN
_
�w19
e99¢" x.D 1963.991
DATUM
:; CITY OF
_u RENTON
K
Planning /Building /Public Works Dept.
RIPLEY
DESFNEP.
HEZVO
-
... ._
MANN. J.
J. BEIZVOG
DN, E w�
p1ECfE0/7% �D
�
ATAT NIL SCNE
6 Nm ONE IN
S,WE 0W"'
NO.
REVISION
BY
DATE
APPR
"FF �nRS9rc
D- 331505
N. STORM SYSTEM IMPROVEMENT
WATER UTILITY
AND SANITARY SEWER
NOTES AND SPECIFICATIONS
3/21/08
G4
OF