HomeMy WebLinkAboutS-334103>1 It CONSTRUCTION SEQUENCING FOR NEW 18 INCH WAIER LINE SIR 1. INSTALL DEAD-MAN BLOCK ON EXIS71NG 2-12" WATER LINES AT STA. 0+00, SIA. 0+19, STA. 1+71 AND STA. 1+52 FOR LATER INSTALLA77ON OF VALVES AND FINAL CONNECTIONS. ALLOW A41NIMUM 5­a4Y FOR CONCRETE CURING 77ME. 0,� 2. INSTALL NEW 18' WATER LINE FROM ABOUT STA. 0+25 (SOUTH END) TO ABOUT STA. < 1+50 (NORTH END), A MINIMUM OF I FOOT BELOW THE EXISTING SAS MAIN. VERIFY ALL 9�� EXIS77NG PIPING, DIMENSIONS AND ELEVATIONS OF EXISTING 12" LINES TO DETERMINE VER77r.4L BEND REQUIREMENTS AND ASSURE PROPER FIT J. INSTALL THRUST BLOCKS AND DEAD-MAN BLOCKS ON NEW 18' WATER LINE AT Z N5� LOCATIONS SHOWN ON PLAN. LLI 4. CLEAN NEW 18- LINE WITH POLYPIG, PERFORM PRESSURE TEST AND DISINFECT NEW 18' LINE. z LLJ N S. CITY CREW WILL PERFORM NORTH END coNNEcnoN or NEW w LINE To EXISTING z z EASTERLY 12" LINE, INSTALL NEW 12' VALVE AND SHACKLE VALVE TO PREVIOUSLY Z 0 INSTALLED DFJID-M4N BLOCK. SHACKLE NEW 18*xl2" TEE TO 90, SEND AT STA 1+36, &Nh�_ LL_ -i CONTRACTOR SHALL PERFORM ALL EXC4VATION, SHORING, TRENCH DEWATERING, DISPOSAL o o ui OF UNSUITABLE MATERIALS, PLACEMENT OF IMPORT 15ACKFILL AND SHALL PROVIDE ALL REQUIRED 947ERALS AND FITTINGS TO COMPLETE THE CONNEC77ONS TO THE EXIS17NG WATER LINES, LJJ U) 6 EXISTING EASTERLY 12- LINE, INSTALL NEW 18- 45' BEND, 18'x12' REDUCER, 12" VAL% CITY CREW WILL PERFORM SOUTH END, STA. 0+19, CONNEC77ON OF NEW 18" LINE TO 12"XI2" TEE AND SHACKLE ALL FITTINGS AND VALVES TO PREVIOUSLY INSTALLED DEAD-W BLOCKS 17- ON EXIS77NG 12" AND NEW 18' WATER WINS. :z < 7. CITY CREW WILL PERFORM NORTH END, SIA. 1+71, CONNEC71ON OF NEW 12- LINE TO LINE, INSTALL NEW 12- 90' BEND, 12- VALVES AND SHACKLE ALL EXISTING WESTERLY 12 FITTINGS AND VALVES TO PREVIOUSLY INSTALLED DEAD-MAN BLOCKS ON EXISTING 12' LINE AND TO 12* TEE AT STA 1+52. 8. CITY CREW WILL INSTALL 12- 90' BEND AT SOUTH END, STA. 0+00, OF EXISTING 12- WESTERLY LINE AND INSTALL END-CAP ON EXIS77NG LINE TO BE ABANDONED. SHACKLE 90' BEND TO PREVIOUSLY INSTALLED DEAD-MAN BLOCKS ON EXISTING 120 LINE AND TO NEW VALVE AND TEE AT STA 0+19. tu 0- 0- 4"x 2 1/2" FIRE DEPARTMENT DOUBLE CONNECTION FOR STAND PIPE WITH BREAKABLE CAST IRON HOSE CAPS. z ONE EACH SIDE EQUAL TO GRINNEL FIG. 0 1333. 1682 WITH HOSE CAPS FIG. 4" ADAPTER, FL.x SCREWED ONE EACH SIDE id> of 4"x 4"x 4" BULL HEAD TEE, FL. 4" PIPE FL.x FL, TO BUILDING� E3 u I LT PRECAST CONCRIETE VAULT WITH LOCKING CAST IRON COVER (H20 RATED), NO WE. CONTRACTOR RESPONSIBLE FOR SIZING VAULT TO FIT CHECK AND DRIP VALVES. SWING-TYPE GRAVITY OPERATED CHECK ILVE 3/4- STRAIGHT SALL DRIP VALVE NPT-TAPPED INTO INVERT OF PIPE c; t�i�EIRE DEPARTMENT CONNECTION z 1\ �-o N.T.S. RESTORE ROADWAY PER CITY OF RENTON STANDARDS NEW FIRE HYDRANT ASSEMBLY CONNECT TO EX. 80 WATER TAPPING TEE 1-80XB"x6 1-6* TAPPING GATE VALVE I-THRUST BLOCK EX. SIDE SEWER -SEE CONSTRUCTION NOTE 1 RIM I E 3.5 RIM 12.8 142.72 4 IE=36.42 (ASSUMED) C3.0 -SEE CONSTRUCTION NOTE: 1 Q3@2 I 55LF-6"PVC 02.00%- �EPLACE EX. WATER METER WITH 1-1/2- MEIER AND TRAFFIC RATED COVER 63LF 1-1/2-DOMESTIC- WATER/SEWER CROSSING IE(W)=39.65 37LF-4"DI WATER IE(SS)=37.40 < - 11 14LF-4"Di cq FIRE SPRINKLER WATER I RESTORE ROADWAY I PER CITY OF RENTON STANDARDS m 0 4 4"PIV Lf) G3.1 CONNECT TO EY. 8WATER 1-13"X13"WrAPPING TEE > < 1, CID 1_4"TAPPING GATE VALVE 1-THRUST BLOCK < Lo WATER/SEWER CROSSING SC IE(W)- 39.90 > b Z_� , .2 RIM=4&7�9- G IE=37.80 43.53 0 O'l 0 E(SS)=37.56 U k < LL- �':/F ol� I _-\'Gi� N D D L I E S S OR i3i N G -v cf: NiTON R�_CORD�_. 'I I "IIN BUILDING FOOTPRINT REMOVE WATER MAINS WATERMAIN STA 0+0 - S CONSTRUCTION NOTE 4 'n M NO[ VISIBLE 0 i: ITRW IE=36.70 FIX Bu IFF 6' 7/ 7­11V I W A2 ------- 7-7 7, T VER CROSSING 15 1 90' - 26 'A� 4 3.27 PNC '3 "p kc 0 P! AN _R Xqt� r 1-4"x9(VrBEND (MJxM 1 -THRU BLOCI 1-THRUST BLOCK DI 13LF-4"DI WATER 4"DDCV-SEE CONSTRUCTION N07 3 L , IAT-- !Ns ­_l 20- 4"DI WATER 4 3 FF=45.00(i ryt) 1 st LEVEL 2 4 1 G -S FT - 12nd LEVEL 3815 1 �_ 't� 5rd LEVPL 385-9,_,SQ_�1--,FT YD 1�72 �? I u l8,xl2! PEXPEk mi ­7 FROM ALL�� ALL 90' w :12"- - - - - - - F4 C PACT/�OMPA( A�_ -I R6beH IRODS� TO EX. 12'0 WATER V 8'xl8-xl2-rEE( 1.8 2-12 2" GV 5 a-p, 1-18"xl2* ER J) lixmi 1 -TH BLOC N-B K- 'ODI 43,79 T.. 16LF-18'ODI CONCR ANCHOI 1 2 T.O. �O�P__ / 11 (18" UCER '9LF-1 "o IP P0E (M MEADMAN <l'.oO'MI . DEADMAN on 18" x 42.57 4,2 FRO DEADMAN-�'_� ALL 8" Drt%yE, 1 ALLi� DNVJ IA41_1118" DI HAVE �, RISER x 77 SPUR nv,p PORUJ'l 01 EASEK4EN F OVER _Rly P P, Off 114 61 T I CUT & CONE TO EX.f/ 12"0 x9TBE] 12", 1 -THR i `�_ - 7��l p 1 41-22 I I '�! ') / 3.1,9 -- ,,, 11000, r'- �1' STA 1 x 1:THx9O`B.ELNo, SEE CONSTRUCTION NdTE/6 ') 4M3 WATERMAIN/GAS CROSSING/ 91LF-18"ODIP , / CONSTRUCT ANCHOR BLOCK WITH TIE RODS AROUND EXISTING WATER LINE. ALLOW A MINIMUM OF 5 DAYS CURING nME PRIOR TO TESTING. BACKFILL AND COMPACT FACE OF WALL TO 95% MAX. DRY DENSITY. PLACE CONCRETE 12" PIPE AGAINST UNDISTURBED EARTH BOTH FACES CLASS 5 1/2 SACK CONCRErE 3000 PSI MIN 6- SHACKLE RODS FOR '� '�2 PIPE PLAN VIEW #4 REBAR 8- D.C. E.W. CENTER IN CONCRErE NSTINIG PIPE -3/4' RODS t- --4- T 4_�/4' RODS 6-3/4* R ' DOS 4­4­4­4-: 4­�4­�-4 81 J r'� c INVINOi msit CONSTRUCTION NOTES JXmi -12 1 "x J) 1 45' �\�NWATERMAIN/GAS CROSSING 1pt. �.lxm' M2 9(r B -MAN 8' mi 1. RE-USE EX. STUB IF IT IS 6"OMIN. AND IE=36.42 (AT CONNECTION Mj I DE mi SEE CONSTRUCTION NOTE 6 7- Z2 SLEEVE POINT) OR LOWER. OTHERWISE, REPLACE EX. STUB AND RECONNECT TO C"3.0 (:Iyp) 12" 45* 12" GV SEWER MAIN (USE 8"x8N6" STRAIGHT TEE, IE= 35.15 (EX.81, MjXMj 8" 45! MjxMj SUEE�/E JF�.35.23 (NEW 61). SEE NOTE 2 BELOW. 12 12"X8" 12" GV mi TEE MjXMj MjXMj T_ (IS 4" PIPE 36"TO 42" Bp\o FL. x SCREW 0+19 FOUND 1 1/2- BRASS DISK I- D-MAN B CX I i Q - 1-1 E(MJ JxMJ) W/PUNCH IN CASE. TPEPP I VISITED 6/13/03 1-02� . 4 vi I 1-12"A R(MJxR C: 2-12-G VALVE(FL 131.06,1 S 1-12" 8"R UCER(I -WIT4,C8 RODS I- x45!BEN Jxh 1" 90 BEN FL7---,.� BETWEEN 0+19 1 RUST BLOC E BIEM R" I I CONCRETTE E SUPPORT, 12- HIGH (MIN) 1-1/2' DRAIN ROCK, 12" MIN. DEPTH .12LJ 2. ALL SEWER PIPES SHALL BE 6"PVC ASTM D3034 SDR35 INSTAU_ED WITH 5'MIN. COVER AND 2% MIN. SLOPE. <8LOCK 3. INSTALL DDCV INSIDE THE BUILDING (MECH. ROOM) WITH OUTSIDE REMOTE READER FOR BYPASS METER. 4. SEE DErAJL2 ON SHEET C3.1 FOR 18"0 WATERMAN PROFILE. 5. CONTRACTOR TO POTHOLE EX. 12'0 WATERMAINS TO VERIFY DEPTH AND LOCATIONS PRIOR TO INSTALLING WATERMAIN. IF CONDITIONS ARE DIFFERENT THAN SHOWN ON THE PLANS, CONTACT THE ENGINEER AND THE CITY FOR REVISIONS. 6. CONTRACTOR SHALL POTHOLE EX. 8"0 GAS MAIN TO VERIFY DEPTH AND LOCATION PRIOR TO INSTAILUNG WATERMAN. WATERMAIN SHALL BE 0 10 20 MIN. 1.00' ABOVE OR BELOW GAS MAIN PER PSE STANDARDS. 7. CONTRACTOR TO COORDINATE ALL WATERMAIN TIE-INS WITH CITY OF SCALE: 1" 10'-0" RENTON WATER DEPARTMENT C3.0 SANITARY SEWER AND WATER PLAN -SrA 0+42 g \TMCAL CONCRET DEADMAN ANCHOR 17 1-18'x4FBEND(MJxMJ) (PER MY OF RENTON WATER DEPARTMiWT) _47 1 -THRUST BLOCK 18" mixw JCER 20LF-18"ODIP DEADMAN 12' 11 1/4 BLOCK INVINOi msit CONSTRUCTION NOTES JXmi -12 1 "x J) 1 45' �\�NWATERMAIN/GAS CROSSING 1pt. �.lxm' M2 9(r B -MAN 8' mi 1. RE-USE EX. STUB IF IT IS 6"OMIN. AND IE=36.42 (AT CONNECTION Mj I DE mi SEE CONSTRUCTION NOTE 6 7- Z2 SLEEVE POINT) OR LOWER. OTHERWISE, REPLACE EX. STUB AND RECONNECT TO C"3.0 (:Iyp) 12" 45* 12" GV SEWER MAIN (USE 8"x8N6" STRAIGHT TEE, IE= 35.15 (EX.81, MjXMj 8" 45! MjxMj SUEE�/E JF�.35.23 (NEW 61). SEE NOTE 2 BELOW. 12 12"X8" 12" GV mi TEE MjXMj MjXMj T_ (IS 4" PIPE 36"TO 42" Bp\o FL. x SCREW 0+19 FOUND 1 1/2- BRASS DISK I- D-MAN B CX I i Q - 1-1 E(MJ JxMJ) W/PUNCH IN CASE. TPEPP I VISITED 6/13/03 1-02� . 4 vi I 1-12"A R(MJxR C: 2-12-G VALVE(FL 131.06,1 S 1-12" 8"R UCER(I -WIT4,C8 RODS I- x45!BEN Jxh 1" 90 BEN FL7---,.� BETWEEN 0+19 1 RUST BLOC E BIEM R" I I CONCRETTE E SUPPORT, 12- HIGH (MIN) 1-1/2' DRAIN ROCK, 12" MIN. DEPTH .12LJ 2. ALL SEWER PIPES SHALL BE 6"PVC ASTM D3034 SDR35 INSTAU_ED WITH 5'MIN. COVER AND 2% MIN. SLOPE. <8LOCK 3. INSTALL DDCV INSIDE THE BUILDING (MECH. ROOM) WITH OUTSIDE REMOTE READER FOR BYPASS METER. 4. SEE DErAJL2 ON SHEET C3.1 FOR 18"0 WATERMAN PROFILE. 5. CONTRACTOR TO POTHOLE EX. 12'0 WATERMAINS TO VERIFY DEPTH AND LOCATIONS PRIOR TO INSTALLING WATERMAIN. IF CONDITIONS ARE DIFFERENT THAN SHOWN ON THE PLANS, CONTACT THE ENGINEER AND THE CITY FOR REVISIONS. 6. CONTRACTOR SHALL POTHOLE EX. 8"0 GAS MAIN TO VERIFY DEPTH AND LOCATION PRIOR TO INSTAILUNG WATERMAN. WATERMAIN SHALL BE 0 10 20 MIN. 1.00' ABOVE OR BELOW GAS MAIN PER PSE STANDARDS. 7. CONTRACTOR TO COORDINATE ALL WATERMAIN TIE-INS WITH CITY OF SCALE: 1" 10'-0" RENTON WATER DEPARTMENT C3.0 SANITARY SEWER AND WATER PLAN