WATER UTILITY- GENERAL NOTES
1. ALL WORK MATERIAL SHALL BE IN CONFORMANCE WITH THE STANDARDS AND
SPECIFICATIONS OF THE CITY OF RENTON UTILITY DEPARTMENT AND THE
LATEST EDITION OF THE WSDOT /APWA STANDARDS AND SPECIFICATIONS, AS
APPROVED BY THE CITY OF RENTON. A SET OF THE APPROVED PLANS SHALL BE
KEPT ON SITE AT TIMES DURING CONSTRUCTION.
2. THE HOURS OF WORK IN THE STREET RIGHT -OF -WAY SHALL BE LIMITED TO 8:30
AM TO 3:30 PM ON WEEK DAYS UNLESS OTHERWISE APPROVED IN WRITING BY
THE TRANSPORTATION DIVISION AT 277 -6222. ALL STREET CLOSURES, PARTIAL
OR FULL, SHALL BE APPROVED BY THE TRANSPORTATION DIVISION AT 277 -6222 24
HOURS IN ADVANCE. THE POLICE DEPARTMENT, FIRE DEPARTMENT, AND 911
SHALL BE NOTIFIED 24 HOURS IN ADVANCE.
3. ALL LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE AND IT
SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE TRUE AND
CORRECT LOCATION SO AS TO AVOID DAMAGE OR DISTURBANCE. FOR UTILITY
LOCATE CALL 48 -HOURS LOCATORS. 1800- 424 -5555.
4. ALL WATER MAIN PIPE TO BE CEMENT LINED DUCTILE IRON PIPE CONFORMING
TO AWWA C110 AND C111 OR LATEST REVISION, THICKNESS CLASS 52. CEMENT
LINING AND SEAL COATING SHALL CONFORM TO AWWA C104 OR LATEST
REVISION. PIPE JOINT TO BE PUSH -ON OR MECHANICAL JOINT. BEDDING TO BE
CLASS C. ALL DUCTILE IRON PIPE SHALL BE POLYETHYLENE WRAPPED PER
ANSI /AWWA C105 -77 STANDARDS.
5. CAST IRON FITTINGS SHALL BE CEMENT LINED, PRESSURE RATED AS NOTED ON
PLANS, AND IN ACCORDANCE WITH ANSI /AWWA C110/A21.10 -82. CEMENT SHALL
BE IN ACCORDANCE WITH ANSI /AWWA C104/A21.4 -85. IF FITTINGS ARE 3 INCHES
TO 12 INCHES IN DIAMETER AND HAVE A MECHANICAL JOINTS, THE FITTINGS
SHALL BE IN ACCORDANCE WITH EITHER ANSI /AWWA C710/A21.10 -82 OR
ANSI /AWWA C153/A21.53 -84. 3 INCHES TO 12 INCHES DIAMETER FITTINGS WHICH
HAVE MECHANICAL JOINTS AND/ OR FLANGES JOINTS SHALL BE IN ACCORDANCE
WITH ANSI /AWWA G110/A21.10.82 OR A COMBINATION OF ANSI /AWWA
C110/A21.10.82 AND ANSI /AWWA C153/A21.53 -84 SUCH THAT THE PORTION OF THE
FITTING WITH A MECHANICAL JOINT(S) MAY BE IN ACCORDANCE WITH
ANSI /AWWA C153/A21.53 -84 AND THAT PORTION OF THE FITTING WITH FLANGED
JOINT(S) SHALL BE IN ACCORDANCE WITH ANSI /AWWA C110/A21.10 -82.
ACCEPTANCE TESTING IN ACCORDANCE WITH SECTION OF ANSI /AWWA
C153/A21.53 -84 OR WITH SECTION 10 -4.3 OF ANSI /AWWA C110/A21.10 -82 SHALL BE
OBTAINED BY THE CONTRACTOR AND TRANSMITTED TO THE OWNER.
6. GATE VALVES SHALL CONFORM TO AWWA C500 AND SHALL BE IRON BODY,
BRONZED - MOUNTED, DOUBLE DISC WITH BRONZE WEDGING DEVICE AND O -RING
STUFFING BOX. VALVES SHALL DESIGNED FOR A MINIMUM WATER OPERATING
PRESSURE OF 200 PSI. GATE VALVES SHALL BE CLOW LIST 14, MUELLER
COMPANY NO A2380, OR M & H. ALL VALVES 12" IN DIAMETER AND LARGER
SHALL BE INSTALLED IN AS VAULT. SEE WATER STANDARD DETAIL FOR 12" GATE
VALVE ASSEMBLY VAULT AND 1" BYPASS INSTALLATION.
7. FIRE HYDRANTS SHALL BE COREY TYPE (OPENING WITH THE PRESSURE)
CONFORMING TO AWWA C- 504 -80 WITH A 6 INCH INLET AND A M.V.O. OF 5 INCHES,
TWO 2 -1/2 INCH HOSE NOZZLES WITH NATIONAL STANDARD 7 INCH, 60 DEGREES
V, THREADS, O.D. THREAD 4.875 AND ROOT DIAMETER 4.6263, 1 -3/4 INCH
PENTAGON OPERATING NUT OPENED BY TURNING COUNTER CLOCKWISE (LEFT).
8. ALL WATER MAIN 10 INCHES AND SMALLER TO MAINTAIN A MINIMUM COVER OF
36" BELOW FINISH GRADE. ALL WATER MAIN 12 INCHES AND LARGER SHALL BE
AT A MINIMUM OF 48 INCHES BELOW FINISH GRADE. WHERE UTILITY CONFLICTS
OCCUR, WATER MAINS ARE TO BE LOWERED TO CLEAR.
9. ALL WATER MAINS SIX (6 ) INCHES IN DIAMETER OR LARGER SHALL CLEANED
WITH PIPE CLEANING "PIGS" PRIOR TO DISINFECTION. THE "POLY PIGS" SHALL BE
GIRARD INDUSTRIES AQUA SWAB -AS OR APPROVED EQUAL, 2 LB /CU. FT. DENSITY
FOAM WITH 90A DUROMETER URETHANE RUBBER COATING ON THE OF THE "PIG'
ONLY. "PIGS" SHALL BE CYLINDER SHAPED WITH BULLET NOSE OR SQUARE END.
THE CONTRACTOR WILL PERFORM THE CLEANING OPERATION.
10. ALL WATER MAINS AND SERVICES SHALL BE PRESSURE TESTED TO A MINIMUM
OF 200 PSI OR 150 PSI OVER OPERATING PRESSURE, IN ACCORDANCE WITH THE
SPECIFICATIONS OF THE CITY OF RENTON AND THE WASHINGTON STATE HEALTH
DEPARTMENT. ALL PRESSURE TESTING SHALL BE DONE IN THE PRESENCE OF A
REPRESENTATIVE OF THE CITY OF RENTON.
11. ALL WATER MAINS AND SERVICES SHALL BE DISINFECTED BY THE INJECTION OF
A 50 PPM (MINIMUM CONCENTRATION) CHLORINE /WATER SOLUTION. DRY
CALCIUM HYPOCHLORITE SHALL NOT BE PLACED IN THE PIPE AS LAID. CHLORINE
SHALL BE METERED /INJECTED IN ACCORDANCE WITH SECTION 7- 11.3(12)E OR 7-
11.3(12) F OF THE STANDARD SPECIFICATIONS REFERENCED IN 1 ABOVE.
12. A PRECONSTRUCTION CONFERENCE IS REQUIRED PRIOR TO ANY CONSTRUCTION.
A MINIMUM OF 10(TEN) WORKING DAYS NOTICE IS REQUIRED FOR SCHEDULING.
PRIOR TO SCHEDULING THE PRECON, A PERMIT INFORMATION SHEET MUST BE
SUPPLIED TO THE UTILITY ENGINEER'S OFFICE. TWENTY -FOUR HOUR NOTICE
WILL BE REQUIRED PRIOR TO STARTING NEW CONSTRUCTION.
13. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SECURE ALL NECESSARY
PERMITS PRIOR TO STARTING CONSTRUCTION.
14. INSTALLATION OF CORPORATE STOPS, WATER SERVICES, LINES AND METERS
SHALL NOT DONE UNTIL ALL SERVICE AGREEMENTS, METER APPLICATIONS,
CONSTRUCTION PERMITS, AND PAYMENT OF FEES HAVE BEEN MADE TO THE
CITY OF RENTON.
15. ALL CONNECTION TO EXISTING MAINS TO BE ACCOMPLISHED BY THE CITY OF
RENTON, EXCEPT WET TAPS WHICH MAY BE MADE BY APPROVED WET TAP
CONTRACTORS WITH PRIOR APPROVAL FROM THE WATER UTILITY SECTION. ALL
NECESSARY EXCAVATION AND MATERIALS TO BE SUPPLIED BY THE
CONTRACTOR AND BE ON -SITE PRIOR TO CITY NOTIFICATIONS.
16. INSPECTION WILL BE ACCOMPLISHED BY A REPRESENTATIVE OF THE CITY OF
RENTON. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO NOTIFY THE CITY
INSPECTOR 24 HOURS IN ADVANCE OF BACKFILLING ALL CONSTRUCTION. THE
CONTRACTOR AS WELL AS THE ENGINEERS SHALL KEEP AS -BUILT DRAWINGS.
17. CONTRACTOR TO PROVIDE PLUGS AND TEMPORARY BLOW -OFF ASSEMBLIES FOR
TESTING AND PURITY ACCEPTANCE PRIOR TO FINAL TIE -IN.
18. ALL JOINT RESTRAINT SYSTEMS (SHACKLE RODS, NUTS, BOLTS, ETC.) SHALL BE
MANUFACTURED BY THE STAR MANUFACTURING COMPANY OF COLUMBUS OHIO
OR EQUAL APPROVED IN WRITING BY THE WATER UTILITY SECTION.
WATER UTILITY- GENERAL NOTES CONTD.
19. ASPHALT AND CONCRETE STREET PAVING SHALL BE SAWCUT TO A MINIMUM
DEPTH OF TWO INCHES. OIL MAT STREETS MAYBE SPADE CUT. ALL SURFACE
CONCRETE, PAVEMENT, SIDEWALKS, CURBS, GUTTERS, AND DRIVEWAY
APPROACHES SHALL BE SAWCUT TO A MINIMUM DEPTH OF TWO INCHES OR
REMOVED TO AN EXISTING EXPANSION JOINT.
20. A TEMPORARY COLD MIX ASPHALT PATCH SHALL BE PLACED ON THE DAY OF
INITIAL EXCAVATION WITH A PERMANENT, SEALED PATCH TO BE PLACED, TO
CITY OF RENTON POLICY, WITHIN TEN DAYS. CALL FOR SUBGRADE INSPECTION
PRIOR. TO PLACEMENT OF FINAL PATCH. TRENCHES WILL NOT BE LEFT OPEN
OVER NIGHT WITHOUT PRIOR WRITTEN APPROVAL OF THE INSPECTOR.
21. FOR CITY PROJECTS SUCH TELEMETRY CONDUIT, THE PVC PIPE USED SHALL BE
SCHEDULE 40 IN UNIMPROVED AREAS AND SCHEDULE 80 UNDER IMPROVED
AREAS. ALL CHEMICAL PROCESS LINES SHALL BE SCHEDULE 80 PVC PIPE.
SANITARY SEWER NOTES AND SPECIFICATIONS
1. ALL WORK MATERIALS SHALL BE IN CONFORMANCE WITH THE STANDARDS SAND
SPECIFICATIONS OF THE CITY OF RENTON AND THE LATEST EDITION OF THE
WSDOT /APWA STANDARDS AND SPECIFICATIONS..
2, THE HOURS OF WORK IN THE STREET RIGHT -OF -WAY SHALL BE LIMITED TO 8:30
A.M. TO 3:30 P.M. ON WEEKDAYS UNLESS OTHERWISE APPROVED IN WRITING BY
THE TRANSPORTATION DIVISION AT 277 -6222. ALL STREET CLOSURES; PARTIAL
OR FULL, SHALL. BE APPROVED BY THE TRANSPORTATION DIVISION 24. HOURS IN
ADVANCE. THE POLICE DEPARTMENT, FIRE DEPARTMENT, AND 911 SHALL BE
NOTIFIED 24 HOURS IN ADVANCE. -
3. ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH "STANDARD
SPECIFICATIONS FOR MUNICIPAL PUBLIC WORKS CONSTRUCTION" PREPARED BY
WASHINGTON STATE CHAPTER AMERICAN PUBLIC WORKS ASSOCIATION, LATEST
EDITION (APWA) AND THE CITY OF RENTON STANDARD SPECIFICATIONS.
4. ALL LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE AND IT
SHALL BE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE TRUE AND CORRECT
LOCATION SO AS TOT AVOID DAMAGE OR DISTURBANCE.
5. A PREPCONSTRUCTION CONFERENCE AND A 24 HOUR NOTICE SHALL BE
REQUIRED PRIOR TO STARTING NEW CONSTRUCTION. IT SHALL BE THE
CONTRACTOR'S RESPONSIBILITY TO SECURE ALL NECESSARY PERMITS PRIOR TO
STARTING CONSTRUCTION. (INSPECTION WILL BE ACCOMPLISHED BY
REPRESENTATIVE OF THE CITY OF RENTON.) IT .SHALL BE THE CONTRACTOR'S
RESPONSIBILITY TO NOTIFY THE CITY INSPECTOR 24 HOURS IN ADVANCE OF
BACKFILLING ALL CONSTRUCTION.
6. CONTRACTOR IS SOLELY RESPONSIBLE FOR THE MEANS, METHOD AND
SEQUENCES OF CONSTRUCTION AND FOR THE SAFETY OF WORKERS AND OTHERS
ON THE CONSTRUCTION SITE.
7. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO OBTAIN STREET USE
AND ANY OTHER RELATED PERMITS PRIOR TO ANY CONSTRUCTION,
8.. PLANS APPROVED BY THE CITY OF RENTON, DEVELOPMENT SERVICES DIVISION,
SHALL TAKE PRECEDENCE OVER ALL OTHER PLANS.
9. A COPY OF THE THESE APPROVED PLANS MUST BE ON THE JOB SITE WHENEVER
CONSTRUCTION IS IN PROGRESS.
10. THE CONTRACTOR SHALL PROVIDE THE CITY OF RENTON WITH AN AS -BUILT OF
THE SANITARY SEWER SYSTEM WHICH HAS BEEN STAMPED AND SIGNED BY A
LICENSED ENGINEER OR LICENSED PROFESSIONAL SURVEYOR.
11. BACKFILL SHALL BE PLACED EQUALLY ON BOTH SIDES OF THE PIPE IN LAYERS
WITH LOOSE AVERAGE DEPTH OF 6 INCHES, MAXIMUM DEPTH OF 8 INCHES,
THOROUGHLY TAMPING EACH LAYER TO 95 PERCENT OF MAXIMUM DENSITY.
THESE COMPACTED LAYERS MUST EXTEND FOR ONE PIPE DIAMETER ON EACH
SIDE OF THE PIPE OR TOT HE SIDE OF THE TRENCH. MATERIALS TO COMPLETE
THE FILL OVER PIPE SHALL BE THE SAME AS DESCRIBED.
12. OPEN CUT ROAD CROSSINGS FOR UTILITY TRENCHES ON EXISTING TRAVELED
ROADWAY SHALL BE BACKFILLED WITH CRUSHED ROCK AND MECHANICALLY
COMPACTED. CUTS INTO THE EXISTING ASPHALT SHALL BE NEATLINE CUT WITH
SAW IN A CONTINUOUS LINE. A TEMPORARY MIX PATCH MUST BE PLACED
IMMEDIATELY AFTER BACKFILL AND COMPACTION. A PERMANENT HOT MIX
PATCH SHALL BE PLACED WITHIN 10 DAYS AND SHALL PER CITY OF RENTON
CURRENT STANDARDS.
13, DATUM SHALL BE CITY OF RENTON, U.S.C. AND G.S.
14. ALL DISTURBED AREAS SHALL BE SEEDED AND IffiL6hL9* OTHERWISE
STABILIZED TO THE SATISFACTION OF THE DEPARTMENT FOR THE PREVENTION
OF ON -SITE EROSION AFTER THE COMPLETION OF CONSTRUCTION.
15. ALL PIPE AND APPURTENANCES SHALL BE LAID ON A PROPERLY PREPARED
FOUNDATION IN ACCORDANCE WITH SECTION 7- 02.3(1) OF THE CURRENT STATE
OF WASHINGTON STANDARD SPECIFICATIONS FOR ROAD AND BRIDGES
CONSTRUCTION. THIS SHALL INCLUDE NECESSARY LEVELING OF THE TRENCH
BOTTOM OR THE TOP OF THE FOUNDATION MATERIAL AS WELL AS PLACEMENT
AND COMPACTION OF REQUIRED BEDDING MATERIAL TO UNIFORM GRADE SO
THAT THE ENTIRE LENGTH OF THE PIPE WILL BE SUPPORTED ON A UNIFORMLY
DENSE UNYIELDING BASE. PIPE BEDDING SHALL BE PEA GRAVEL 6" ABOVE AND
BELOW THE PIPE.
16. SANITARY SEWER PIPE SHALL BE POLYVINYL CHLORIDE (PVC) RUBBER
GASKETED ASTM D 3034, SDR 35, OR DUCTILE IRON CLASS 50.
17. IN UNIMPROVED AREAS, MANHOLES TO EXTEND MINIMUM 6 INCHES ABOVE
FINISHED GRADE. IN PAVED AREA, COVER MUST SLOPE IN ALL DIRECTIONS TO
MATCH PAVING.
ROLL 2,0_6
FUTURE
r6"D NG SEWER PIPE BUILDING SEWER
- w 2 "x 4" STUD SERVICE MARKER PAINT UPPER
SIDE OUTLET oo' PORTION"WHITE ANS STENCIL ON SIDE
21 WORDING'SEWER" WITH 3" HIGH BLACK LETTERS.
AND #6 WIRE WRAPPED AROUND THE STUD AND
TOP OF THE STUD.
E APPROVED BY THE CITY, MAKE TAP THROUGH CAST
URED TO SEWER MAIN WITH STAINLESS STEEL BANDS
WHEN CONNECTING NEW SIDE SEWERS TO EXISTING MAIN.
VITRIFIED CLAY, PLAIN AND REINFORCED CONCRETE, D7 PIPE AND Cl
PIPE SEWER MAINS ARE TO BE CORE DRILLED
60" ALLOWABLE MAX.
FOR CAST IRON PIPE
OR DUCTILE IRON PIPE.
1:3:5 MIX n° ��•(NO 0
N
CONCRETE } GK
BLOCKING
29 MIN SLOPE
6" SIDE OUTLET TEE / HORIZONTAL
6" MIN.
SEWER MAIN LSEWER MAIN
CONCRETE BLOCKING ANGLE
OF TEE AT MAIN OVER 25 TYPICAL SIDE SEIVER ELEVATION
NOTE:
UNLESS OTHERWISE SHOWN ON PLAN, SIDE SEWER SHALL HAVE A MINIMUM 2.5' COVER AT PROPERTY
LINE OR 3 -5' LOWER THAN THE LOWEST HOUSE ELEVATION, WHICHEVER IS LOWER.
LEVEL ALL GROUND
MIN 3' RADIUS ;
LEVEL ALL GROUND,'
MIN 3' RADIU
1 5° STORTZ
�6 1
ONE MAN ROCK e
e
1
6�
7.
CUT FILL
HYDRANT LOCATION IN CUT OR FILL
FIRE HYDRANT SHALL BE COREY -TYPE EQUAL TO IOWA F -5110
OR COMPRESSION TYPE SUCH AS CLOW MEDALLION; M & H 929
AND MUELLER SUPER CENTURION 200 WITH 6' MECHANICAL JOINT
5 -1/4" MAIN VALVE OPENING. TWO 2 -i/2" HOSE CONNECTIONS
NATTfIONAL STANDARD THREADS. 4° PUMPER CONNECTION CITY OF
SEATTLE THREADS WITH A STORTZ ADAPTOR, 4" SEATTLE THREAD
X 5' STORK, ATTACHED WITH 1/8" STAINLESS STEEL CABLE.
1 -1/4" PENTAGON OPERATING NUT. FIRE HYDRANT TO BE
PAINTED WITH TWO COATS OF PAINT. PRESERVATIVE
PAINT No. 43 -655 SAFETY YELLOW OR APPROVED EQUAL.
PUMPER CONNECTION TO FACE ROADWAY ASSEMBLY.
FIRE HYDRANT EXTENSION TO BE USED IF REQUIRED
WATER MAIN IF ADDITIONAL ADJUSTMENT IS
REQUIRED, INSTALL 2 -2" CLOSE
NIPPLE AND 2 -2" 90' BEND, SCREWED
2" CLOSE NIPPLE
AT THIS POINT. FIELD LOCATE
- CONCRETE METER BOX
2" CLOSE NIPPLE
2' 90' ELBOW
2" 90' ELBOW
2" GALVANIZED AS REQUIRED
CONCRETE BLOCKING
PLAN
PLAN
VALVE NUT EXTENSION AS REQUIRED CONCRETE SIDEWALK
TWO PIECE CAST IRON VALVE
EQUAL TO OLYMPIC FOUNDRY CO.
(SEE DWG BR46 / PAGE B090)
GROUND UN
STANDARD 8" TOP SECTION, WITH
6" MAX.
REGULAR BASE SECTION LENGTH
TO FIT.
2" GATE VALVE, SCREWED
2 -1/2" NST (HOSE)
2" GALVANIZED
BLOW -OFF HYDRANT EQUAL TO
PIPE 12" LONG
N78 KUPFERLE FOUNDRY CO.
2" CLOSE NIPPLE
2 "x2 "x2" TEE
BETWEEN CAP OR PLUG
AND 2" 90' ELBOW
2" CLOSE NIPPLE BEWTEEN
TEE AND 90' ELBOW.
INSTALL 4 MIL POLYETHYLENE
2" 90' ELBOW
PLASTIC COVER OVER WASHED
GRAVEL. CUT HOLE FOR PIPE
2" GALVANIZED PIPE
18"
c° LONG
0 o eu P. 0
18" MAX.
z" cAP WITH 1/8"
TAP FOR DRAIN
10 CU. FT. WASHED GRAVEL PASSING
1 -1/2' AND RETAINED ON 1/4" MESH
FOR DRAIN
ELEVATION
g9g9k gggL
mwa n..a , ca. . r
NOTE:
A -A „ °a" a
M. 4 T _1
I NOTEN,w
� /�- k �' Tfl}eq EEflncE
,n om dr»
I-- 18" TO 20" ►�Ldt� BEHIND BACK OF CURB 3Ar HAIL CE
\ I OR 12" BEHIND BACK OF SIDEWALK DETATF. NO MIA
THAT IS ADJACENT TO CURB
MAX
MIN
1
CONCRETE BLOCKING
i
12F1
16" x 8" x 4" MININUM --7
CONCRETE
UNDER HYDRANTK 1/3 CU. YD. WASHED DRAIN'ROCK (3" TO 3/
FM =R!"1L\ 1 L'lL LY DETAIL.''ENGINEER:
WrAIII, NO BM4
' N-iJ- la
H
TWO-PIECE OFOUNDRYE CO.XSTA STANDARD 8" "TOP SECTION WITH RECOMMENDED FOR APPROVAL
REGULAR BASE SECTION LENGTH TO FIT. VALVE NUT EXTENSION
AS REQUIRED (SEE DWG BR46 / PAGE 8090).
RAISED PAVEMENT MARKER TYPE 88 AS Q� ®�
STIMSONITE TWO -WAY BLUE. BY.' � ^�"�"� DATE.' '/�A?
42" MIN CONCRETE BLOCKING
BURY 5a �� A
0
wl, 3"
- CAST IRON TEE. WITH 6" FLANGE SIDE OUTLET.
6" GATE VALVE (FL X MJ) AWWA C -509, RESILIENT SEAT
'TILE IRON PIPE, CLASS 52 CEMENT LINED, LENGTH TO FIT TWO .3/4°
71E RODS. SEE STD DETAIL FOR TIE RODS.
20734 �4,j
�rsrsaE° G \�
NAL EN `I Ib1�
3: 3 1/2000 NO. REVISION
> LUA 05 -065
JAEGER ENGINEERING
9419 South 204th Place
Kent, WA. 98031
Phone No. (253) 850 -0934
Fax No. (253) 850 -0155
BY.' DATE:
BY.' DATE:
BY: DATE:
CITY OF RENTON
DEPARTMENT OF PUBLIC WORKS
WATER & SEWER DETAILS
WEBBER SHORT PLAT
DESIGNED: JJJ DATE: 2/10/05 FILE NAME:
DRAWN: JJJ
CHECKED: JJJ SCALE: NONE FE 800Y.; PAGE;
APPROVED: SHEET: 9 CF: 11
Co U) •337307_